46
Installation Instructions - Relay Box for Infrared Cabins
Installing multiple cabins
EN
Ferrite ring per jack
One jack per connection must be fitted with 1 ferrite ring.
The ferrite ring for jack #1 is included in the scope of delivery for each con-
trol unit and add-on module.
Once the cabins with their custom cabin address (IDs) are connected, the
icon of the connected cabin appears in the footer.
The number corresponds to the cabin currently selected (not the number
of connected cabins).
6.3 Programming the cabin address
The relay box is programmed with cabin address 1 as delivered. To ensure
that EmoTouch 3 detects multiple cabins, the cabin address must be
changed to a different cabin address starting with cabin 2.
To program the cabin addresses, you must open the housings of the relay
boxes and the EmoTouch 3 control unit housing and plug in the S bus lines.
Ensure that you observe the connection sequence.
The connection sequence must start with jack #1 on the EmoTouch 3 cir-
cuit board. See
Jacks – EmoTouch 3 circuit board,
Cabins with incorrect connections will not be detected or displayed on the
control panel.
In installations with EmoTec and EmoStyle control units, relay boxes are
always assigned cabin address 1.
Programming the address
1
Open the relay box’s housing as needed.
2
Open the control unit.
RJ10
RJ14