Warning: Always connect the
sauna oven's neutral conductor.
Tab. 1
2.2.1 Connecting the sauna oven
The electrical connection can
only be carried out by an
approved electrician, observing the
local energy supply company's
guidelines and those of the VDE
(German Electrical Association). We
should advise you at this point that in
the case of a warranty claim, a copy of
the invoice from the electrical company
who carried out the work will be
required.
2.2 Electrical connection
I
n general, there can only be one perma-
nent connection to the power supply network,
to include a device which allows the unit to
be disconnected from the power source with
a contact distance of at least 3 mm from all
terminals.
All electrical installations and connector
cables inside the cabin must be able to
withstand temperatures up to 140°C.
Please use the table below to determine
the required cable diameters for this task.
Attach the power supply lead wire as shown
in Illust. 5 to the power supply terminals of
the control unit. Connection instructions are
printed directly in the control unit.
Assemble the sauna oven and the
vaporizer according to the instructions
provided by the manufacturer in front of the
air intake opening. Lead the silicon lines
and electrical conduits to their respective
terminals on the control unit and connect
them according to the circuit diagram
printed there.
Please note: If no electrical conduits are
present, drill a hole with a diameter of 10
mm next to the air intake opening and lead
the oven control cables through this hole
to their corresponding terminals (U V W) in
the control unit. To protect the silicon lines
from external influences, install them in a
shielded fashion. For this task, use a fitting
cable or simple PVC conduit and lead the
silicon cable through it to the control unit
2.2.3 Connecting the sauna lamp
The sauna lamp must be splashproof (by
Standard IP54) and suitable for
temperatures up to 140°C. The sauna
lamp can be mounted anywhere except in
the area of the rising hot air above the oven.
.
minimum diameter in mm² (copper wire)
connection to 380 V 3N AC
connector
capacity in
KW
appropriate for
cabin sizes
in m³
power supply lead wire
to the control unit
oven connector cable
control unit for oven
safety fuse
capacity in A
4,5
4 - 6
5 x 2,5 mm²
5 x 1,5 mm²
3 x 16
6,0 6 - 10 5 x 2,5 mm²
5 x 1,5 mm²
3 x 16
7,5
8 - 12
5 x 2,5 mm²
5 x 1,5 mm²
3 x 16
9,010
- 14
5 x 2,5 mm²
5 x 1,5 mm²
3 x 16