Optional FX10 Control

The optional FX10 control provides unparalleled capability 
in several areas including performance monitoring, zoning, 
humidity, energy management, and service diagnosis, and 
then communicates it all thru standard DDC protocols like 
N2, Lon and BACnet (MS/TP @ 19,200 Baud rate).

The most unique feature is integrating the FX10 into the 
Envision series as both the heat pump and DDC controller 
providing both a cost advantage and providing features 
not typically found on WLHP controls. This integration 
allows heat pump monitoring sensors, status and service 
diagnosis faults to be communicated thru the DDC direct 
to the building automation system (BAS), giving building 
supervisors detailed and accurate information on every 
piece of equipment without removing an access panel.

FX10 Advanced Control Overview

The Johnson Controls FX10 board is specifically designed 
for commercial heat pumps and provides control of the 
entire unit as well as input ports for Open N2, LonTalk, 
BACnet (MS/TP @ 19,200 Baud rate) communication 
protocols as well as an input port for a user interface. The 
user interface is an accessory item that can be used to aid 
in diagnostics and unit setup. A 16-pin low voltage terminal 
board provides terminals for common field connections. 
The FX10 Control provides:

Operational sequencing

• 

High and low-pressure switch monitoring 

• 

General lockout

• 

Water Coil Low Temperature (Freeze Sensing) 

• 

Condensate overflow sensing 

• 

Lockout mode control 

• 

Emergency shutdown mode 

• 

Random start and short cycle protection

• 

Short Cycle Protection

Allows a minimum compressor “off” time of four minutes 
and a minimum “on” time of two minutes.

Random Start 

A delay of 1 to 120 seconds is generated after each power-
up to prevent simultaneous startup of all units within a 
building after the release from an unoccupied cycle or 
power loss.

Emergency Shutdown 

A field-applied dry contact can be used to place the con-
trol into emergency shutdown mode. During this mode, all 
outputs on the board are disabled.

Water Coil Low Temperature (Freeze Sensing) Limit 

Field selectable for 15° or 30°F (-9° or -1°C)

 
Installation Options 

Standalone controlled by standard room thermostat

• 

Standalone with a Zone Temperature Sensor (must  

• 
  have user interface to change set points beyond the  
  a/- 5°F)

Integrated into BAS by adding communication module

• 

Accessory Outputs 

Quantity 2. One cycled with fan, other with compressor.

User Interface

4 x 20 backlit LCD.

Optional Plug-in Communication Modules - 
(compatible with standard BAS protocols) 

Open N2

• 

LonTalk

• 

BACnet (MS/TP @ 19,200 Baud rate)

• 

Display 

Requires DLI Card/Kit. Up to 2 displays, either 1 local and 
1 remote, or 2 remote. (A 2-display configuration requires 
identical displays.) Local display can be up to 3 meters 
from the controller, power supply, and data communica-
tion. Remote display can be up to 300 meters from the 
controller. Remote display must be independently powered 
with data communication done via 3 pole shielded cable.

Envision Console Controls

Main FX 10 Board

Содержание R-410A Residential

Страница 1: ...formation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Страница 2: ......

Страница 3: ...Ground Water Systems 17 Electrical Connections 18 Auxiliary Heat Ratings 18 Unit Electrical Data 19 Fan Performance Table 19 Wiring Schematics 20 24 Envision Console Controls 25 39 Unit Startup Notes...

Страница 4: ...Range 3 No Coating Extended Range Piping Option 4 No Coating Standard Range L Left R Right N A with chassis only Sound Kit A None Voltage B Blanket 0 208 230 60 1 2 265 60 1 Auxilliary Electric heat...

Страница 5: ...the packag ing if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Wa...

Страница 6: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Страница 7: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Страница 8: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Страница 9: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Страница 10: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3...

Страница 11: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Страница 12: ...47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA 3 2 3 3 7 5 1 0 E3 113AA 3 1 3AA 113AA 3 47 B3 1 B 3 1 23 A B3 2 7 1 31B7 E B3 CB 4 B E B3 7 4 B B7 0 19 B3 1 3AA 113AA...

Страница 13: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Страница 14: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Страница 15: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Страница 16: ...inet repositioning pieces 4 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Страница 17: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Страница 18: ...pliance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW1 Switch 2 to the WELL position Refer to the Dip Switch Field Selection table Sl...

Страница 19: ...L S X2 X1 W2 Field Connections Unit Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL SHUTDOWN NIGHT SETBACK LOAD SHED Requires common connections or 24 VAC for activation Red Bl...

Страница 20: ...500 fpm by 0 16 in wg Unit Electrical Data Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA 09 208 230 60 1 197 253 6 4 4 1 21 0 0 50...

Страница 21: ...White 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low...

Страница 22: ...ack 27 RB 4 2 5 Red EH T2 T1 L2 White White L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blu...

Страница 23: ...ated ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standar...

Страница 24: ...g information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red 32 Handi Box Ground Lug Unit...

Страница 25: ...eeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for use with a wall mounted thermostat A23 A13 A...

Страница 26: ...tional Medium User Interface MUI can be used as a field service tool Standalone Unit Mounted Digital Dial Sensor Remote Mounted Standard Thermostat Remote Mounted Sensor FX10 w N2 FX10 Control functio...

Страница 27: ...he Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is locat...

Страница 28: ...e sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum c...

Страница 29: ...r Coil Low Temperature Freeze Sensing Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compresso...

Страница 30: ...talled emergency heat in the event that the compressor is locked out This input can also be commanded on from a BAS as needed An alarm history can be viewed through the MUI and will be held in memory...

Страница 31: ...or becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected This should be displayed as an alarm on the BAS and the MUI This alarm will be repor...

Страница 32: ...capacity for a minimum of 30 seconds before the full capacity com pressor output can be enabled During low capacity compressor operation the ECM2 blower will operate in medium speed and will operate...

Страница 33: ...arm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu Each fault type will be displayed in the history menu with a...

Страница 34: ...ter to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History WFI Envision Series PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input O...

Страница 35: ...p 0 Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occur...

Страница 36: ...ting Freeze Sensing Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Sensing Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Co...

Страница 37: ...Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt...

Страница 38: ...9 Loss of Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value...

Страница 39: ...network to send space temperature values to the heat pump controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupi...

Страница 40: ...k command equivalent of a thermostatic G call 14 3 Compressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalen...

Страница 41: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Страница 42: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Страница 43: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Страница 44: ...85 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EXPANSIO...

Страница 45: ...09 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2...

Страница 46: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Страница 47: ......

Страница 48: ...nace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continu...

Отзывы: