40
Wall Framing
Horizontal
Termination
Wall Thimble
Fire Stop
Exhaust Pipe
Combustion Air
Outer Pipe
Elbow
Initial Installation
QUALIFIED INSTALLERS ONLY
h
oRizontaL
t
eRmination
:
1
�
A MINIMUM OF 24” [610mm] VERTICAL RISE PLUS AN ELBOW IS REQUIRED
WHEN HORIZONTALLY TERMINATING WITH AN APPROVED VENT CAP�
2. Horizontal pipes must not
be level� For every 12” (305
mm) of horizontal travel
(away from the stove),
there should be at least ¼”
(6�4 mm) of vertical rise�
Never allow the vent to run
downward, as this could
cause high temperatures or
even present the possibility
of a fire.
3. The exterior of the horizontal
vent termination must not be
blocked or obstructed.
4. If the vent termination is not
being attached to wood, the
four wood screws provided
should be replaced with material
appropriate fasteners.
5. For buildings with vinyl siding,
a vinyl standoff should be
installed between the vent cap
and the exterior wall. Attach
the vinyl siding standoff to the
horizontal termination. Note that the termination bolts onto the flat portion of the standoff, providing
an air space between the wall and the vent termination. The air gap prevents excessive heat from
possibly melting the vinyl siding.
6. Horizontal pipes must be supported every 3’ (914 mm)
. Plumber’s all round strap will suffice.
7. Ensure venting clearances are maintained, see page 35 for details.
Step 1.
Set the fireplace in the desired location. Check to determine if wall studs will be in the way when
the venting system is attached. If this is the case, the location of the fireplace may have to be
adjusted or the venting may have to be offset.
Step 2.
Direct vent pipe sections are designed with special twist-lock connections. Dry fit the desired
combination of pipe and elbows to the appliance adaptor.
Step 3.
With the pipe in the correct position and attached to the fireplace, mark the wall for a hole as
directed by specified wall thimble dimensions. Cut and frame the hole in the exterior wall where
the vent will be terminated. If the wall being penetrated is made of a non-combustible material
(i.e. masonry or concrete) a 8 1/2” (21�6 cm) hole is acceptable.
Figure 52:
Horizontal Vent Termination
Содержание C60I
Страница 55: ...55 55 Parts Diagram 1 2 3 5 11 6 13 4 10 9 7 8 12 14 15 15 ...
Страница 57: ...57 Notes ...
Страница 58: ...58 Notes ...