
1
KT-400 Ethernet Four-Door Controller Installation Manual
Pre-Installation Information
To the Installer:
If you are familiar with the installation, you can use the installation checklist on page 36 with
the
symbol
.
Safety Instructions
Important: NEVER INSTALL THE EQUIPMENT DURING A LIGHTNING STORM!
This equipment, KT-400 Ethernet Four-Door Controller Model KT-400-EU, shall be used installed and used within an
environment that provides the pollution degree max 2 and over voltages category II NON HAZARDOUS LOCATIONS, INDOOR
only. The equipment is FIXED and PERMANENTLY CONNECTED and is designed to be installed by Service Persons only;
[service person is defined as a person having the appropriate technical training and experience necessary to be aware of
hazards to which that person may be exposed in performing a task and of measures to minimize the risks to that person or other
persons.] The equipment is installed in a metallic cabinet that meets the applicable requirements for a FIRE ENCLOSURE.
Note:
When installed on the North American Market, powered via the UL, cUL Listed 75VA Transformer, the KT-400 Ethernet
Four-Door Controller shall be connected to the mains by a
LICENSED ELECTRICIAN
in accordance with the applicable
rules of the National Electrical Code or Canadian Electrical Code regarding this type of connection.
1. The
connection to the mains supply
must be made as per the local authorities rules and regulations: In the UK as per
BS6701. An appropriate disconnect device must be provided as part of the building installation. Where it is not possible to rely
on the identification of the NEUTRAL in the AC MAINS SUPPLY, the disconnecting device must disconnect both poles
simultaneously (LINE and NEUTRAL).
2. AVOID
setting up
the equipment near heaters, air conditioners, ventilators, and/or refrigerators;
DO NOT select a place that exposes your controller to direct sunlight, excessive heat, moisture, vapors, chemicals or dust.
3. If
during the installation
a knockout on the cabinet is removed, it is the installer's responsibility to ensure that the same
degree of protection for the cabinet is provided by the use of bushings, fittings, adequate sealant, etc.
4. The metallic
cabinet must be secured to the building structure before
operation. Use four (4) stainless steel tapping
screws #8, 32 mm (1.25 in) to mount the cabinet.
5. The
ground connection
must be as shown within the included diagram, or equivalent.
6.
Internal wiring
must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation;
- Reducing the clearance between SELV (Safety Extra Low Voltage) circuits and NON-POWER Limited Circuits (Battery wires);
- Route the battery wires away from the rest of the SELV circuits.
7. It is the end-user and/or installer's responsibility to ensure that the disposal of the used batteries is made according to the
waste recovery and recycling regulations applicable to the intended market.
8. There are
no serviceable parts within the equipment
; For any issues regarding the equipment please contact your
installer.
9. Before leaving the premises, the Ethernet communication lines must first be connected to an approved (acceptable to local
authorities) type Network Interface Device (NID), (UL installations, UL 60950 listed NID, for ULC installations CAN/CSA C22.2,
No. 60950-1 Certified NID). All wiring shall be performed according to the local electrical codes.
10.
DISCONNECT POWER BEFORE SERVICING
.
wwww.EntraPASS.com / 8641 S. Warhawk Rd., Conifer, CO 80433 - Tel: 303-670-1099 - Email: [email protected]
wwww.EntraPASS.com
8641 S. Warhawk Rd., Conifer, CO 80433 - Tel: 303-670-1099 - Email: [email protected]