Regular safety checks
To help you fulfil the national/international requirements and to avoid malfunction and risk
for injuries, we have provided the following checklist.
Do not use if repair or adjustment is necessary.
Disconnect supply
12
when cleaning or other maintenance is to be carried
out.
If problem
occurs
Daily Action
Activate your operator and check visually, fastening of
•
operator
1
•
arm system
2
•
cables
3
•
programme selectors
4
•
hinges
5
•
door and glass
6
Also inspect your operator and check visually for
•
sharp edges on the door leaf and door frame (if any)
7
•
condition of door seals
8
•
finger protection
9
•
and finally that the complete door runs properly and closes slowly in a smooth way
Set the programme selector to OFF and check that the operator and electromechanical lock (if
fitted) work together. Also check that the lock
10
really secures the door.
Activate the manual activation units
11
, if any, and walk towards the door. Check that the door
has opened appropriately while you pass the entrance/exit.
Then proceed with the automatic activation units
12
in the same way.
Check the non-monitored safety sensors
13
if any, by standing in the swing path and activate
the operator. The door must not hit you when opening nor when closing.
If you are unsure of which type of sensor you have, please contact your Entrematic representative.
Set the programme selector in AUTO mode. Push the door manu-
ally in escape direction and make sure that no object or function
will prevent the door from opening. Also make sure the escape
route is free for use.
By law, these tests must be per-
formed regularly by trained person-
nel.
Escape
doors
Let the door close after an impulse ensuring nothing prevents the
door from closing and locking (if regulations require it).
Fire
doors
Contact your Entrematic representative. For contact information, see last page.
=
Take appropriate measures.
=