• Now adjust the individual valves to extract at the appropriate rate
for each wet room. Once this step has been completed it may be
necessary to adjust the unit boost rate again to account for any
increase in pressure.
• Press the SET button once to move on to the next flow rate. The
flashing LED indicates which flow rate is being modified.
A: Extract Boost
B: Supply Boost
C: Extract Trickle
D: Supply Trickle
• Commission the unit in the order shown below, using the previous
steps for adjusting air flow rates and valves.
(When maximum speed setting is reached, the LED will flash faster.
When the minimum speed setting is reached the LED will flash slowly).
Step
Flow Rate
Actions
1
Extract Boost
Lock the valves.
Record the air flow rates.
2
Supply Normal (Trickle)
Lock the valves.
Record the air flow rates.
3
Supply Boost
Do not adjust the valves.
Record the air flow rates.
4
Extract Normal (Trickle)
Do not adjust the valves.
Record the air flow rates.
• When commissioning is complete for all four flow rates, press SET
for 4 seconds to return to normal running mode. If this is not done,
the unit will automatically return to normal running mode after 60
minutes of inactivity and the current settings will be saved.