Aurora ‘Advanced’ Control Features

The Aurora ‘Advanced’ 

Control system expands on 

the capability of the Aurora 

‘Base’ Control (ABC) 

by adding the Aurora 

Expansion Board (AXB).

All of the preceding 

features of the Aurora 

‘Base’ Control are included. 

The following control 

description is of the 

additional features and 

capability of the Aurora 

advanced  control. 

It is highly recommended the 

installing/servicing contractor obtain 

an Aurora Interface and Diagnostic 

Tool (AID) and specialized training 

before attempting to install or service 

an Aurora ‘Advanced’ control system. 

The additional AXB features include the following:

AXB DIP Switch 

DIP 1 - ID

: This is the AXB ModBus ID and should always 

read On.

DIP 2 & 3 - Future Use

DIP 4 & 5 - Accessory Relay2

: A second, DIP configurable, 

accessory relay is provided that can be cycled with the 

compressor 1 or 2 , blower, or the Dehumidifier (DH) 

input. This is to complement the Accessory 1 Relay on 

the ABC board.

Position

DIP 4

DIP 5

Description

1

ON

ON

Cycles with Fan or ECM (or G)

2

OFF

ON

Cycles with CC1 first stage of compressor 

or compressor spd 6

3

ON

OFF

Cycles with CC2 second stage of 

compressor or compressor spd 7-12

4

OFF

OFF

Cycles with DH input from ABC board

Advanced Hot Water Generator Control 
(Domestic Hot Water Option)

In lieu of the ‘Base Hot Water Generator Control’, the 

Advanced features an AID Tool selectable temperature limit 

and microprocessor control of the process. This will maximize 

hot water generation and prevent undesirable energy use. An 

alert will occur when the hot water input temperature is at 

or above setpoint (100°F - 140°F) for 30 continuous seconds 

(130°F is the default setting). This alert will appear as an E15 

on the AID Tool and the hot water pump de-energizes. Hot 

water pump operations resume on the next compressor cycle 

or after 15 minutes of continuous compressor operation during 

the current thermostat demand cycle. Since compressor hot 

gas temperature is dependent on loop temperature in cooling 

mode, loop temperatures may be too low to allow proper 

heating of water. The control will monitor water and refrigerant 

temperatures to determine if conditions are satisfactory for 

heating water. LED1 (red LED) will flash code 15 when the 

DHW limit is reached and when conditions are not favorable 

for water heating. Error code 15 will also be displayed on the 

AID Tool in the fault screen. This flash code is a noncritical 

alert and does not necessarily indicate a problem.

Compressor Monitoring

The AXB includes two current transducers to monitor the 

compressor current and starting characteristics. Open 

circuits or welded contactor faults will be detected. A fault 

will produce an E10 code.

IntelliZone2 Zoning Compatibility 
(Optional IntelliZone2 Zoning)

A dedicated input to connect and communicate with the 

IntelliZone2 (IZ2) zoning system is provided on P7. The is a 

dedicated communication port using a proprietary ModBus 

protocol. An AXB can be added to other selected ABC-only 

systems as well. Then an advanced communicating IntelliZone2 

zoning system can be added to ABC-only systems. Consult the 

IntelliZone2 literature for more information. 

Variable Speed Pump

This input and output are provided to drive and monitor 

a variable speed pump. The VS pump output is a PWM 

signal to drive the variable speed pump. The minimum and 

maximum level are set using the AID Tool. 75% and 100% 

are the default settings respectively. The VS data input 

allows a separate PWM signal to return from the pump 

giving fault and performance information. Fault received 

from the variable speed pump will be displayed as E16.

Modulating Water Valve

This output is provided to drive a modulating water valve.  

Through advanced design the 0-10VDC valve can be 

driven directly from the VS pump output. The minimum 

and maximum level are set in the same way as the VS 

pump using the AID Tool. 75% and 100% are the default 

settings respectively.

Loop Pump Linking

This input and output are provided so that two units can be 

linked together with a common flow center. When either unit 

has a call for loop pump, both unit’s loop pump relays and 

variable speed pumps are energized. The flow center then can 

simply be wired to either unit. The output from one unit should 

be routed to the input of the other. If daisy chained up to 16 

heat pumps can be wired and linked together in this fashion.

Controls - Aurora cont.

Содержание NCW09-18

Страница 1: ...nformation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Страница 2: ...17 Electrical Connections 18 Electrical Data 19 Auxiliary Heat Ratings 20 Blower Performance 20 Wiring Schematics 21 25 Controls CCM 28 Controls Aurora 29 35 Controls Aurora UPC 36 44 Unit Startup Not...

Страница 3: ...d Option Details SS Standard Option Air Coil Insulation Option 5 AlumiSealTM Extended Range 6 AlumiSealTM Standard Range 7 No Coating Extended Range 8 No Coating Standard Range Sound Kit A None B Blan...

Страница 4: ...the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Wa...

Страница 5: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Страница 6: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Страница 7: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Страница 8: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Страница 9: ...25 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22 6 F...

Страница 10: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Страница 11: ...ATE COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS PAN...

Страница 12: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Страница 13: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Страница 14: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Страница 15: ...abinet repositioning pieces 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Страница 16: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Страница 17: ...emely hard water the owner should be informed that the heat exchanger may require occasional flushing Units with cupronickel heat exchangers are recommended for open loop applications due to the incre...

Страница 18: ...le 208 Volt Operation All Envision Series 208 230 units are factory wired for 230 volt operation For 208 volt operation the red and blue trans former wires must be switched Microprocessor Remote Therm...

Страница 19: ...1 0 2 6 6 7 7 7 10 15 265 60 1 238 292 6 7 4 3 22 0 2 5 6 8 7 9 10 15 12 115 60 1 104 127 14 8 9 5 50 0 4 25 13 8 16 1 25 208 230 60 1 187 253 7 7 4 9 25 0 2 6 7 5 8 8 10 15 265 60 1 238 292 7 0 4 5 2...

Страница 20: ...70 11 3 14 1 25 265 60 1 239 292 2000 2 50 7 55 10 1 12 6 20 15 18 3 kW 208 60 1 197 254 2454 2 45 11 80 14 3 17 8 30 230 60 1 197 254 3000 2 60 13 04 15 6 19 6 35 265 60 1 239 292 3000 2 50 11 32 13...

Страница 21: ...1 T ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Black...

Страница 22: ...ue Wht 36 Blue Wht 35 White 34 Blue T6 FS Yellow 44 Yellow 44 Brown 43 Yellow 13 Page 1 Blue Tan 41 Blue 40 Blue 40 Brown 3 Tan 41 Brown 26 Green 00 Red 39 Gray 42 NOTE 3 NOTE 4 Violet 4 Violet 4 Viol...

Страница 23: ...30 F Com1 LED5 Com2 LED5 Test Mode F1 3A P1 C PWM 1 2 3 4 5 6 7 8 ALM ALG ACC COM ACC NO ACC NC R C G Y1 EH2 C EH1 C CO C R C R Off Fault LED1 R Status LED3 Config LED2 CC2 CC F C R F FG CC CCG CC2 H...

Страница 24: ...Red Status LED LED1 Green Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Delay Fast Fla...

Страница 25: ...G CC2 HI CC2 LO CC2 G REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS Aurora Base Control ABC K1 RV Relay K2 CC Relay K3 CC2 Relay K4 Fan Relay K5 Alarm Relay K6 Acc Relay F R C CC G Y1 C R ES LS P2 EH1 Y G G G...

Страница 26: ...LED LED3 Red Status LED LED1 Green Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Delay...

Страница 27: ...T NET COM 1 2 1 2 LON Network Connections Devices Must Be Wired in Daisy Chain Configuration Page 1 DIP Switch Value 1 2 4 8 ON 1 2 3 4 ZS Sensor Information Each ZS sensor must have a unique address...

Страница 28: ...eed switch The temperature can be controlled by rotating the thermostat control knob The Fan Only setting provides constant fan operation In the Heat mode a call for heat by the thermostat closes the...

Страница 29: ...and 1 second off Additionally when entering test mode LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holdi...

Страница 30: ...ed on The fault type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset...

Страница 31: ...he blower will start immediately upon receiving a thermostat G command If there are no other commands from the thermostat the ECM will run on G speed until the G command is removed Regardless of blowe...

Страница 32: ...AID Tool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes...

Страница 33: ...will monitor water and refrigerant temperatures to determine if conditions are satisfactory for heating water LED1 red LED will flash code 15 when the DHW limit is reached and when conditions are not...

Страница 34: ...Smoke CO Alarm Fault no lockout info only Switch output from Smoke CO sensor Dirty Filter Alarm no lockout info only Output from dirty filter sensor Home Automation 2 E24 HA2 With a closed dry contact...

Страница 35: ...will be noticed from normal cooling Dehumidification mode will be shown on the ABC and the communicating thermostats Fault LED LED1 Red Red Fault LED LED Flash Code Lockout Reset Remove Fault Conditio...

Страница 36: ...ABC heat pump control into our latest water source heat pumps This will allow for a BAS to integrate and communicate to the heat pump thru a choice of 3 different communication protocols The Aurora U...

Страница 37: ...ooling control from a remotely located zone sensor Rnet communication port which allows for multiple Rnet zone sensors 5 to be connected for space temperature averaging if desired Local laptop or BACv...

Страница 38: ...baud rate for the BAS port Mac address is set by 2 rotary dials Aurora Touch Interface Utilizing a touch screen interface the UPC provides a technician the ability to configure and diagnose equipment...

Страница 39: ...ous sec Fault Freeze Detection FP1 5 Yes Hard or Soft Freeze protection sensor has tripped 15 or 30 degF for 30 continuous sec Fault Condensate Overflow 7 Yes Hard or Soft Condensate switch has shown...

Страница 40: ...ay1 A configurable accessory relay on the ABC is provided that can be cycled with the compressor blower or the Dehumidifier DH input A third factory setting cycles the relay with the compressor but de...

Страница 41: ...is provided to optionally drive a modulating water valve Through advanced design a 0 10VDC valve can be driven directly from the VS pump output The mini mum and maximum level are set in the same way...

Страница 42: ...ing cooling liquid line FP1 These sensors allow the measurement of discharge and suction pressures suction and liquid line temperatures as well as superheat and subcooling This information can be disp...

Страница 43: ...t one ZS Pro or ZS Pro F with up to four ZS standard sensors wired to the Rnet port on the UPC for a total of 5 zone sensors The sensors use a precise 10k ohm thermistor with less than 0 18 F drift ov...

Страница 44: ...ycle Temp with VOC or Temp VOC Humidity All Models 12 Vdc 60 mA Temp with CO2 or Temp CO2 Humidity All Models 12 Vdc 15 mA idle to 190 mA CO2 measurement cycle Power Supply A controller supplies the R...

Страница 45: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Страница 46: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Страница 47: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Страница 48: ...500 485 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EX...

Страница 49: ...1 2 1 0 0 9 0 8 0 7 0 6 09 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 1 5 0 9 0 8 0 7 0 6 0 5 12 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 2 0 1 7 1 6 1 5 1 4 1 3 15 3 0 3 3 3 2 3 0 2 9 2 8...

Страница 50: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Страница 51: ...51 ENVISION CONSOLE INSTALLATION MANUAL Notes...

Страница 52: ...Updated Nomenclature and Wiring Schematics ABC and UPC Controls 1 Sept 2015 MA All Obsoleted PSC Option Updated Nomenclature Updated Wiring Schematics 04 Mar 2015 MA All Updated With Aluminum Air Coil...

Страница 53: ...terFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2015 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy...

Отзывы: