Initial Installation
QUALIFIED INSTALLERS ONLY
Table 7: Minimum ‘H’ for Figure 47.
Roof Pitch
Minimum Height (H)
Feet
Meters
Flat to 7/12
1
0.3
Over 7/12 to 8/12
1.5
0.46
Over 8/12 to 9/12
2
0.61
Over 9/12 to 10/12
2.5
0.76
Over 10/12 to 11/12
3.25
0.99
Over 11/12 to 12/12
4
1.22
Over 12/12 to 14/12
5
1.52
Over 14/12 to 16/12
6
1.83
Over 16/12 to 18/12
7
2.13
Over 18/12 to 20/12
7.5
2.29
Over 20/12 to 21/12
8
2.44
Figure 47: Height of Vertical Termination;
Reference Table 7
Figure 49: Use of Wall Straps.
Figure 48: Multi-Story Vent Pipe Installation
NOTES:
1. If an
offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe
every
3’ ( 914 mm)
using wall straps to avoid excessive stress on the elbows.
2. Use 45
°
degree elbows instead of 90
°
degree elbows when ever possible. The 45
°
degree elbow
offers less restriction to the flow of flue gases and intake air.