KT-400

Ethernet Four-Door Controller

Installation Manual

wwww.EntraPASS.com 

8641 S. Warhawk Rd., Conifer, CO 80433 - Tel: 303-670-1099 - Email: [email protected]

Содержание KT-400

Страница 1: ...KT 400 Ethernet Four Door Controller Installation Manual wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 2: ...aPASS com 303 670 1099 303 679 8949 fax wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 3: ...ocking Devices 17 Hooking Up Inputs 18 Connect readers and keypads 18 Relay Controlled Outputs 19 Auxiliary Outputs 19 Tamper Protection 19 Connecting the KT 400 Ethernet Four Door Controller 20 Connecting the VC 485 or the USB 485 to the RS 485 Bus 20 Connecting over Corporate Network LAN 21 Powering the KT 400 Ethernet Four Door Controller 21 SPI Expansion Port 23 Important Installation Rules ab...

Страница 4: ...traPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 5: ...uipment near heaters air conditioners ventilators and or refrigerators DO NOT select a place that exposes your controller to direct sunlight excessive heat moisture vapors chemicals or dust 3 If during the installation a knockout on the cabinet is removed it is the installer s responsibility to ensure that the same degree of protection for the cabinet is provided by the use of bushings fittings ad...

Страница 6: ...er EntraPASS products contact technical support Monday to Friday at 303 670 1099 wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 7: ...re 2 for all the connection possibilities offered by the KT 400 Ethernet Four Door Controller Communication Ports 1 10 100Base T ETH1 Ethernet for network connection with the EntraPass Gateway 1 10 100Base T ETH2 Ethernet for network connection with intelligent IP peripherals 1 RS 232 for communication with EntraPass 1 RS 485 COM1 for communication with EntraPass or loop of controllers 1 RS 485 CO...

Страница 8: ...itch input The tamper switch is a non programmable Fixed Function input It is used to identify tampering of the KT 400 cabinet Lock Outputs There are 4 onboard lock outputs and they are supervised The locking function can also be performed by any onboard relay configured for this functionality Relay Outputs There are 4 onboard relay outputs Up to 256 relay outputs can be supported through the addi...

Страница 9: ...C terminals such as the 12V AUX For further details see Troubleshooting on page 28 section ETH1 ETH2 LINK GREEN The LED is OFF when there is no Ethernet network or the cable is disconnected and ON when there is an Ethernet cable and network connection ETH1 ETH2 TXRX YELLOW The LED indicates network activity Built in SPI Expansion The KT 400 Ethernet Four Door Controller allows connection of expans...

Страница 10: ...6 Figure 1 KT 400 Ethernet Four Door Controller PCB View wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 11: ...Four Door Controller Installation Manual Figure 2 KT 400 Ethernet Four Door Controller Inputs and Outputs View wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 12: ...8 Figure 3 KT 400 Cabinet Models for North America and European Union wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 13: ...tion and a Global Gateway Over RS 485 with a VC 485 See Figure 6 Application with EntraPass Global Edition and a KT NCC Over the Internet with a KT NCC See Figure 7 Application with EntraPass Special Corporate and Global Editions Over RS 232 straight from EntraPass RS 232 COM port See Figure 8 Figure 4 Over the Internet with EntraPass Special and Corporate Editions with Multi site Gateway wwww Ent...

Страница 14: ...ure 6 VC 485 with EntraPass Global Edition and Global or Multi site Gateway wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 15: ...n Manual Figure 7 Over the Internet with a KT NCC and EntraPass Global Edition Figure 8 Over RS 232 straight from the EntraPass RS 232 COM port wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 16: ...Patterns Booting Up Steady Factory Default DHCP Continuous LONG Pulses Unable to Resolve DNS 2 LONG Pulses Forced Default Static 3 LONG Pulses DHCP Server Failed 4 LONG Pulses Receive Broadcast Single 2 5 Sec Burst Card Read or Swipe Single 0 5 sec burst resume previous flash Hard Reset 4 SHORT Pulses Multi site Gateway 3 SHORT Pulses Global Gateway 1 SHORT Pulse Fail Soft Continuous SHORT Pulses ...

Страница 17: ...l JP4 on EXT 750 mA each or 3 0 Amps total for the KT 400 EU model JP4 on INT Auxiliary reader outputs LEDs LED OUT1 and OUT2 and buzzer BUZ for each individual door 25mA max each open collector outputs Relay controlled output 4 onboard Form C Relay controlled outputs 30 VDC 3 Amps max each Communication ports 1 x RS 232 with RJ 12 2 x RS 485 2 x Ethernet 10 100 Base T with RJ 45 Expansion port 1 ...

Страница 18: ... Metal Cabinet European Union Model see Table 2 KT 400 PCB KT 400 Ethernet Four Door Controller PCB only IP Ready with Accessory Kit see Table 2 KT 400 CAB KT 400 Black Metal Cabinet with Lock and Keys see Table 2 KT 400 CABEU KT 400 Black Metal Cabinet with Lock and Keys European Union Model see Table 2 Expansion Modules Models KT MOD INP16 KT 400 Expansion Module 16 Zone Inputs with SPI Cable 41...

Страница 19: ...9F to RJ 12 adaptor and 740 1041 DB9M to DB25F adaptor USB 485 USB 485 interface USB cable 0 9 m 3 ft and USB drivers on CD ROM VC 485 VC 485 interface RS 232 cable 3 m 10 ft with RJ 12 connectors 740 1012 DB25F to RJ 12 adaptor 740 1022 DB9F to RJ 12 adaptor and 740 1033 DB25M to RJ 12 adaptor KT 3LED PLATE Three color LED alarm indicator mounted on single plate KT ACPW LED AC power LED indicator...

Страница 20: ...aenaur EX S5 or equivalent not included Note 5 A time lag fuse of 630mA is included with the fuse block terminal If replacement is needed only use recommended type 250VA 630mA Time lag TUV or VDE approved must meet EN60127 1 2 3 Item Description KT 400 Notes 1 2 4 KT 400 PCB Note 2 KT 400 ACC KT 400 CAB Notes 1 4 KT 400 EU Notes 1 2 3 4 5 KT 400 CABEU Notes 1 4 KT 400 PCB 1 1 1 Cabinet 1 1 1 1 KT ...

Страница 21: ... any transmitting equipment Physical access using keys on controlled doors must be provided so that the KT 400 Ethernet Four Door Controller can easily be accessed for servicing in case of malfunction Earth Grounding AWG 18 grounding wire to EGND The KT 400 Ethernet Four Door Controller uses high performance communication proper grounding must be provided to ensure proper operation Make an earth g...

Страница 22: ... associated request to exit detector as input 6 Inputs 9 and 10 are automatically reserved for the third controlled door Inputs 13 and 14 are automatically reserved for the fourth controlled door There is no obligation to follow these rules but this standard convention facilitates servicing Connect readers and keypads READER CONNECTION TERMINAL WARNING Connecting the red wire lead or power lead of...

Страница 23: ...e external power supply requirement for expansion modules Auxiliary Outputs Connect auxiliary outputs to readers and local warning devices Auxiliary outputs are used for visual and audible signal They can be activated according to input conditions or events and local alarms Auxiliary outputs READER DOOR 1 to 4 LED provide visual feedback of access operation and auxiliary outputs READER DOOR 1 to 4...

Страница 24: ...ion speed of the system Note 1 Most installations should be set to 38400 Bauds Note 2 Connecting several KT 400 at a single point is not recommended neither are splitters or spider web star networks Note 3 If the AUX 12 VDC is already used the RS 485 signal ground can be connected to the other GND terminals on the KT 400 The EGND earth ground terminal cannot be used for signal ground only use the ...

Страница 25: ...r Door Controller Install transformer if applicable Place battery in cabinet Power up the KT 400 Ethernet Four Door Controller The KT 400 must be powered by a wire in or plug in transformer After you have completed all the necessary steps you can power up the KT 400 Connect AC power and connect the battery Once powered check the Heartbeat LED status indicator to determine the communication status ...

Страница 26: ...1 15 modules KT MOD OUT16 x 750 mA 11250 mA 2 11250 mA 500 mA or 0 mA if the 12 VDC AUX of the KT 400 is used 10750 mA 3 10750 mA divided by 1850 mA 5 8 which means in fact 6 external power supplies 12 VDC 2 Amps are required 4 Connect an external power supply at every expansion module where the current draw has reached 1 85 Amps 5 Make sure the power jumper on the modules is in the correct positi...

Страница 27: ...wing documents Part Number Description DN1775 KT MOD INP16 Install Sheet French version DN1776 KT MOD INP16 Install Sheet English version DN1780 KT MOD OUT16 Install Sheet French version DN1781 KT MOD OUT16 Install Sheet English version DN1785 KT MOD REL8 Install Sheet French version DN1786 KT MOD REL8 Install Sheet English version DN1805 KT MOD CAB Install Sheet French version DN1806 KT MOD CAB I...

Страница 28: ...24 Figure 10 PCB View of Expansion Modules wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 29: ...troller Installation Manual Figure 11 Example of KT 400 Ethernet Four Door Controller Interconnection with Expansion Modules wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 30: ...26 Figure 12 Expansion Modules Cabinets for North America and European Union wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 31: ... is cleared IP address is kept if valid Controller generates the message Controller Hard Reset Internal RTC Real Time Clock and clock are settled to the default time and date values January 1st 2005 00 00 00 Saturday 3 long pulses Forced Default Static When JP2 is ON and JP3 is OFF Same as Soft Reset condition except IP address is forced to the default static IP 192 168 1 2 Continuous long pulses ...

Страница 32: ...should lit and the yellow TXRX LED should be flashing The blue Heartbeat LED should be flashing 1 Remove JP2 and JP3 jumpers as described in Table 3 for Factory Default DHCP mode 2 Press the reset button 3 Check the blue Heartbeat LED heartbeat pattern 4 Verify the IP address with the KT Finder see page 32 5 Put back JP2 and JP3 jumpers 6 Configure the KT 400 with the KT Finder see page 32 Figure ...

Страница 33: ...eries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors Regarding the recommended backup battery 12 VDC 7 Ah It is the service person s responsibility to assure that the disposal of used batteries is made according to the waste recovery and recycling regulations applicable to the intended market Use ...

Страница 34: ... determine the status See Table 3 on page 28 for details 2 Start your web browser and enter the following IP 192 168 1 2 and press Enter Note Even though the KT 400 is in Forced Default Static mode the DHCP status displays Enable Make sure to change it accordingly when entering the parameters from the Network Configuration Information Sheet 3 Put a jumper on JP3 Both jumpers should now be on JP2 a...

Страница 35: ...the EntraPass DVD ROM available as a free download from http www kantech com 1 Quit all EntraPass applications 2 Make sure the KT 400 is in Factory Default DHCP mode See Table 3 on page 28 3 Start the KT Finder Note If you try to run the KT Finder while running EntraPass you will get an error message similar to this 4 Select KT 400 from the Device menu 5 Enter the MAC address of the KT 400 then cl...

Страница 36: ...ollowing IP address This information must be the same as entered in EntraPass workstation for Devices Site 9 Select a Protocol UDP or TCP 10 Change the Port number if required not applicable in TCP Note The port number should only be changed when you have more than one KT 400 at the same remote site 11 Click OK 12 Repeat the procedure for each KT 400 at this site wwww EntraPASS com 8641 S Warhawk ...

Страница 37: ...ils please refer to the EntraPass Reference Manual MAC Address 00 50 F9 ______ ______ ______ Protocol _________ Port 18810 by Default or _________ UDP only IP Address Type DHCP or Static IP Address ______ ______ ______ ______ Subnet Mask ______ ______ ______ ______ Default Gateway Router ______ ______ ______ ______ EntraPass Special Edition Multi site Gateway IP Address ______ ______ ______ ______...

Страница 38: ... 400 Ethernet Four Door Controller Site MAC Address 00 50 F9 ______ ______ ______ IP Address Type Static or Reserved DHCP IP Address ______ ______ ______ ______ Subnet Mask ______ ______ ______ ______ Default Gateway Router ______ ______ ______ ______ DNS Server IP Address ______ ______ ______ ______ Router Public IP Address ______ ______ ______ ______ or Domain name ____________________________ P...

Страница 39: ...pads Auxiliary Outputs Connect auxiliary outputs to readers and local warning devices Tamper Protection Install tamper switch on cabinet Connecting the KT 400 Ethernet Four Door Controller Connecting the VC 485 or the USB 485 to the RS 485 Bus Connect the RS 485 cable to COM1 485 and the RS 485 signal ground to the 12 VDC AUX negative Connecting the Master Controller to the Host PC Connect the RS ...

Страница 40: ... EOL DRY or DEOL DOOR Z9 NO or NC EOL DRY or DEOL REX Z10 NO or NC EOL DRY or DEOL INPUT Z11 NO or NC EOL DRY or DEOL INPUT Z12 NO or NC EOL DRY or DEOL DOOR Z13 NO or NC EOL DRY or DEOL REX Z14 NO or NC EOL DRY or DEOL INPUT Z15 NO or NC EOL DRY or DEOL INPUT Z16 NO or NC EOL DRY or DEOL Relay Outputs RELAY 1 NO NC RELAY 2 NO NC RELAY 3 NO NC RELAY 4 NO NC wwww EntraPASS com 8641 S Warhawk Rd Con...

Страница 41: ...t Four Door Controller Installation Manual Figure 14 KT 400 Cabinet Inner Door Sticker Diagram North America wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 42: ...38 Figure 15 KT 400 EU Inner Door Sticker Diagram European Union wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...

Страница 43: ...tion 33 of UL 294 fifth edition UL 1076 Compliance Notice The KT 400 is UL 1076 Listed as a Commercial Proprietary Control Unit Accessory and Proprietary Burglar Alarm Unit Section 83 2 with EntraPass and Redundant Server alarm system features KT 300 Controllers ioProx Proximity readers and TRex request to exit devices other sensor devices temperature water level etc may be used as long as they ar...

Страница 44: ...ollowing EntraPASS readers have been validated by UL for the UL 1076 Standard P225W26 P225KPW26 P225XSF P225KPXSF P325W26 P325KPW26 P325XSF P325KPXSF and P600 Note All readers can be ordered with or without the following suffixes BEI BEI SE GRY or GRY SE The KT 400 Ethernet Four Door Controller is UL 1076 listed when used with the APOU ALVY KT NCC Network Communications Controller All alarms shall...

Страница 45: ...ce control output is reset when the preset release time has expired or when the APAS is opened The applicable parameter Input response time for maximum delay time between the occurrence of an event and the annunciation of this event shall be set so that the alert is received at the monitoing console in less than 10 seconds for the worst case configuration of the access control system Please refer ...

Страница 46: ...th a separately energized relay in order to provide 30VA galvanic isolation The output shall be programmed using the EntraPass software to activate when an authorized access has been granted to the respective access point All access granted events shall be annunciated at the monitoring console using the EntraPass software Access granted in conjunction with the access granted annunciation at the mo...

Страница 47: ...1 S Warhawk Rd Conifer CO 80433 Patrick McAllister EntraPASS com 303 670 1099 303 679 8949 fax wwww EntraPASS com 8641 S Warhawk Rd Conifer CO 80433 Tel 303 670 1099 Email Patrick McAllister EntraPASS com ...