116
Appendix | Bellwin
05 (05) read ZDH series build-in temperature
data
Request:
Domain Name
Bytes
Description
Function Code
1
Function code: 05 H
Temperature Id
1
Number of Lines
Respone:
Domain Name
Bytes
Description
Function Code
1
Function code: 05 H
Temperature Id
1
Number of Lines
Temperature Negative
1
0 for positive and 1 for negative
Temperature Value
2
Temperature value
Temperature Unit
1
Units of Temperature, 0 for degrees Celsius,
1 for degrees Fahrenheit
Err:
Feedback
value
Description
-1
Package format error
-2
Parameter error
Example:
Device output (outlet) data to be read:
LRC = F9 = ~(05+01)
Send:
0501F9(CR)
Recv:
050100013900BF