34
ENVISION CONSOLE INSTALLATION MANUAL
Inputs and Outputs Configuration
Field Selectable Options
Freeze Detection Limit Set Point (BI-5)
The freeze detection limit set point input allows you to
adjust the freeze detection limit set point (AI-5). When the
jumper is installed on BI-5 (Wire #24) the freeze detection
limit set point is factory set for 30°F. When the jumper on
BI-5 (Wire #24) is removed the freeze detection limit set
point will be 15°F.
Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior
to the compressor output being energized. Accessory
Output 2 will be energized with the fan output (BO-1).
When the corresponding compressor output is turned
off the accessory output will be deactivated immediately.
These outputs are selectable for normally open or normally
closed operation through the Medium User interface or
through the Building Automation System.
Control Accessories
Zone Sensors
• TAXXJ02 Room Command Module
• TAXXA01 LCD Room Command Module
• A99
Sensor
MUI (LCD User interface) for diagnostics
and commissioning.
• MUIK3 - Panel Mount, Portable
• MUIK4 - Wall Mount
Envision Console Controls cont.
Input Name
Input
Output Name
Output
Zone Temp 1
AI 1
Fan Enable
BO1
Relative Humidity Input
AI 2
Comp – Low Capacity
BO2
Condensate Level
AI 3
Reversing Valve
BO3
Universal Temp Input
AI 4
Comp – Full Capacity
BO4
Water Coil Low Temperature Limit
AI 5
Network Output/EH Output
BO5
Warm/Cool Adjust and Temp Occ
AI 6
Alarm
BO6
Accessory 1 Output
BO7
Occupied
BI 1
Accessory 2 Output
BO8
Emergency Shutdown
BI 2
Network Controlled Output
B09
Stage 1 Low Pressure
BI 3
Network Viewable Input 1
BI 4
ECM2 Fan
PWM1
Water Coil Low Temp Limit Set Point
BI 5
Network Controlled Output
PWM2
Network Viewable Input 2
BI 6
Thermostat Y1
BI 7
Thermostat Y2
BI 8
Thermostat O
BI 9
Thermostat G
B10
Stage 1 High Pressure
BI11
Compressor Proving
BI12
XP10 Expansion Card
Input Name
Input
Output Name
Output
Unused
AI 1
Unused
BO 1
Unused
AI 2
Unused
BO 2
Unused
AI 3
Unused
BO 3
Unused
AI 4
Unused
BO 4
SINGLE and DUAL STAGE WATER-TO-AIR