background image

The Proflame 2 IFC (Figure 6) connects directly to the gas valve, stepper motor, pilot and covection fan with a wiring 

harness. The IFC is mainly powered by 120 VAC but can also run off a battery backup four (4) AA type batteries for 

shorter periods of time. The IFC accepts commands via radio frequency from the Transmitter to operate the appliance 

in accordance with the particular Proflame 2 system configuration. The IFC has a red reset button at the front right 

corner that is used is to synchronize the Transmitter when using the for the first time, or after the batteries have been 

replaced.

Figure 5: Proflame 2 Transmitter LCD Screen.

Figure 6: Integrated Fireplace Controller

Low battery alarm

Key Lock

Room

Temperature

Dimmer ON

Set Point

Temperature/Level/State

Flame ON

Thermostat OFF/
ON/SMART

Comfort fan 

Transmission

Split Flow 

Aux ON

CPI mode

Operating Instructions

i

ntegRateD

 f

iRepLace

 c

ontRoLLeR

 (ifc):

Reset Button

10

Содержание Westley

Страница 1: ...injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html W A R R A N T Y R E G I S T R A T...

Страница 2: ...plumber or gas fitter when installed within the Commonwealth of Massachusetts Other Massachusetts code requirements Flexible connector must not be longer than 36in a shut off valve must be installed o...

Страница 3: ...e performed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 o...

Страница 4: ...e Glass 15 Cleaning the Firebox 15 Replacing the Glass 15 Flashout Guard 15 Cast Door Removal 16 Glass Door Removal 16 Burner Removal 17 Fuel Conversion 18 Initial Installation 20 Preparation for Inst...

Страница 5: ...HEATERS CSA 2 17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES CSA P 4 1 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY This ENVIRO Westley Fireplace Has been certified for use with either natural...

Страница 6: ...Dimensions Rating LabeL Lighting instRuctions Location The rating label and lighting instructions are located on a plate hanging on the back of of the unit 27 1 2 69 9 cm 25 15 16 65 9 cm 19 9 16 49 7...

Страница 7: ...pliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Read the owner s ma...

Страница 8: ...If the shutter is opened or closed all the way and the correct flames cannot be attained turn off the gas and contact the dealer Warning Incorrect shutter adjustment may lead to improper combustion wh...

Страница 9: ...gure 4 The Transmitter is powered by three 3 AAA type batteries A Mode Key is provided to Index between the features and a Thermostat Key is used to turn on off or index through Thermostat functions F...

Страница 10: ...the particular Proflame 2 system configuration The IFC has a red reset button at the front right corner that is used is to synchronize the Transmitter when using the for the first time or after the b...

Страница 11: ...display will show all active Icons on the screen A single beep from the IFC will confirm reception of the command and will commence to first ignite the pilot light followed by the main burner This sh...

Страница 12: ...e difference between the set point temperature and the actual room temperatures As the room temperature gets closer to the set point the Smart Function will modulate the flame down To activate this fu...

Страница 13: ...ure 4 to index to the fan control icon Figure 13 Use the UP DOWN arrow keys to turn on off or adjust the fan speed Figure 13 A single beep from the IFC will confirm the command has been received Figur...

Страница 14: ...the number of changes to the room thermostat set point etc When the Transmitter batteries are low a Bettery Icon will appear on the LCD display of the Transmitter see Figure 17 before all battery pow...

Страница 15: ...Ion log set InstallatIon section If any logs are damaged contact your nearest ENVIRO dealer RepLacing the gLass The glass in the fireplace is a high temperature ceramic If the glass is damaged in any...

Страница 16: ...hown in Figure 22 To replace the glass door simply reverse the above procedure Warning Do not touch or attempt to remove the glass door if the fireplace is not completely cold WARNING Never operate th...

Страница 17: ...ear burner screws using a T20 screwdriver 5 Unsrew the front burner bolt located in the middle of the front row of burner holes using a 5 32 Allen head screwdriver or wrench 6 Slide the burner to the...

Страница 18: ...on kit If any parts have been damaged or are missing contact your dealer distributor or courier company to have them replaced before starting this installation Maintenance And Service Conversion Kit I...

Страница 19: ...ved Teflon tape NEVER USE AN OPEN FLAME WHEN TESTING FOR LEAKS 12 Relight the pilot and confirm the flame properly covers the flame sensor see Figure 27 Should the pilot require adjustment turn the ad...

Страница 20: ...ll or ceiling joist Check stove and flue system clearance requirements Locate the stove where it can be accessed by a gas supply line Locate the stove in a large and open room that is centrally locate...

Страница 21: ...not be recessed into a wall or siding WARNING This gas appliance must not be connected to a chimney flue serving a separate solid burning appliances Figure 29 Vent Framing For Wall or Ceiling DiRect v...

Страница 22: ...6DVA FF 4F Flat flashing 46DVA VCH SVT High wind vertical termination 4DHCS 4DT HC 46DVA HC HT High wind horizontal termination 4DT HKA 4DT HKB 46DVA KHC 4HTK Horizontal termination kit 4DT CCKA 46DVA...

Страница 23: ...y be opened C 12 in 30 cm Clearance from permanently closed window to prevent condensation D 24 in 60 cm Vertical clearance to ventilated soffit located above the terminal within a horizontal distance...

Страница 24: ...E until the required setting is inline with the finger catch Refer to the following Allowable Venting Configuration graphs for the required restrictor setting The proper setting is crucial for an effi...

Страница 25: ...Length Approved through wall thimble 2 61 cm length NG 3 91 cm length LP 12 30 5 cm Maximum Horizontal Length 5 12 7 cm Minimum Rear Clearance Exterior Wall 55 5 141 cm Minimum Height NG 67 5 171 cm...

Страница 26: ...shown in Figures 35 36 In addition to what is shown if a 90 elbow is used in the horizontal plane 3 ft 91 4cm must be subtracted from the allowable horizontal run for each 45 elbow 1 5ft 45 7cm must...

Страница 27: ...17 18 19 20 21 22 23 24 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 HORIZONTAL RUN ft VERTICAL RISE Restrictor Setting 1 No Restriction 0 INSTALLATION PROHIBITED Min 3 Section Required Propane...

Страница 28: ...TAL RUN ft VERTICAL RISE 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 INSTALLATION PROHIBITED Restrictor Setting 1 Restrictor Setting 3 Restrictor Setting 2 INSTALLATION PROHIBITED Natural Gas...

Страница 29: ...2 1 HORIZONTAL RUN ft VERTICAL RISE 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 INSTALLATION PROHIBITED Restrictor Setting 1 Restrictor Setting 2 INSTALLATION PROHIBITED Propane LP Initial I...

Страница 30: ...he air gap prevents excessive heat from possibly melting the vinyl siding 5 Horizontal pipes must be supported every 3 feet 914 mm Plumber s all round strap will suffice 6 When running horizontal pipe...

Страница 31: ...he vent termination should be pointing up Run a bead of non hardening mastic around the edges of the vent cap to make a seal with the wall Ensure the proper clearances to combustibles have been mainta...

Страница 32: ...the base of the flashing to the roof with roofing nails Use a non hardening sealant between the uphill edge of the flashing and the roof Insure the roofing material overlaps the top edge of the flashi...

Страница 33: ...oors see Figure 41 The opening should be framed to 10 254 mm x 10 254 mm inside dimensions in the same manner as shown in Figure 29 4 Any occupied areas above the first floor including closets and sto...

Страница 34: ...adaptor so the wires exit to the rear of the fireplace Slide the Drafthood Adaptor over the outlet pipe of the fireplace until the bottom of the adaptor collar stops on the top of the outlet The Draft...

Страница 35: ...removed from the Drafthood Adaptor for this modification Figure 43 Step 2 Strip off approx 1 4 of insulation from the wire ends Step 3 Remove the ON OFF terminal block from the X4 port on the IFC Figu...

Страница 36: ...must be connected to the chimney vent using a 4 10 cm single wall flexible venting When an existing masonry chimney is utilized for the venting it is required the drafthood be connected to an approved...

Страница 37: ...48 4 Remove and replace the spill switch with a 50 885 Spill Switch Assembly using a T 20 torx type driver 5 Follow the reverse of the previous steps OPTI ONAL FI NI SHI NG In installations where the...

Страница 38: ...rom the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psig 3 45 KPa Always...

Страница 39: ...tion against shock hazard and should be plugged directly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong from this plug CAUTI ON When servicing controls label all...

Страница 40: ...ht side at the rear of the firebox Slide the log left until it contacts the finger stop next to the pilot shield Figure 51 Note Ensure the metal air scoop is installed on the burner pan before proceed...

Страница 41: ...rovided coals on the burner pan in front of the air holes but do not block them figure 56 Using the supplied brush evenly spread the ember wool and Embaglow on top of the burner pan as shown Figure 57...

Страница 42: ...t for it to cool down Then remove the glass and make sure none of the burner ports are blocked Figure 62 Proper Burn and Flame Maintenance Once a year the logs should be removed and checked for deteri...

Страница 43: ...retaining bolts Figure 63 using a 1 4 socket and remove the damaged screen while noting the orientation Install the new screen 50 3715 by simply re installing the retaining bolts Re install the cast...

Страница 44: ...blink one 1 time in intervals 3 Parasitic Pilot Flame the LED indicator will blink two 2 times in intervals 4 System Lock out the LED indicator will blink three 3 times in intervals Additional Ignitio...

Страница 45: ...rifice Pilot will not remain lit 7 Day Shutdown The pilot has been in operation for 7 continuous days without main burner operation Turn fireplace ON to reset pilot timer Problem with Flame Sensor cir...

Страница 46: ...temperature Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configuration with manual Terminal may be re circulating flue gases Check to see...

Страница 47: ...Assembly 50 3730 10 Burner Mounts set of 4 50 3731 11 Convection Fan only EC 069 12 Heyco Strain Relief EC 044 13 Domestic Power Cord 115v EC 042 14 Side Door Complete 50 3734 15 Side Door Glass w Gas...

Страница 48: ...Parts List 21 1 2 12 13 15 14 16 7 6 5 4 3 9 8 11 20 17 18 19 10 48...

Страница 49: ...19 Cast Front Antique Bronze 50 3720 24 Cast Skirt Painted 50 3721 Cast Skirt Antique Bronze 50 3722 25 Cast Right Side Painted 50 3723 Cast Right Side Antique Bronze 50 3724 26 Cast Left Side Painted...

Страница 50: ...Notes 50...

Страница 51: ...ety screen mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused fro...

Страница 52: ..._______________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyy...

Отзывы: