Figure 19: Freestanding Installation into existing fireplace.
Unless you are experienced, we recommend
installation by your dealer or a professional
installer.
Many venting manufacturers have listed kits
available to connect a stove to a masonry fireplace.
Always follow the vent manufacturer’s installation
instructions.
The existing damper may have to be
removed to allow installation.
Installation
m
asonry
f
irEplacE
i
nstallation
- f
rEEstanding
:
m
oBilE
H
omE
i
nstallation
:
SPECIAL REQUIREMENTS:
All freestanding installation requirements in “
Installation Of A Listed,
Factory Built Chimney”, must comply with all local codes that may apply, and the following must be met:
VENTING:
In Canada:
Any ULC-S629 listed chimney system with the accompanying double-wall vent connector.
In U.S.A.
Any UL-103-HT listed chimney system with the accompanying double-wall vent connector.
Do not connect a listed chimney of one manufacturer with a listed double wall connector from another
manufacturer.
These connectors must be installed in accordance with the manufacturer’s instructions. Use only specified
components. The chimney and pipe must extend at least 10 feet (2.4 m) above the stove and 3 feet (0.9
m) above the highest point of the roof. Install a rain cap with spark arrestor at the top that will not impede
the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight will not sit
on the stove. Seal with silicone to maintain vapor barrier at the chimney and outside air penetrations.
Floor Protection
Combustible Floor
Masonry Fireplace
Rain Cap
Steel Plate or Flashing
Rigid Stainless
Steel Liner
Damper Removed
or Fastened Open
Clean-out tee
Chimney
Support and Clamp
Clean-out
cover
Flexible Stainless
Steel Section
Stainless Steel
Connector Pipe
Listed Liner
Stove pipe must
end higher than liner
27