(Example 1).
When using the
control panel for sliding gate ap-
plications:
- connect the opening and clos-
ing limit switch NC contacts to
terminals 0-11-12 if required.
With this configuration, the wing
stops when the limit switches are
activated.
N.B.: if the self-controlled safety edge SOFA1-SOFA2 is used, make the connections
indicated in paragraph 4.1.
WARNING: with CROSS5EH1 and CROSS7EH1 automations with a limit switch and without
encoder, you must set DIP5B=OFF and DIP�B=OFF.
(Example 2).
The remote control
can be used with step-by-step
functioning and, at the same time,
terminal 5 with opening function by
making the connections indicated
and setting DIP1A=OFF.
Closing limit switch
Opening limit switch
1 5 9 13 20
0 1 6 8 41
C NO
11
12
0
14 0
VA VC TC R1
<MAX
A
1
ON
2 3 4 5 6
B
1
ON
2 3 4 5 6 7
DIP2B=ON
DIP1A=ON
Closing limit switch
Opening limit switch
Opening
Partial opening
1 5 9 13 20
0 1 6 8 41
C NO
11
12
0
14 0
VA VC TC R1
<MAX
A
1
ON
2 3 4 5 6
B
1
ON
2 3 4 5 6 7
DIP2B=ON
DIP3B=ON
DIP1A=OFF
12. Application example for sliding gates
When using the control panel for sliding automation applica-
tions:
- Select the correct opening direction with DIP2A
i