I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

MAC 10

®

 LEAC2

Fan Filter Unit

  

Service: Removal and Replacement of RSRE Gel Seal Filters 

Note:

 All filters should be visually inspected for freight damage before installation.  It is necessary to use two workers when 

removing the filter and for installation to avoid twisting or separation of the media seals.  Handle the filter only by the frame 

and never place anything on the upstream filter side of the filter. Additionally, it is important to keep the filter level to prevent 

any shearing force on the media itself.

For RSRE Filters:

Tools Required: Phillips head screwdriver, 3/16” ball driver hex head wrench

 

Step 1.

 Remove the diffuser screen by removing the six 10-32x1/2 screws.

Step 2. 

Loosen the six 1/4x20 socket cap head screws far enough to rotate the filter clip 90°.  The filter will not drop during this 

operation.  Slowly pull the filter away from the knife-edge seal, taking care not to touch the filter face during this operation.  It 

is important to pull the filter slowly and evenly away from the seal so that the gel remains in the filter gel track.

Step 3. 

Inspect filter for visual damage.  If damaged, set aside for replacement or repair.

Step 4. 

Inspect the gel seal if reinstalling the removed filter.  Determine if the gel has lost its ability to seal.  If so, have a certified 

professional replace the missing, dried out, and/or severely damaged gel.

Step 5. 

Place the filter evenly against the filter plenum housing of the RSRE unit.  Install filter clips and screws.  The clips 

can be rotated and angled into place.  Using the clips as a lever, the filter can be seated.  It is recommended to work either 

clockwise or counter-clockwise around the filter and raise the filter into the gel.

Step 6. 

Reinstall screen.  Reinstall and hand-tighten diffuser screen screws.  Avoid overtightening the screen hardware.

WARNING 

DISCONNECT THE UNIT FROM THE ELECTRICAL 

POWER SOURCE BEFORE ATTEMPTING 

ANY SERVICE.

WARNING 

THE RSRE FILTER IS PROTECTED WITH AN 

EXPANDED METAL FACE SCREEN. THIS IS

NEVER TO BE USED TO HANDLE THE FILTER.  

IT IS ONLY FOR PROTECTION AGAINST AN 

ACCIDENTAL TOUCH OF THE FILTER.  

ONLY HANDLE THE FILTER BY THE FRAME.

FILTER PLENUM

(DOWN STREAM)

1/4-20 CAP SCREW

FILTER CLIP

SCREEN HARDWARE:

#10-32x1/2 PHP SCREW

#10 NYLON WASHER

GEL TRACK

PLENUM KNIFE EDGE

FILTER PLENUM

(UP STREAM)

GEL SEAL FILTER

PERFORATED DIFUSSER

SCREEN

SCREEN HARDWARE

FILTER CLIP

1/4-20 CAP SCREW

2-PIECE WELDED

FILTER PLENUM

HOUSING

FAN FILTER UNIT

GEL SEAL FILTER

Figure 7 - RSRE Filter Replacement

FILTER MEDIA

PERFORATED DIFUSSER SCREEN

Figure 7: RSRE Filter Replacement

Innovators in Clean Air Technology   |   www.envirco.com   |   Installation, Operation & Maintenance

Содержание MAC 10 LEAC2

Страница 1: ...ENVIRCO Technical Support 800 884 0002 MAC 10 LEAC2 Fan Filter Unit Standard RSRE Models INSTALLATION OPERATION MAINTENANCE MANUAL...

Страница 2: ...ng the Prefilter G4 Pleated 7 Service Removal and Replacement of Standard Filters 8 Service Removal and Replacement of RSRE Filters 9 Service Standard Motor Removal and Installation 10 Service RSRE Mo...

Страница 3: ...LABEL PN 268177 XXX 150412345 BA AS1CH LISTED 2F82 AIR FILTER E152685 Innovators in clean air technology LEAC2 SUITABLE FOR COMMERCIAL OR INDUSTRIAL USE ONLY C R R R Company Purchased From ___________...

Страница 4: ...e A Z in the part number indicates that the unit is special This may indicate a size change from standard or a special filter Please contact the factory for part numbers if this is the situation I n s...

Страница 5: ...stem with eyebolts s hooks and chain Screw the four eyebolts into the nutserts on the lid assembly before lifting into an overhead position See Figure 2 Note Confirm fan dimensions to match T grid dim...

Страница 6: ...s per IEST specifications should be conducted to determine the filter condition and appropriate fan setting Figure 3 Speed Airflow Adjustment ENAC Control Card Optional MAC 10 LEAC2 units will have th...

Страница 7: ...sition Step 3 Remove the prefilter from the snap in frame The beverage board frame has slots that have to be depressed to release the filter from the prefilter housing See Figure 5 above Step 4 After...

Страница 8: ...assembly off the HEPA ULPA filter See Figure 6 Discard the used filter as per requirements of the applicable regulations Note Before replacing with a new HEPA ULPA filter carefully inspect the new fil...

Страница 9: ...reinstalling the removed filter Determine if the gel has lost its ability to seal If so have a certified professional replace the missing dried out and or severely damaged gel Step 5 Place the filter...

Страница 10: ...the four screws mounting the blower bracket to the blower assembly plate and cut cable tie securing blower cable to blower bracket Remove motor mount assembly from plate Step 11 Remove the four screw...

Страница 11: ...or blower and components previously removed in reverse order to complete work Carefully tighten motor mount bracket screws Don t forget to reinstall challenge port tubing WARNING DISCONNECT THE UNIT F...

Страница 12: ...er output NON LAMINAR FLOW AND OR EXCESSIVE CONTAMINATION Step 1 Ensure that no large obstructions are upstream of airflow pattern Step 2 Determine that no other air moving devices are operating in or...

Страница 13: ...CONTROL WHITE GRN YEL BLUE GRN YEL WHITE MAC10 LEAC2 INPUT POWER CAPACITOR Figure 10 Wiring Diagram SSSC Figure 11 WIRING DIAGRAM ENAC BLUE MOTOR BROWN BLACK GRN YEL WHITE GRN YEL WHITE GRN YEL BLUE W...

Страница 14: ...68110 002 268110 003 268109 001 63739 002 268716 115 268716 230 268716 277 268171 115 268171 230 268171 277 ITEM FILTER REPLACEMENT FFU SIZE ACTUAL FILTER SIZE 7A STD FILTER 2X4 23 63 x 47 63 HEPA 99...

Страница 15: ...cords and c modification or repair of the Goods only as authorized by ENVIRCO ENVIRCO does not warrant the Goods or any repaired or replacement parts against normal wear and tear or damage caused by m...

Страница 16: ...ng Grid System Hospital Healthcare Hospital Healthcare IsoClean and IsoClean with Ultraviolet Light AirCeil Hospi Gard Room Pressure Monitor Enviramedic Products HOR Horizontal Flow Enclosure HCF Hori...

Отзывы: