AFTER INSTALLING THIS UNIT,

PLEASE PASS ONTO END USER

DO NOT THROW AWAY

Appliance Symbols

Recommendation

Read 

instruction 

manual.

Risk of 

electric 

shock.

General 

hazard 

safety alert.

Disconnect the 

mains supply 

before removing 

this cover.

Wait until all machine 

components have 

completely stopped 

before touching them.

1.  A short piece of flexible ducting, approx 

300mm long is used to connect the unit to 

the ducting system.

2.  Any flexible ducting used must be pulled 

taut.

3.  A minimum distance of 300mm between 

the unit and any sharp bends in duct work.

4.  Ducting should be insulated where it 

passes through unheated areas and voids 

with the equivalent of at least 25 mm of 

a material having a thermal conductivity 

of ≤0.04 W/(m.K) to reduce the possibility 

of condensation forming. Where a duct 

extends externally above roof level the 

section above the roof should be insulated 

or a condensate trap should be fitted just 

below roof level.

5.  Ducts within the building heated envelope 

between the external terminals and 

the unit’s From Atmosphere and To 

Atmosphere ports should be insulated and 

wrapped additionally with a vapour barrier 

outside the insulation.

6.  Where ducts pass through fire barriers, 

they must be appropriately fire stopped 

in accordance with the requirements of 

Building Regulations.

7.  A ducting condensate drain to be fitted on 

vertical To Atmosphere duct work.

8.  Ducting must be installed in such a way 

that resistance to airflow is minimised.

9.  Ducting connected to the From Atmosphere 

and To Atmosphere ports, must be to/

from the external air outside the building 

envelope.

10.  Duct joints to the unit’s duct ports must 

be fixed using a method that ensures a 

long term seal is achieved. If using a short 

piece of flexible ducting secure using a 

hose clamp, do not over tighten.

11.  A minimum distance of 2m exists between 

the external supply and exhaust terminals.

Disconnect the 

mains supply before 

removing this cover.

Before obtaining access to terminals 

or removing this cover, all supply 

circuits must be disconnected.

&

Содержание energiSava 325

Страница 1: ...energiSava 325 INSTALLATION GUIDE FOR ENGINEER INSTALLER...

Страница 2: ...24AWG Stranded Tinned Copper 11 Control and communication cables should not be placed within 50mm or on the same metal cable tray as any 230V lighting or power cables 12 Ensure all cable glands are fu...

Страница 3: ...ust below roof level 5 Ducts within the building heated envelope between the external terminals and the unit s From Atmosphere and To Atmosphere ports should be insulated and wrapped additionally with...

Страница 4: ...eed 7 Boost Speed with Overrun Timer 7 Status Indicator Boost Alert 8 Summer Bypass 8 Summer Kick Up Mode 8 Auto Setback Speed 8 Automatic Frost Protection 8 Integrated Humidity Sensor 8 Wiring Diagra...

Страница 5: ...o the outside Fresh air is drawn into the unit from outside which is warmed by the heat exchange cell and delivered into the living dining and bedroom areas Packaging Contents Inspect the unit when ta...

Страница 6: ...ont to back and side to side 1 Mark a horizontal line on the wall using a spirit level This line will be approximately 95mm below the location of the top face of the unit when fitted excluding duct po...

Страница 7: ...that ducting is connected to the correct ports in line with the icons below EXTRACT FROM DWELLING This duct port is connected to the ducting that carries waste air from the Wet Rooms to the unit TO AT...

Страница 8: ...errun Timer Boost speed increases the extract and supply air flow Boost speed is configured with step less independent fan controls and includes an overrun timer variable between 0 and 60 minutes The...

Страница 9: ...r kick up mode is trigged by summer bypass the increased fan speed can be prevented either manually or automatically Manual This is by means of a volt free switch wired directly into the controller PC...

Страница 10: ...ng and Controls Status Indicator Mains cable must be separate from the communication cables See Important Information Supply wiring diagram 230V Connection at unit L N 12V A B 0V 12V A B 0V L N Fuse D...

Страница 11: ...be used To Boost using switch live a relay is required SWHT BOXRELAY Volt free setback switch or normally open relay contacts 1 1 23 23 Volt free sensor Volt free Setback switching of MVHR controller...

Страница 12: ...inuous speed and boost speed are programmed by placing the controller into program mode via the program run switch and changing the position of the rotary potentiometers When applying power for the fi...

Страница 13: ...n program run switch to centre position to exit commissioning For the commissioning settings to be stored the unit needs to be powered up Continuous Supply Extract Speeds Move program run switch to co...

Страница 14: ...rom the run position to the continuous position from the continuous position to the boost position and back to the run position To ensure that the reset switch movements are registered by the controll...

Страница 15: ...hanger 2 Carefully remove any dust from face of heat exchanger interior of the unit and the bypass if fitted using a vacuum cleaner Do not use water or any other fluids Cleaning Exterior For best resu...

Страница 16: ...G4 ES325 How to Change Filters 1 Remove front cover or filter covers 2 Slide out filters 3 The energiSava 325 filters uses unequal filters Make a note of which side of the unit the filter with the sho...

Страница 17: ...out charges may apply if a fault cannot be identified Supply Only If your product has been supplied by EnviroVent and installed by a third party it is covered by a two year parts only warranty If you...

Страница 18: ...17 energiSava 325 SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL US ON 0345 27 27 810 Serviced By Company Date Notes Service Record...

Страница 19: ...it or the package indicates that disposal of this unit after its lifecycle could harm the environment Do not dispose the unit as unsorted municipal waste it should be disposed by a specialized company...

Страница 20: ...read carefully to ensure simple installation and a long trouble free life for the user Delivering innovative and sustainable ventilation solutions worldwide EnviroVent Ltd EnviroVent House Hornbeam B...

Отзывы: