INSTALLATION, OPERATION & MAINTENANCE MANUAL

Содержание MAC 10 LEAC2

Страница 1: ...ENVIRCO Technical Support 800 884 0002 MAC 10 LEAC2 Fan Filter Unit Standard RSRE Models INSTALLATION OPERATION MAINTENANCE MANUAL...

Страница 2: ...ng the Prefilter G4 Pleated 7 Service Removal and Replacement of Standard Filters 8 Service Removal and Replacement of RSRE Filters 9 Service Standard Motor Removal and Installation 10 Service RSRE Mo...

Страница 3: ...LABEL PN 268177 XXX 150412345 BA AS1CH LISTED 2F82 AIR FILTER E152685 Innovators in clean air technology LEAC2 SUITABLE FOR COMMERCIAL OR INDUSTRIAL USE ONLY C R R R Company Purchased From ___________...

Страница 4: ...e A Z in the part number indicates that the unit is special This may indicate a size change from standard or a special filter Please contact the factory for part numbers if this is the situation I n s...

Страница 5: ...stem with eyebolts s hooks and chain Screw the four eyebolts into the nutserts on the lid assembly before lifting into an overhead position See Figure 2 Note Confirm fan dimensions to match T grid dim...

Страница 6: ...s per IEST specifications should be conducted to determine the filter condition and appropriate fan setting Figure 3 Speed Airflow Adjustment ENAC Control Card Optional MAC 10 LEAC2 units will have th...

Страница 7: ...sition Step 3 Remove the prefilter from the snap in frame The beverage board frame has slots that have to be depressed to release the filter from the prefilter housing See Figure 5 above Step 4 After...

Страница 8: ...assembly off the HEPA ULPA filter See Figure 6 Discard the used filter as per requirements of the applicable regulations Note Before replacing with a new HEPA ULPA filter carefully inspect the new fil...

Страница 9: ...reinstalling the removed filter Determine if the gel has lost its ability to seal If so have a certified professional replace the missing dried out and or severely damaged gel Step 5 Place the filter...

Страница 10: ...the four screws mounting the blower bracket to the blower assembly plate and cut cable tie securing blower cable to blower bracket Remove motor mount assembly from plate Step 11 Remove the four screw...

Страница 11: ...or blower and components previously removed in reverse order to complete work Carefully tighten motor mount bracket screws Don t forget to reinstall challenge port tubing WARNING DISCONNECT THE UNIT F...

Страница 12: ...er output NON LAMINAR FLOW AND OR EXCESSIVE CONTAMINATION Step 1 Ensure that no large obstructions are upstream of airflow pattern Step 2 Determine that no other air moving devices are operating in or...

Страница 13: ...CONTROL WHITE GRN YEL BLUE GRN YEL WHITE MAC10 LEAC2 INPUT POWER CAPACITOR Figure 10 Wiring Diagram SSSC Figure 11 WIRING DIAGRAM ENAC BLUE MOTOR BROWN BLACK GRN YEL WHITE GRN YEL WHITE GRN YEL BLUE W...

Страница 14: ...68110 002 268110 003 268109 001 63739 002 268716 115 268716 230 268716 277 268171 115 268171 230 268171 277 ITEM FILTER REPLACEMENT FFU SIZE ACTUAL FILTER SIZE 7A STD FILTER 2X4 23 63 x 47 63 HEPA 99...

Страница 15: ...cords and c modification or repair of the Goods only as authorized by ENVIRCO ENVIRCO does not warrant the Goods or any repaired or replacement parts against normal wear and tear or damage caused by m...

Страница 16: ...ng Grid System Hospital Healthcare Hospital Healthcare IsoClean and IsoClean with Ultraviolet Light AirCeil Hospi Gard Room Pressure Monitor Enviramedic Products HOR Horizontal Flow Enclosure HCF Hori...