ENVISION CONSOLE INSTALLATION MANUAL

Over/Under Voltage Shutdown

 - An over/under voltage 

condition exists when the control voltage is outside the 
range of 18 VAC to 30 VAC. If the over/under voltage 
shutdown lasts for 15 minutes, the lockout and alarm relay 
will be energized. Over/under voltage shutdown is self-
resetting in that if the voltage comes back within range 
of 18 VAC to 30 VAC for at least 0.5 seconds, then normal 
operation is restored.

Operation Description

Power Up

 - The unit will not operate until all the inputs and 

safety controls are checked for normal conditions. The unit 
has a 5 to 80 second random start delay at power up. Then 
the compressor has a 4 minute anti-short cycle delay after 
the random start delay.

Standby

 In standby mode, Y1, Y2, W, DH, and G are not 

active. Input O may be active. The blower and compressor 
will be off.

Heating Operation

Single Compressor Heating, 2nd Stage (Y1, Y2)

 

The compressor will be staged to full capacity 20 seconds 
after Y2 input is received. The ECM blower will shift to high 
speed seconds after the Y2 input is received.

Dual Compressor Heating, 2nd Stage (Y1, Y2)

 

In dual compressor operation, two ABC boards used in 24 
VAC operation, there will be a Y2 call to the Y1 input on the 
second ABC. The compressor will stage to full capacity 30 
seconds after Y1 input is received to the second board. 

Single Compressor Heating, 3rd Stage (Y1, Y2, W)

 

The hot water pump is de-energized and the first stage of 
electric heat is energized 10 seconds after the W command 
is received. If the demand continues the second stage of 
electric heat will be energized after 5 minutes.

Dual Compressor Heating, 3rd Stage (Y1, Y2, W)

 - 

The first stage of electric heat is energized 10 seconds 
after the W command is received.  If the demand continues 
the second stage of electric heat will be energized after 5 
minutes

Emergency Heat (W)

 - The blower will be started on “G” 

speed, 10 seconds later the first stage of electric heat will 
be turned on. 5 seconds after the first stage of electric 
heat is energized the blower will shift to Aux speed. If the 
emergency heat demand is not satisfied after 2 minutes the 
second electric heat stage will be energized.

Blower (G)

 - The blower will start immediately upon 

receiving a thermostat G command. If there are no other 
commands from the thermostat the ECM will run on “G” 
speed until the G command is removed. Regardless of 
blower input (G) from the thermostat, the blower will 
remain on for 30 seconds at the end of each heating cycle.

Cooling Operation

In all cooling operations, the reversing valve directly tracks 
the O input. Thus, anytime the O input is present, the 
reversing valve will be energized.

Single Compressor Cooling, 2nd Stage (Y1, Y2, 0)

 

The compressor will be staged to full capacity 20 seconds 
after Y2 input was received. The ECM blower will shift to high 
speed 15 seconds after the Y2 input was received. 

Dual Compressor Cooling, 2nd Stage (Y1, Y2, O)

 

In dual compressor operation, two ABC boards used in 24 
VAC operation, there will be a Y2 call to the Y1 input on the 
second ABC. The compressor will stage to full capacity 30 
seconds after Y1 input is received to the second board. 

Blower (G)

 - The blower will start immediately upon 

receiving a thermostat G command. If there are no other 
commands from the thermostat the ECM will run on “G” 
speed until the G command is removed. Regardless of 
blower input (G) from the thermostat, the blower will 
remain on for 30 seconds at the end of each heating, 
cooling, and emergency heat cycle.

Dehumidification (Y1, O, DH or Y1, Y2, O, DH)

 - When a 

DH command is received from the thermostat during a 
compressor call for cooling the ECM blower speed will be 
reduced by 15% to increase dehumidification.

Emergency Shutdown

 - Four (4) seconds after a valid ES 

input, P2-7 is present, all control outputs will be turned off 
and remain off until the emergency shutdown input is no 
longer present. The first time that the compressor is started 
after the control exits the emergency shutdown mode, 
there will be an anti-short cycle delay followed by a random 
start delay. Input must be tied to common to activate.

Continuous Blower Operation

 - The blower output will 

be energized any time the control has a G input present, 
unless the control has an emergency shutdown input 
present. The blower output will be turned off when G input 
is removed.

Load Shed 

- The LS input disables all outputs with the 

exception of the blower output. When the LS input has been 
cleared, the anti-short cycle timer and random start timer 
will be initiated. Input must be tied to common to activate.

Controls - Aurora cont.

Содержание NCW09-18

Страница 1: ...nformation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Страница 2: ...17 Electrical Connections 18 Electrical Data 19 Auxiliary Heat Ratings 20 Blower Performance 20 Wiring Schematics 21 25 Controls CCM 28 Controls Aurora 29 35 Controls Aurora UPC 36 44 Unit Startup Not...

Страница 3: ...d Option Details SS Standard Option Air Coil Insulation Option 5 AlumiSealTM Extended Range 6 AlumiSealTM Standard Range 7 No Coating Extended Range 8 No Coating Standard Range Sound Kit A None B Blan...

Страница 4: ...the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Wa...

Страница 5: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Страница 6: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Страница 7: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Страница 8: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Страница 9: ...25 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22 6 F...

Страница 10: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Страница 11: ...ATE COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS PAN...

Страница 12: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Страница 13: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Страница 14: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Страница 15: ...abinet repositioning pieces 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Страница 16: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Страница 17: ...emely hard water the owner should be informed that the heat exchanger may require occasional flushing Units with cupronickel heat exchangers are recommended for open loop applications due to the incre...

Страница 18: ...le 208 Volt Operation All Envision Series 208 230 units are factory wired for 230 volt operation For 208 volt operation the red and blue trans former wires must be switched Microprocessor Remote Therm...

Страница 19: ...1 0 2 6 6 7 7 7 10 15 265 60 1 238 292 6 7 4 3 22 0 2 5 6 8 7 9 10 15 12 115 60 1 104 127 14 8 9 5 50 0 4 25 13 8 16 1 25 208 230 60 1 187 253 7 7 4 9 25 0 2 6 7 5 8 8 10 15 265 60 1 238 292 7 0 4 5 2...

Страница 20: ...70 11 3 14 1 25 265 60 1 239 292 2000 2 50 7 55 10 1 12 6 20 15 18 3 kW 208 60 1 197 254 2454 2 45 11 80 14 3 17 8 30 230 60 1 197 254 3000 2 60 13 04 15 6 19 6 35 265 60 1 239 292 3000 2 50 11 32 13...

Страница 21: ...1 T ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Black...

Страница 22: ...ue Wht 36 Blue Wht 35 White 34 Blue T6 FS Yellow 44 Yellow 44 Brown 43 Yellow 13 Page 1 Blue Tan 41 Blue 40 Blue 40 Brown 3 Tan 41 Brown 26 Green 00 Red 39 Gray 42 NOTE 3 NOTE 4 Violet 4 Violet 4 Viol...

Страница 23: ...30 F Com1 LED5 Com2 LED5 Test Mode F1 3A P1 C PWM 1 2 3 4 5 6 7 8 ALM ALG ACC COM ACC NO ACC NC R C G Y1 EH2 C EH1 C CO C R C R Off Fault LED1 R Status LED3 Config LED2 CC2 CC F C R F FG CC CCG CC2 H...

Страница 24: ...Red Status LED LED1 Green Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Delay Fast Fla...

Страница 25: ...G CC2 HI CC2 LO CC2 G REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS Aurora Base Control ABC K1 RV Relay K2 CC Relay K3 CC2 Relay K4 Fan Relay K5 Alarm Relay K6 Acc Relay F R C CC G Y1 C R ES LS P2 EH1 Y G G G...

Страница 26: ...LED LED3 Red Status LED LED1 Green Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Reserved Reserved Load Shed ESD 1 second on and 1 second off Random Start Delay...

Страница 27: ...T NET COM 1 2 1 2 LON Network Connections Devices Must Be Wired in Daisy Chain Configuration Page 1 DIP Switch Value 1 2 4 8 ON 1 2 3 4 ZS Sensor Information Each ZS sensor must have a unique address...

Страница 28: ...eed switch The temperature can be controlled by rotating the thermostat control knob The Fan Only setting provides constant fan operation In the Heat mode a call for heat by the thermostat closes the...

Страница 29: ...and 1 second off Additionally when entering test mode LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holdi...

Страница 30: ...ed on The fault type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset...

Страница 31: ...he blower will start immediately upon receiving a thermostat G command If there are no other commands from the thermostat the ECM will run on G speed until the G command is removed Regardless of blowe...

Страница 32: ...AID Tool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes...

Страница 33: ...will monitor water and refrigerant temperatures to determine if conditions are satisfactory for heating water LED1 red LED will flash code 15 when the DHW limit is reached and when conditions are not...

Страница 34: ...Smoke CO Alarm Fault no lockout info only Switch output from Smoke CO sensor Dirty Filter Alarm no lockout info only Output from dirty filter sensor Home Automation 2 E24 HA2 With a closed dry contact...

Страница 35: ...will be noticed from normal cooling Dehumidification mode will be shown on the ABC and the communicating thermostats Fault LED LED1 Red Red Fault LED LED Flash Code Lockout Reset Remove Fault Conditio...

Страница 36: ...ABC heat pump control into our latest water source heat pumps This will allow for a BAS to integrate and communicate to the heat pump thru a choice of 3 different communication protocols The Aurora U...

Страница 37: ...ooling control from a remotely located zone sensor Rnet communication port which allows for multiple Rnet zone sensors 5 to be connected for space temperature averaging if desired Local laptop or BACv...

Страница 38: ...baud rate for the BAS port Mac address is set by 2 rotary dials Aurora Touch Interface Utilizing a touch screen interface the UPC provides a technician the ability to configure and diagnose equipment...

Страница 39: ...ous sec Fault Freeze Detection FP1 5 Yes Hard or Soft Freeze protection sensor has tripped 15 or 30 degF for 30 continuous sec Fault Condensate Overflow 7 Yes Hard or Soft Condensate switch has shown...

Страница 40: ...ay1 A configurable accessory relay on the ABC is provided that can be cycled with the compressor blower or the Dehumidifier DH input A third factory setting cycles the relay with the compressor but de...

Страница 41: ...is provided to optionally drive a modulating water valve Through advanced design a 0 10VDC valve can be driven directly from the VS pump output The mini mum and maximum level are set in the same way...

Страница 42: ...ing cooling liquid line FP1 These sensors allow the measurement of discharge and suction pressures suction and liquid line temperatures as well as superheat and subcooling This information can be disp...

Страница 43: ...t one ZS Pro or ZS Pro F with up to four ZS standard sensors wired to the Rnet port on the UPC for a total of 5 zone sensors The sensors use a precise 10k ohm thermistor with less than 0 18 F drift ov...

Страница 44: ...ycle Temp with VOC or Temp VOC Humidity All Models 12 Vdc 60 mA Temp with CO2 or Temp CO2 Humidity All Models 12 Vdc 15 mA idle to 190 mA CO2 measurement cycle Power Supply A controller supplies the R...

Страница 45: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Страница 46: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Страница 47: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Страница 48: ...500 485 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EX...

Страница 49: ...1 2 1 0 0 9 0 8 0 7 0 6 09 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 1 5 0 9 0 8 0 7 0 6 0 5 12 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 2 0 1 7 1 6 1 5 1 4 1 3 15 3 0 3 3 3 2 3 0 2 9 2 8...

Страница 50: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Страница 51: ...51 ENVISION CONSOLE INSTALLATION MANUAL Notes...

Страница 52: ...Updated Nomenclature and Wiring Schematics ABC and UPC Controls 1 Sept 2015 MA All Obsoleted PSC Option Updated Nomenclature Updated Wiring Schematics 04 Mar 2015 MA All Updated With Aluminum Air Coil...

Страница 53: ...terFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2015 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy...

Отзывы: