Страница 1: ...G SYSTEM SLIM BUTTON DUCT ACCESS Installation Maintenance Instructions EMF305M Call 1300 369 273 www enware com Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph 02 8536 4000...
Страница 2: ...efficiency rating 1 year warranty OPTIONS available on request Sentinel Flushing Every 12 or 24 hours Water Supply 350 kPa Connection Inlet BSP 15mm Minimum Water Supply Line Size 20mm Mains Powered...
Страница 3: ...led min 300mm above wall hung urinal and 450mm above continuous wall urinals Pipe work to the valve fixture must be sized according to water service rule calculations and simultaneous demand requireme...
Страница 4: ...RE 1 5 Note a wall thickness of 55mm is required to fit the adaptor 9 Fit mounting plate with locknut and red fibre washer on back of wall FIGURE 1 6 Note fixing screws of the clients choice can be us...
Страница 5: ...Valve Air Gap 600 MAX TROUGH 1 9 INSTALLATION OF AIR GAP EMFS10 Air gap must be installed vertically to prevent leakage Fit air gap to solenoid use thread tape or similar to seal Fit sparge 25mm pipe...
Страница 6: ...o Backplate Filter Union Connection Nipple Transformer Red Fibre Washer Tail Shut off valve Backnut EMDS800 24V Transformer 1 8M Lead EMFS300 Switch Piezo 22MM S S Urinal EMS804 Solenoid 3 8 24V AC EN...
Страница 7: ...valve Clean or replace filter Supply pressure issue Ensure pressure delivered to unit is above 200kpa and below 500kPa dynamic Flush pattern not fully covering bowl Supply pressure issue Ensure pressu...