E90-803-001-005-01 – Rev 4
- 17 -
Flame is pulsating
Faulty or dirty nozzle
Excessive flue draught.
2) Measure draught.
Replace nozzle.
Reset combustion or
adjust draught stabilizer
(if fitted).
Smoking Flame
Faulty nozzle.
Combustion not set
correctly.
Insufficient air.
Fuel pressure too low
Check combustion.
3) Check combustion.
4) Check fuel pressure.
Replace nozzle.
Reset combustion
Increase air setting.
Check ventilation.
Increase fuel pressure.
Burner keeps
bringing ignition
back on
Flame recognition.
Low sulphur fuel.
Expose photocell to good
ambient (or torch) light.
If the problem disappears
then the problem is with the
flame picture
If the problem does not
disappear then the photocell
must be at fault
As above.
Reset combustion.
Replace photocell.
2) Reset combustion to
give a higher CO
2
level.
WARNING:
Do not keep the lockout reset button permanently pressed as this will overheat the ignition unit. Allow 2 minutes
between reset attempts to allow sufficient cooling.
Please note: The information given above is provided to assist the engineer with any problems they may
encounter. This is not a definitive list.
If further problems are encountered then please contact EOGB Energy Products Ltd for advice.
Technical helpline – Tel: 01480-477066