System Cleaning and Flushing

Cleaning and Flushing

Prior to start up of any heat pump, the water circulating system must be 

cleaned and flushed of all dirt and debris.

If the system is equipped with water shutoff valves, the supply and 

return runouts must be connected together at each unit location (This 

will prevent the introduction of dirt into the unit,  see Figure 7).  The 

system should be filled at the water make-up connection with all air 

vents open.  After filling, vents should be closed.

The contractor should start the main circulator with the pressure reduc-

ing valve makeup open.  Vents should be checked in sequence to bleed 

off any trapped air and to verify circulation through all components of 

the system.

As water circulates through the system, the contractor should check 

and repair any leaks found in the piping system.  Drain(s) at the lowest 

point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same 

rate.  Check the pressure gauge at the pump suction and manually adjust the make-up water valve to hold the same posi-

tive pressure both before and after opening the drain valves.  Flushing should continue for at least two hours, or longer if 

required, until drain water is clean and clear.

The supplemental heater and/or circulator pump, if used, should be shut off.  All drains and vents should be opened to 

completely drain the system.  Short-circuited supply and return runouts should now be connected to the unit supply and 

return connections.

Refill the system with clean water.  Test the system water for acidity and treat as required to leave the water slightly alkaline 

(pH 7.5 to 8.5).  The specified percentage of antifreeze may also be added at this time.  Use commercial grade antifreeze 

designed for HVAC systems only.  Environol™ brand antifreeze is recommended..

Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the sys-

tem from dirty water conditions.  Dirty water will result in system-wide degradation of performance, and solids may clog 

valves, strainers, flow regulators, etc.  Additionally, the heat exchanger may become clogged which reduces compressor 

service life and can cause premature unit failure.

In boiler/tower application, set the loop control panel set points to desired temperatures.  Supply power to all motors and 

start the circulating pumps.  After full flow has been established through all components including the heat rejector (re-

gardless of season),  air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up 

and for air and water balancing.

Ground Source Loop System Checkout

Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is 

needed.  A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from 

the loop itself.  Antifreeze solution is used in most areas to prevent freezing.  Flush the system adequately to remove as 

much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter).  This is 

normally adequate for good system operation.  Loop static pressure may decrease soon after initial installation, due to pipe 

expansion and loop temperature change.  Running the unit for at least 30 minutes after the system has been completely 

purged of air will allow for the “break-in” period.  It may be necessary to adjust static loop pressure (by adding water) after 

the unit has run for the first time.  Loop static pressure will also fluctuate with the seasons.  Pressures will be higher in the 

winter months than during the cooling season.  This fluctuation is normal and should be considered when charging the 

system initially.

Insure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger.  

Usually 2.25-3.0 GPM of flow per ton of cooling capacity is recommended in earth loop applications.

Return Runout

Supply Runout

Mains

Rubber Hose

Runouts Initially
Connected Together

Figure 7:  Flushing with Water

Shutoff Valve Equipped Systems

Содержание NCE09-18

Страница 1: ...nformation Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance Envision Console Installation Manual Geothermal Water Source Heat Pumps R 410A Refrigerant 0 75...

Страница 2: ...d Water Systems 17 Electrical Connections 18 Electrical Data 19 Auxiliary Heat Ratings 20 Blower Performance 20 Wiring Schematics 21 26 Envision Console Controls 27 36 Unit Startup Notes 37 Unit Start...

Страница 3: ...Card 6 FX10 w Lonworks Com Card 7 FX10 w BacNet Com Card Vintage B PSC Blower Aluminum Air Coil C ECM Blower Aluminum Air Coil Non Standard Option Details SS Standard Option Air Coil Insulation Optio...

Страница 4: ...m the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage W...

Страница 5: ...3 3 49 1 11 8 4 3 cm 127 0 31 1 65 2 23 4 88 9 15 6 8 3 124 7 29 8 10 9 09 12 15 18 4 0 5 7 8 1 3 2 6 47 B3 0 193B 47 B3 0 193B 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3 232 B 0 0 19 2 4 B6 C B7 B 0...

Страница 6: ...1 2 5 49 1 11 8 4 3 cm 127 0 32 0 73 9 23 4 88 9 15 6 6 4 124 7 29 8 10 9 09 12 15 18 3 D3 AB71 AB 7 4 0 93 B 0 2 3 13 0 93 3253 4 35 A A6 E 6 7 8 1 4 3 2 5 0 756B 3BC B 4 B 34B 3BC 23B 7 0 BE7AB 3FB3...

Страница 7: ...6 6 1 124 7 30 5 10 9 in 55 0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 47 B3 0 193B 47 B3 0 193B 2 3 1 6 7 8 4 0 5 0 756B 3BC B 4 B 3...

Страница 8: ...2 4 1 7BG 0 B6 A723A 3 31B 71 63 B 23 0 7 3 3AA AE7B16 B7 4 B7 AE7B16 B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 E D B 53 B3 7 A 4F 3 B3 E AB B B7 A G B7 4CA32 4CA32 27A1 31B B7 0...

Страница 9: ...25 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22 6 F...

Страница 10: ...D3A B7 6 A3 97BA 1 23 A B3 2 7 1 31B7 47 B3 6 2G 0 F B7 3 31B 71 63 B B7 0 19 B3 3 C7 32 4 2 3 7 AB B7 CBA723 7 2 3 B7 473 2 7 AB 32 1 B 3 3 D3 4 113AA B 1 B 0 F 2 3 44 AE7B16 1 3AA 113AA 3 3 D32 4 1...

Страница 11: ...ATE COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS PAN...

Страница 12: ...ate mounting height is increased by the thickness of the shims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matti...

Страница 13: ...o the units An air vent must be installed in the water distribution system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The pi...

Страница 14: ...should be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the suppl...

Страница 15: ...abinet repositioning pieces 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the...

Страница 16: ...rotect the sys tem from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchange...

Страница 17: ...emely hard water the owner should be informed that the heat exchanger may require occasional flushing Units with cupronickel heat exchangers are recommended for open loop applications due to the incre...

Страница 18: ...licable 208 Volt Operation All Envision Series 208 230 units are factory wired for 230 volt operation For 208 volt operation the red and blue trans former wires must be switched Microprocessor Remote...

Страница 19: ...7 253 10 4 6 7 33 5 2 6 9 3 10 9 15 265 60 1 238 292 8 7 5 6 28 0 2 5 8 1 9 5 15 HACR circuit breaker in USA only 1 20 14 Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Mi...

Страница 20: ...60 1 197 254 818 2 45 3 93 6 4 8 0 10 230 60 1 197 254 1000 2 60 4 35 7 0 8 7 15 265 60 1 239 291 1000 2 50 3 77 6 3 7 8 10 09 12 2 kW 208 60 1 197 254 1636 2 45 7 86 10 3 12 9 20 230 60 1 197 254 200...

Страница 21: ...White 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low...

Страница 22: ...ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Black 25...

Страница 23: ...e L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blue 38 Blue Wht 36 Blue Wht 35 White 34 Blue...

Страница 24: ...d ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standard d...

Страница 25: ...4 Check installlation wiring information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red...

Страница 26: ...ontacts N O N C 2 Disconnect for15 degree freeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for...

Страница 27: ...ation systems Software can be custom ized for specific projects Optional Medium User Interface MUI can be used as a field service tool Standalone Remote Mounted Standard Thermostat Remote Mounted Sens...

Страница 28: ...Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is located...

Страница 29: ...eze sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum...

Страница 30: ...g General lockout Freeze detection Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compressor o...

Страница 31: ...ed through the MUI and will be held in memory until the unit is power cycled Relative humidity can be read by a 0 5VDC humidity sensor that is displayed over the network If you are using an ECM2 3 blo...

Страница 32: ...emp Limit fault High Pressure BI 11 The high pressure switch shall be a normally closed NC switch that monitors the systems refrigerant pressure If the input senses the high pressure switch is open it...

Страница 33: ...mmand BI 7 from the thermostat the compressor output BO2 will be enabled During the heating cycle the reversing valve will be commanded into the off position Cooling Cycle On a call for cooling the bl...

Страница 34: ...TAXXJ02 Room Command Module TAXXA01 LCD Room Command Module A99 Sensor MUI LCD User interface for diagnostics and commissioning MUIK3 Panel Mount Portable MUIK4 Wall Mount Envision Console Controls c...

Страница 35: ...Water to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History WFI Envision Series PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Inpu...

Страница 36: ...m History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occurred more than 4 tim...

Страница 37: ...able in five models with equipment rated fuses to provide addi tional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect C...

Страница 38: ...ng setpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure...

Страница 39: ...rmance based on entering air temperatures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Am...

Страница 40: ...500 485 for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EX...

Страница 41: ...1 2 1 0 0 9 0 8 0 7 0 6 09 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 1 5 0 9 0 8 0 7 0 6 0 5 12 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 2 0 1 7 1 6 1 5 1 4 1 3 15 3 0 3 3 3 2 3 0 2 9 2 8...

Страница 42: ...ssure Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedu...

Страница 43: ...43 ENVISION CONSOLE INSTALLATION MANUAL Notes...

Страница 44: ...44 ENVISION CONSOLE INSTALLATION MANUAL Pages Description Date By All Updated With Aluminum Air Coils 02 Mar 2014 DS 44 Added Revision Guide 02 Mar 2014 DS Revision Guide...

Страница 45: ...terFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2014 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy...

Отзывы: