ENVISION CONSOLE INSTALLATION MANUAL

BACnet Variables

Envision Console Controls

The variables will be listed with the point type and instance 
preceding the variable name. 

Analog Input (Type 0)

0:1 

Space Temp

 

[Read only, shows the space temperature]

0:2 

Discharge Air Temp

 

[Read only, field mounted sensor unless supplied  

 

 

as a factory special]

0:3 

Effective Clg Setpt

 

[Read only, shows the active cooling setpoint]

0:4 

Effective Htg Setpt

 

[Read only, shows the active heating setpoint]

0:5 

Space Humidity

 

[Read]

0:6 

Water Coil Temp

 

[Read, shows the refrigerant temperature at its

 

coldest, for predictive freeze condition detection]

0:7 

Low Temp Limit

 

[Read, shows the water coil low temperature (freeze

 

sensing) limit that will result in unit shutdown.]

0:8 

ECM Cmd Output

 

[Read, shows the commanded speed (0-100%) of 

 

the ECM Blower]

0:9 

Alarms Enumerated

 

[Read only, 0=no alarms, 1=condensate alarm,

 

2=Compressor Hi Discharge Pressure alarm,

 

3=Compressor low Suction Pressure alarm,

 

4=Freeze sensing alarm, 8=Faulty Freeze 

Sensor  

 

alarm, 9=Loss of Charge]

0:10  AO2 Value

 

[Read, shows the output value (0-100%) of AO2]

Analog Output (Type 1)

1:1 

Space Setpoint

 

[Write, Raise and lower the heating and cooling

 

setpoints from a single command point(volatile, 

 

reverts to ‘uncommanded’ after power outage).]

1:2 

ECM Fan Ovrd

 

[Write, allows network direct control of the ECM 

 

blower speed (volatile, reverts to ‘uncommanded’ 

 

after power outage)]

1:3 

AO2 Override

 

[Write, allows network direct control of the Analog  

 

Output 2, volatile, reverts to ‘uncommanded’ after 

 

power outage)]

1:4 

Space temp Ovrd

 

[Write, allows the network to send space

 

temperature values to the heat pump controller, 

 

volatile, these will supersede any temperature  

 

 

sensor connected to the space temperature Analog 

 

Input.]

Analog Value (Type 2)

2:1 

Occupied Cool

 

[Write, Cooling setpoint in Occupied mode]

2:2 

Unoccupied Cool

 

[Write, Cooling setpoint in Unoccupied mode]

2:3 

Occupied Heat

 

[Write, Heating setpoint in Occupied mode]

2:4  

Unoccupied Heat

 

[Write, Heating setpoint in Unoccupied mode]

2:5 

Temporary Occ Time

 

[Write, set the duration of the temporary occupancy 

 

timer which is initiated by pressing the button on the 

 

zone sensor]

2:6 

Remote Setpt Span

 

[Write, sets the offset range that the setpoint knob 

 

on the zone sensor may apply to the effective Htg/

 

Clg setpoints]

2:7 

Remote Setpt Bias

 

[Write, biases the entire readjust range of the

 

remote setpoint adjust to allow zeroing from the

 

network.]

2:8 

Space Temp Offset

 

[Write, Adds an offset to the Space Temp value for 

 

calibration]

2:9 

Dehumidify Setpt

 

[Write, sets the humidity value that will cause the 

 

heat pump to enter passive dehumidification]

2:10  Low Temp Limit Adj

 

[Write, sets the water coil low temperature (freeze 

 

sensing) limit for shutdown]

Binary Input (Type 3)

3:1 

Fan Cmd Status

 

[Read, show the commanded condition of the Fan

 

Output,Inactive=Off, Active=On]

3:2 

Comp Cmd Status

 

[Read, show the commanded condition of the 

 

Compressor Output, Inactive=Off, Active=On]

3:3 

Comp Hi Capacity Cmd

 

[Read, show the commanded condition of the ‘Hi 

 

Capacity’ Compressor control, Inactive=Off, 

 

Active=On.]

3:4 

Reversing Valve

 

[Read, show the commanded condition of the 

 

Reversing Valve Output, Inactive =Heating,

 

Active =Cooling]

3:5 

Accessory 1 Output

 

[Read, Shows the commanded value of the X1

 

(Accessory

3:8 

Alarm Status

 

[Read, shows the in alarm/out of alarm status, 

 

Inactive=Off, Active=On]

Содержание R-410A Residential

Страница 1: ...formation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Страница 2: ......

Страница 3: ...Ground Water Systems 17 Electrical Connections 18 Auxiliary Heat Ratings 18 Unit Electrical Data 19 Fan Performance Table 19 Wiring Schematics 20 24 Envision Console Controls 25 39 Unit Startup Notes...

Страница 4: ...Range 3 No Coating Extended Range Piping Option 4 No Coating Standard Range L Left R Right N A with chassis only Sound Kit A None Voltage B Blanket 0 208 230 60 1 2 265 60 1 Auxilliary Electric heat...

Страница 5: ...the packag ing if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Wa...

Страница 6: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Страница 7: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Страница 8: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Страница 9: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Страница 10: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3...

Страница 11: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Страница 12: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA...

Страница 13: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Страница 14: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Страница 15: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Страница 16: ...inet repositioning pieces 4 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Страница 17: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Страница 18: ...pliance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW1 Switch 2 to the WELL position Refer to the Dip Switch Field Selection table Sl...

Страница 19: ...L S X2 X1 W2 Field Connections Unit Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL SHUTDOWN NIGHT SETBACK LOAD SHED Requires common connections or 24 VAC for activation Red Bl...

Страница 20: ...500 fpm by 0 16 in wg Unit Electrical Data Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA 09 208 230 60 1 197 253 6 4 4 1 21 0 0 50...

Страница 21: ...White 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low...

Страница 22: ...ack 27 RB 4 2 5 Red EH T2 T1 L2 White White L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blu...

Страница 23: ...ated ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standar...

Страница 24: ...g information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red 32 Handi Box Ground Lug Unit...

Страница 25: ...eeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for use with a wall mounted thermostat A23 A13 A...

Страница 26: ...tional Medium User Interface MUI can be used as a field service tool Standalone Unit Mounted Digital Dial Sensor Remote Mounted Standard Thermostat Remote Mounted Sensor FX10 w N2 FX10 Control functio...

Страница 27: ...he Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is locat...

Страница 28: ...e sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum c...

Страница 29: ...r Coil Low Temperature Freeze Sensing Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compresso...

Страница 30: ...talled emergency heat in the event that the compressor is locked out This input can also be commanded on from a BAS as needed An alarm history can be viewed through the MUI and will be held in memory...

Страница 31: ...or becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected This should be displayed as an alarm on the BAS and the MUI This alarm will be repor...

Страница 32: ...capacity for a minimum of 30 seconds before the full capacity com pressor output can be enabled During low capacity compressor operation the ECM2 blower will operate in medium speed and will operate...

Страница 33: ...arm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu Each fault type will be displayed in the history menu with a...

Страница 34: ...ter to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History WFI Envision Series PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input O...

Страница 35: ...p 0 Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occur...

Страница 36: ...ting Freeze Sensing Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Sensing Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Co...

Страница 37: ...Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt...

Страница 38: ...9 Loss of Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value...

Страница 39: ...network to send space temperature values to the heat pump controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupi...

Страница 40: ...k command equivalent of a thermostatic G call 14 3 Compressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalen...

Страница 41: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Страница 42: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Страница 43: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Страница 44: ...85 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EXPANSIO...

Страница 45: ...09 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2...

Страница 46: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Страница 47: ......

Страница 48: ...nace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continu...

Отзывы: