Before proceeding with installation ensure all operating & dimensional specifications are suitable for the intended installation. 

1.1  INSTALLATION COMPLIANCE REQUIREMENTS

Enware product’s must be installed in accordance with 

AS/NZS 3500.1 & AS/NZS3500.2 – Plumbing and Drainage, 
the Plumbing Code of Australia as well as imposed Local and 
State / Territory Legislative requirements and the manufacturers 
instructions.

The following clauses must be observed for a compliant installation 

and correct operation of Enware tapware:

Water Services

Plumbing Code of Australia:  

Part B1 Cold Water Services

AS / NZS 3500.1-2003 Water Services;
•  Section 3.3.2 Pressure at outlets (min 200kPa is required for  

  valve to operate)

•  Section 3.3.4 Max. pressure within buildings (500kPa  

 operating)

•  Section 3.4 Velocity Requirement (Max 3.0m/s)
•  Section 16 Testing and Commissioning; Flushing,  

  Hydrostatic testing, cleaning & disinfection of water services.

NOTE: Enware’s WC flushing units have Watermark License to 

ATS5200.020 (For Flushing Valves for Water Closets and Urinals - 
For use with Mains Supply), ATS5200.030 (Solenoid Valves)  and 
WELS registered to AS/NZS 6400

IMPORTANT TECHNICAL REQUIREMENTS

To ensure that the unit works correctly, it is important to ensure that 

the site and location of installation meets the hydraulic requirements 
of AS/NZS 3500.1. Also there must be:

•  Minimum 20mm copper supply line for 1 stall or up to  

  450mm wall space. 600mm of wall space may require  
  25mm supply

•   Minimum 200kPa for valve to operate 

  NOTE: WELS Flush Volume only achieved at 350kPa

•   No more than 1 valve per urinal OR 600mm wall space
•   Flush valve must be no more than 2m above ground level
•  Flush valve should be installed min 300mm above wall 

  hung urinal and 450mm above continuous wall urinals

Pipe work to the valve fixture must be sized according to water 

service rule calculations and simultaneous demand requirements.   
To ensure that the pipeline reticulation system for the valve is 
designed correctly for the satisfactory  performance of the valve  
a Hydraulic services Consultant and/or Engineer (or other 
personnel appropriately qualified in hydraulic services design) must  
be engaged.

1.2 INSTALLATION INSTRUCTIONS

1.   Separate parts from packaging & check each part  

(figure 2.1). Parts will separate as shown in figure 1.2. Pay 
attention to the different models variations. Make sure all parts 
are accounted for before discarding any packaging material. 
If any parts are missing, do not attempt to install your flushing 
system until missing parts are obtained. 

2.   Flush water supply lines thoroughly before installing the flush 

valve. Do not allow dirt, Teflon tape or metal particles to enter the 
unit. 

3.   Shut off water supply and ensure shut off valve is closed  

on flushing system.

4.  Decide on appropriate location combining piezo operation and 

valve placement. Install height of between 1-1.5m recommended 
for piezo placement. 

5.  Cut  a 30mm hole in the wall for piezo assembly and an 

appropriate gap in pipe work in which to fix the valve. 
(FIGURE 1.1)

  

Note

Note

: 20mm (min) inlet pipe with 1/2” BSP (male) adaptor 

required for install.  

 

Note

: piezo can be installed away from valve box where 

necessary, i.e. flush valve in wall cavity with activation on different 
wall. Extensions can be purchased if required. AS3500.1 
requirements are still required to be met.

6.  Connect the shut off valve and upper section of the union (as 

shown) (FIGURE 1.2 and 1.3)

FIGURE 1.2

FIGURE 1.3

UPPER 

SECTION OF 

FLUSH VALVE

LOWER 

SECTION OF 

FLUSH VALVE

SPARGE 

CONNECTION 

(ADAPTOR OR AIR 

GAP)

FIGURE 1.1

Ø30

INSTALLATION INSTRUCTIONS

Содержание EMF305M

Страница 1: ...G SYSTEM SLIM BUTTON DUCT ACCESS Installation Maintenance Instructions EMF305M Call 1300 369 273 www enware com Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph 02 8536 4000...

Страница 2: ...efficiency rating 1 year warranty OPTIONS available on request Sentinel Flushing Every 12 or 24 hours Water Supply 350 kPa Connection Inlet BSP 15mm Minimum Water Supply Line Size 20mm Mains Powered...

Страница 3: ...led min 300mm above wall hung urinal and 450mm above continuous wall urinals Pipe work to the valve fixture must be sized according to water service rule calculations and simultaneous demand requireme...

Страница 4: ...RE 1 5 Note a wall thickness of 55mm is required to fit the adaptor 9 Fit mounting plate with locknut and red fibre washer on back of wall FIGURE 1 6 Note fixing screws of the clients choice can be us...

Страница 5: ...Valve Air Gap 600 MAX TROUGH 1 9 INSTALLATION OF AIR GAP EMFS10 Air gap must be installed vertically to prevent leakage Fit air gap to solenoid use thread tape or similar to seal Fit sparge 25mm pipe...

Страница 6: ...o Backplate Filter Union Connection Nipple Transformer Red Fibre Washer Tail Shut off valve Backnut EMDS800 24V Transformer 1 8M Lead EMFS300 Switch Piezo 22MM S S Urinal EMS804 Solenoid 3 8 24V AC EN...

Страница 7: ...valve Clean or replace filter Supply pressure issue Ensure pressure delivered to unit is above 200kpa and below 500kPa dynamic Flush pattern not fully covering bowl Supply pressure issue Ensure pressu...

Страница 8: ......

Отзывы: