Envirowise XT155H Installation Instructions

 

GENERAL SET UP

Air Handler Return

Dry Air to

Basement

or Crawl Space

Manual

Damper

Envirowise

Supply

Fresh Air

Intake 

(Optional) Motorized

Damper

Indoor

Air Return

Recommended HVAC Ducting Installations

The recommended installation draws air from a dedicated indoor air return and ducts the supply of the  

dehumidifier to the air return of the existing HVAC system. Utilize the optional fresh air ventilation duct to 

provide outside air.

• Install a dedicated 10" air return for the Envirowise XT155H from a central area of the structure.

•  Install an insulated duct from outside to the 6" collar of the Envirowise XT155H to provide fresh air  

ventilation (optional).

•  Duct the supply of the Envirowise XT155H to the return side of the existing HVAC system with a backdraft 

damper. HVAC system interlock is recommended.

•  DO NOT locate return in a bathroom or kitchen.

•  The optional D30 or a system thermostat control with integrated Dehumidification software should be  

located remotely from the dehumidifier and placed in a central location.

Attic Installation - 

Dedicated Return to HVAC Return

Duct the supply of the Envirowise 

XT155H to a 10" x 10" x 10" tee  

damper that is 20 percent open  

to the basement/crawl space.

Basement/Crawl Space Installation -

 Dedicated Return to HVAC Return

Positive Pressurization of crawl 

spaces with dehumidification 

added could potentially bring 

unwanted, unhealthy air into 

living spaces. The recommended 

application with dehumidification 

added is to achieve neutral 

pressure in crawl spaces.

Air Handler

HVAC Supply

Dedicated Ultra-Aire 90 Return to A/C Return

HVAC Return

Fresh Air Intake 

(Optional)

Motorized

Damper

Indoor

Air Return

Envirowise

Supply

HVAC system fan interlock is recommended to  

reduce potential comfort issues with this application.

Create a separate return for the  

Envirowise XT155H in a central  

area of the building.
Installing the supply air from  

the Envirowise XT155H to  

the return of the HVAC system  

requires the HVAC fan to run  

when the Envirowise XT155H  

is operating.

Содержание XT155H

Страница 1: ...de the ultimate in comfort health and property protection through Dehumidification Fresh Air Ventilation Optional Air Filtration TS 978 9 18 Rev A P N EDHUM155 Serial No Install Date Installing Dealer...

Страница 2: ...Determine Ventilation Requirements 14 Controls 15 Filter Instructions 18 Optional Accessories 19 Service 20 Troubleshooting 20 TABLE OF CONTENTS Ingersoll Rand is committed to manufacturing quality p...

Страница 3: ...USE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CARE AND FOLLOW INSTALLATION INSTRUCTIONS DO NO...

Страница 4: ...Pints Day 123 Pints Day Efficiency 7 3 Pints kWh 6 0 Pints kWh Duct Connections 6 Round Inlet 10 Round Inlet 10 Oval Outlet Air Filter MERV 11 Mini Pleat Efficiency 65 ASHRAE Dust Spot Size 16 x 20 x...

Страница 5: ...cation Considerations Allow sufficient clearance to handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal a...

Страница 6: ...using the screws provided The 6 duct should be capped if fresh air is not desired If setting up the unit to provide fresh air ventilation see page 14 Return Air Inlet Attach 10 diameter duct collar t...

Страница 7: ...e relative humidity such as near HVAC supply registers near exterior doors on an outside wall near a window or near a water source The screw terminals on the Envirowise XT155H and the control are labe...

Страница 8: ...e Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety float switch The white leads from...

Страница 9: ...structure Use a minimum 10 diameter round or equivalent rectangular duct for total duct lengths of up to 25 Use a minimum 12 diameter round or equivalent rectangular duct for longer lengths Grills or...

Страница 10: ...em thermostat control with integrated Dehumidification software should be located remotely from the dehumidifier and placed in a central location Attic Installation Dedicated Return to HVAC Return Duc...

Страница 11: ...Motorized Damper Envirowise Supply HVAC Return to HVAC Supply GENERAL SET UP Recommended HVAC Ducting Installations The HVAC fan must be interlocked from the system control to turn on when the dehumi...

Страница 12: ...to utilize multiple rooms to allow air inside the structure to properly circulate Proper air distribution is important to ensure even humidity control and heat distribution throughout the structure A...

Страница 13: ...and outside air conditions When a 6 motorized damper is used a digital control is required It may be necessary to use 8 duct work if additional fresh air is required over 150 CFM In cold climates or a...

Страница 14: ...ecord the required CFM ____________ Determine Ventilation Requirements The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 2016 Use one or both of the options below to determine your v...

Страница 15: ...tallation Guide for instructions on setting up AUX1 contacts on relay panel for Ventilator operation and AUX2 contacts for dehumidifier operation See TCont 824 Installation Guide for instructions on s...

Страница 16: ...cle Timer Automatic fan cycling to ensure dry and clean coils Auto Reboot Resumes operation with prior settings in the event of power failure Envirowise D30 Digital Control Wiring Controls See D30 man...

Страница 17: ...ol DMPR 24VAC Power Transformer Neutral Side Spare Terminal Open Terminal Block Control Operation Compressor ON Fan ON Make contact between 24V and DEHU terminals Compressor OFF Fan ON Make contact be...

Страница 18: ...NG THE FILTER Step 1 The filter door is attached to the cabinet by three hinges Release the latch from the cabinet by pulling it towards the front of the unit The filter door will swing open to gain a...

Страница 19: ...D30 Control W Remote E4037878 MERV 11 Filters 4 Pack E4037885 MERV 11 Filters 12 Pack E4037887 MERV 14 Filter Housing E4037891 MERV 14 Filters 3 Pack E4037905 Pump Kit E4037872 Hang Kit E4037861 6 Mo...

Страница 20: ...ogether the fan only should run Disconnect when complete 8 Jumper a wire from the 24V and DEHU terminal fan and compressor should run Disconnect when complete 9 If this test works then the field contr...

Страница 21: ...or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of performance WARNING ELECTRICAL SHOCK...

Страница 22: ...onnections at control and unit 4 Reset circuit breaker button on dehumidifier WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY...

Страница 23: ...23 Envirowise XT155H Installation Instructions...

Страница 24: ...perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll Rand has a policy...

Отзывы: