Initial Installation

QUALIFIED INSTALLERS ONLY

STEP 5. 

Cut hole in the roof centered on the small hole placed in the roof from Step 2. The hole should 

be of sufficient size to meet minimum requirements for Clearance to Combustibles, as specified. 

Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support 

box up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well 

as above the roof line. The galvanized finish is desirable above the roof line, due to the higher 

corrosion resistance.

STEP 6.

  Once the pipe sections have been joined, and run up through the hole in the roof, slip an elbow 

strap over the exposed sections, bend the support straps outwards, and push the elbow strap 

down to the roof level, as shown in Figure 42. Tighten the clamp around the pipe section. Use 

a level to make sure the pipe is truly vertical. With roofing nails, secure the support straps to 

the roof. Seal the nails holes heads with non-hardening mastic. Trim the excess length of the 

support straps that extend out beyond the edge of the flashing.

STEP 7.

  Slip  the  flashing  over  the  pipe  section  protruding  through  the  roof.  Secure  the  base  of  the 

flashing to the roof with roofing nails. Use a non-hardening sealant between the uphill edge 

of the flashing and the roof. Insure the roofing material overlaps the top edge of the flashing. 

Verify that you have at least the minimum clearance to combustibles at the roof line.

STEP 8.

  Continue  to  add  pipe  sections  until  the  height  of  the  vent  cap  meets  the  minimum  code 

requirements. Refer to Figure 43 and Table 8. Note that for steep roof pitches, the vent height 

must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched 

roofs,  and  other  similar  factors  can  result  in  poor  draft,  or  down  drafting.  In  these  cases, 

increasing the vent height may solve the problem.

STEP 9.

  Slip the storm collar over the pipe, and push it down to the top of the roof flashing as shown 

in Figure 43. Use the non-hardening sealant around the joint between the pipe and the storm 

collar.

STEP 10.

 Twist-lock the vent cap.

Table 8: Minimum ‘H’ for Figure 43.

Roof Pitch

Minimum Height (H)

Feet

Meters

Flat to 7/12

1

0.3

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4

1.22

Over 12/12 to 14/12

5

1.52

Over 14/12 to 16/12

6

1.83

Over 16/12 to 18/12

7

2.13

Over 18/12 to 20/12

7.5

2.29

Over 20/12 to 21/12

8

2.44

Figure 43: Height of Vertical Termination; 

Reference Table 8. 

36

Содержание Q1LI

Страница 1: ...ng property damage personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html 40016...

Страница 2: ...your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualifi...

Страница 3: ...conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 To prevent injury do not allow a...

Страница 4: ...Placement and Framing 19 Rear Vent Conversion 20 Insulating Material 21 Standoffs 22 Corner Installation 23 Mantle and Non Combustible Clearances 24 Direct Vent 25 Venting Fireplace Inserts 25 Vent T...

Страница 5: ...EATERS CAN CGA 2 17 M91 R2009 GAS FIRED APPLIANCES FOR HIGH ALTITUDES CSA P 4 1 02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY This ENVIRO Q1LI Fireplace Has been certified for use with e...

Страница 6: ...7 7 8 199mm 18 3 4 477mm 16 7 8 429mm 6 Specifications Dimensions Figure 1 Q1LI Dimensions Top Vent Rating Label Lighting Instructions Location The rating label plate and lighting instructions are lo...

Страница 7: ...nce and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Read the owner s manual...

Страница 8: ...off the gas and contact the dealer Warning Incorrect venturi adjustment may lead to improper combustion which is a safety hazard Contact the dealer if there is any concern about the venturi adjustmen...

Страница 9: ...is provided to Index between the features and a Thermostat Key is used to turn on off or index through Thermostat functions Figure 5 6 Figure 5 Proflame 2 Transmitter System Description The Proflame...

Страница 10: ...a radio frequency from the Transmitter to operate the appliance in accordance with the particular Proflame 2 system configuration The IFC has a red reset button at the front right corner that is used...

Страница 11: ...lay see Figure 8 Turn on the Appliance Press the ON OFF Key on the Transmitter The Transmitter display will show all active Icons on the screen A single beep from the Receiver will confirm reception o...

Страница 12: ...re and the actual room temperatures As the room temperature gets closer to the set point the Smart Function will modulate the flame down To activate this function press the Thermostat Key Figure 5 unt...

Страница 13: ...the First Time Figure 15 Remote Control Locked Figure 16 Low Battery Indicator WARNING Fire Hazard Can cause severe injury or death The Receiver causes ignition of the appliance The appliance can tur...

Страница 14: ...mount of use the glass should require cleaning no more than two or three times a season Do not clean the glass when it is hot Cleaning The Firebox Remove the logs carefully as they are very fragile Ge...

Страница 15: ...Glass Door Removal In order to install the log set and for regular cleaning the glass door must be removed There are two 2 door latch mechanisms on top the glass door as shown in Figure 17 Each latch...

Страница 16: ...Orifice NG 46 DMS or LP 1 2 mm 1 Servo Regulator with diaphragm 1 Installation instruction sheet 1 Conversion label Carefully inspect all parts supplied with this conversion kit If any parts have been...

Страница 17: ...adjustment screw figure 48 page 39 clockwise to decrease or counterclockwise to increase until the correct flame is achieved Conversion Kit Installation 1 Turn the unit off by pressing the ON OFF Key...

Страница 18: ...American Gas Association guidelines which state the sea level rated input of Gas Designed Appliances installed at elevations above 2000 610 m feet is to be reduced 4 for each 1000 feet 305 m above sea...

Страница 19: ...can be along a wall raised or at floor level or in a corner There are specific framing measurements for each situation The basic opening should have the dimensions shown in Figure 22 The fireplace mus...

Страница 20: ...28 screws total as shown in Figure 23 Vent Collar Base Plate Exhaust Spigot Cover Plate Figure 23 Vent Conversion Step 1 Locating Notch Step 2 Switch the removed parts around as shown in Figure 24 and...

Страница 21: ...nsulation are required Place the ceramic board on top of the unit first and then place the insulation on top of the ceramic board as shown in Figure 25 Top Vent When using the top vent configuration o...

Страница 22: ...the thickness of the wall material The rear standoffs attach to the back corners of the unit and are not adjustable Combustible material can touch the standoffs but must not encroach past them If the...

Страница 23: ...s for allowable pipe lengths Do not interfere with the structural integrity of the walls 15 3 4 260mm 25 1 4 641mm 27 7 8 562mm 13 3 4 203mm 55 7 8 1123mm 39 1 2 794mm O utside W all Inside W all Figu...

Страница 24: ...le facing When installing the Q1LI as a zero clearance fireplace the correct clearances and materials must be used Above Unit A minimum 10 of thick non combustible facing material with a R Value no le...

Страница 25: ...unrestricted Also ensure that all direct vent pipes have been properly sealed and installed after routine inspection or cleaning The air intake and exhaust pipes must be installed in the correct locat...

Страница 26: ...may be opened C 12 in 30 cm Clearance from permanently closed window to prevent condensation D 24 in 60 cm Vertical clearance to ventilated soffit located above the terminal within a horizontal distan...

Страница 27: ...51 mm above and 1 38 mm on the sides and bottom When combustible materials are directly above a 90 elbow 3 76 mm of clearance are necessary Table 4 Vent Pipe Minimum Clearances Vertical Pipe to the Si...

Страница 28: ...48 SV4L48 4D4 48 pipe length 945 4DT EL45 SV4EBR45 4D45B 45 elbow black 990 4DT EL90 SV4EBR90 4D90B 90 elbow black 950 4DT VS SV4VS Vinyl siding standoff sheild 942 4DT WT SV4RSN 4DWT Wall thimble 95...

Страница 29: ...ation Figure 34 Corner Rear Vent No Vertical Rise Approved through wall thimble The Q1LI can be installed in rear vent applications with no vertical rise within the parameters as shown in Figures 34 a...

Страница 30: ...d the total length of horizontal vent pipe can not exceed 14 feet 4 27m and the total vent length can not exceed 44ft 13 4m Any combination of rise and run can be used as long as it lays within the sh...

Страница 31: ...kit is for vertical terminations only and can t be connected to a chimney flue serving a seperate solid fuel burning stove or appliance WARNING Failure to position the parts in accordance with these d...

Страница 32: ...nger be used Base Plate 4 Exhaust Spigot Cover Plate Vent Collar Figure 38 Removal of Co Axial Venting Step 2 Install the components supplied in the adapter kit as shown using the screws that had been...

Страница 33: ...see Secondary Installation Optional Porcelain Panels Installation and Removal then remove the set screws as shown on each side of the firebox Next install the restrictors at the correct setting and ti...

Страница 34: ...he air gap prevents excessive heat from possibly melting the vinyl siding 5 Horizontal pipes must be supported every 3 feet 914 mm Plumber s all round strap will suffice 6 When running horizontal pipe...

Страница 35: ...rom the vent cap assembly to the outer wall of the vent pipe Bend any remaining portion of the strap back towards the vent cap Security Secure Vent uses a twist lock cap Step 5 Position the horizontal...

Страница 36: ...hing to the roof with roofing nails Use a non hardening sealant between the uphill edge of the flashing and the roof Insure the roofing material overlaps the top edge of the flashing Verify that you h...

Страница 37: ...ng should be framed to 10 254 mm x 10 254 mm inside dimensions in the same manner as shown in Figure 33 4 Any occupied areas above the first floor including plumber s tape connected to wall strap Wall...

Страница 38: ...removal of smoke shelf or baffle removal of ember catches removal of log grate removal of viewing screen curtain and removal of doors THE ORIGINAL FIREPLACE MAY NEVER BE RETURNED TO SOLID FUEL USE IN...

Страница 39: ...the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psig 3 45 KPa Always che...

Страница 40: ...st shock hazard and should be plugged directly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong from this plug CAUTION When servicing controls label all wires prior...

Страница 41: ...ber Bed Installation Figure 52 Coal Nuggets Installation Step 1 Place the back log on the top legde of the air duffuser with back up against the rear brick panel Install the ember bed assembly into th...

Страница 42: ...tly curved twig on the far right side by locating the bottom of it on the far right log grate upright The top will rest on the smooth section of the middle ember bed twig Step 4 Next install the secon...

Страница 43: ...grate upright by locating the notch on the bottom side with the log grate cross bar The top of the twig will rest on top of the far right curved twig The last remaining straight twig gets intalled by...

Страница 44: ...he previous section 10 Re Install the glass door Secondary Installation optionaL poRceLain paneLs 50 2939 instaLLation anD RemovaL Turn off the gas control knob and allow the unit to cool Please ensur...

Страница 45: ...will blink one 1 time in intervals 3 Parasitic Pilot Flame the LED indicator will blink two 2 times in intervals 4 System Lock out the LED indicator will blink three 3 times in intervals Additional I...

Страница 46: ...rifice Pilot will not remain lit Problem with Flame Sensor circuit Check for proper connection of the Flame Sensor to the IFC board Check pilot for full flame impingement around Flame Sensor If flame...

Страница 47: ...ssure Check wiring to thermostat for breaks Check for flame impingement on thermopile Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configu...

Страница 48: ...13 Log Grate 50 2997 14 Door Glass w Gasket 19 75 x 17 5in 50 2998 15 Door Complete 50 2990 16 Porcelain Liners Set 4 pieces 50 2939 17 Ceramic Brick Liner Set 3 pieces 50 2938 Ceramic Ledgstone Line...

Страница 49: ...49 Parts Diagram 5 16 8 20 14 15 12 13 17 18 19 7 10 9 4 3 2 22 11 6 1 21...

Страница 50: ...Notes 50...

Страница 51: ...must be provided by you or the dealer including serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a resu...

Страница 52: ...____________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy N...

Отзывы: