FORM ET115.24-NOM11 (118)
WATER SYSTEM BALANCING
A complete knowledge of the hydronic system, its
components, and controls is essential to proper water
system balancing and this procedure should not be
attempted by unqualified personnel. The system must
be complete and all components must be in operating
condition BEFORE beginning water system balancing
operations.
Each hydronic system has different operating
characteristics depending on the devices and controls
in the system. The actual balancing technique may vary
from one system to another.
After the proper system operation is established, the
appropriate system operating conditions such as various
water temperatures and flow rates should be recorded
in a convenient place for future reference.
Before and during water system balancing, conditions
may exist which can result in noticeable water noise
or undesired valve operation due to incorrect system
pressures. After the entire system is balanced, these
conditions will not exist on properly designed systems.
CONTROLS OPERATION
Before proper control operation can be verified all other
systems must be in proper operation. The correct water
and air temperatures must be present for the control
function being tested. Some controls and features are
designed to not operate under certain conditions.
A wide range of controls and electrical options and
accessories may be used with the equipment covered
in this manual. Consult the approved unit submittals,
order acknowledgement, and other manuals for detailed
information regarding each individual unit and its
controls. Since controls and features may vary from
one unit to another, care should be taken to identify
the controls to be used on each unit and their proper
control sequence. Information provided by component
manufacturers regarding installation, operation, and
maintenance of their individual controls is available
upon request.
TABLE 3: EC MOTORS
UNIT
SIZE
FAN
SPEED
EC MOTOR
HP (QTY)
# OF
FANS
WATTS
2
(STD/HS)
AMPS
1,3
115 VOLTS
208/230 VOLTS
277 VOLTS
3-SPEED
(STD/HS)
2-10VDC
3-SPEED
(STD/HS)
2-10VDC
3-SPEED
(STD/HS)
2-10VDC
02
High
(1) 1/4
1
32 / 45
0.7 / 1.0
0.9
0.5 / 0.6
0.5
0.4 / 0.5
0.5
Medium
21 / 36
Low
14 / 26
03
High
(1) 1/4
1
35 / 59
1.0 / 1.5
1.1
0.6 / 0.9
0.7
0.5 / 0.8
0.6
Medium
23 / 43
Low
16 / 33
04
High
(1) 1/4
2
50 / 75
1.5 / 1.8
1.2
0.9 / 1.1
0.8
0.8 / 0.9
0.6
Medium
33 / 56
Low
21 / 41
06
High
(1) 1/4
2
104 / 132
2.6 / 3.1
2.0
1.6 / 1.9
1.2
1.3 / 1.6
1.0
Medium
62 / 89
Low
36 / 62
08
High
(1) 1/4
2
91 / 122
2.3 / 2.9
2.0
1.4 / 1.7
1.2
1.2 / 1.5
1.0
Medium
54 / 90
Low
31 / 62
09
High
(1) 1/4
2
119 / 182
3.7 / 4.5
2.7
2.3 / 2.7
1.6
1.9 / 2.3
1.4
Medium
72 / 116
Low
39 / 77
10
High
(2) 1/4
4
142 / 207
3.9 / 5.1
3.1
2.3 / 3.1
1.9
2.0 / 2.6
1.6
Medium
91 / 139
Low
54 / 104
12
High
(2) 1/4
4
143 / 209
3.2 / 4.5
3.5
2.0 / 2.7
2.1
1.6 / 2.3
1.8
Medium
92 / 152
Low
56 / 105
NOTES:
1. Motor electrical data is nameplate data.
2. Watts are based on an HLP with 3-speed EC motor, 3 row coil, 12FPI, 1" throwaway filter, 0.05" ESP at 115V.
3. For neutral conductor sizing, multiply AMPS by 1.73.
4. Motor data is subject to change and should not be used for submittal. Refer to unit submittal for actual ratings.