POWER FACTOR CONTROLLER

RG3-12C/CS

2. INSTALLATION OF RG3-12C/CS

When RG3-12C/CS is energised for the first time, if the power value

of any phase is negative, it switches on&off the first capacitor step
automatically to recognize the connection error and records the connections.

Later, automatic setup (Refer to page 6 - Automatic setup) is selected

from the menu in order to recognise the connections and connected
capacitor steps automatically.

After automatic recognition, RG3-12C/CS checks all capacitor step

values. If variable loads exist in the system, these variable loads must be
disconnected first and then automatic setup process must be done.
Otherwise, power factor controller may not measure capacitor step powers
correctly. Capacitor step powers and connection types also can be entered
to the power factor controller manually.
(

Refer to page 10 - Setting of the capacitor’s connection and power values

)

After recognising the capacitor step powers, target Cos

j

value is set in order to start the compensation. Factory set value for target
Cos

j

 is ind. 1.000 and Cos

j2

 is ind. 0.900

Note: PFC decreases the switching on&off time to 3 seconds in

Automatic Setup mode but discharge time is not changed. After the

automatic setup process, set values become valid.

After the device is energised, it finds connection errors and corrects
them automatically. Power values of the capacitor steps are measured
automatically according to program selection. If PS-10 program is
selected, power values of all capacitor steps are measured (Refer to
Program Section). If any other program is selected, device measures
first capacitor step value and then calculates other capacitor steps
according to the selected program. For this reason, a 3-phase capacitor
must be connected to the first step. Single phase and/or 3-phase
capacitors can be connected in any order to the other steps. After the
device calculates and saves the capacitor values, it will switch them on
and off when needed.

2.1 Commissioning of RG3-12C/CS

2.2 Capacitor Sequence Setting

3. SETTINGS

3.1.a Manuel Operation Mode Setting

RG3-12C/CS has two operating modes which are automatic
and manual. The operation mode is choosed by selecting the
“Auto Operati” option as 

on

(automatic mode) or 

off

(manual

mode).

 

Manual mode is used for test purposes. In this mode,

capacitor steps are switched on&off to test relay outputs. In
manual mode, capacitor steps are switched on with 

“SET”

button and switched off with 

“ESC”

 button. The conditions of

the steps can be monitored from the 12 step LEDs on the front
panel. C+ LED lights up when a step is switching on and C-
LED lights up when a step is switching off. Factory set values
for switching on (t-on) and switching off (t-of) time are 10 sec.
These values can be changed by the “dELy” menu (

Refer to

Switching on&off Time for Capacitor Steps and Discharge
Time Settings

). In manual mode; step numbers, which will be

switched on&off, can be programmed in “StEP” menu (

Refer

to Step Number Setting

). Even if manual mode is selected,

device switches to automatic mode after 5 minutes continues
to operate in this mode.

3.1 Manual Operation Mode, Automatic Capacitor

Recognition Mode and Automatic Connection Control

Mode

5

Press the 

“SET”

 button for 3 sec. in order to enter to the menu.

Press 

“SET”

 button to set the parameters in “Auto” menu option.

Press 

“UP”

 or 

“DOWN”

 button. To select the automatic operating mode,

choose “

on

” with 

“UP”

 or 

“DOWN”

 buttons and press “

SET

” button. To

select the manual operating mode, choose “

oF

” with 

“UP”

 or 

“DOWN”

buttons and press “

SET

” button.

The first setting in this menu is the operation mode(Operati). The operation
mode of the device is selected according to this options 

on

 or 

off

 selection.

Press 

“SET”

 button to change this setting.

Numerical values of the parameters are set via buttons in the
display. The blinking digit indicates which digit will be set.
Numerical value of the related digit is increased or decreased via

“UP”

 or 

“DOWN”

 button. To set the next digit, 

“SET”

 button is

used. To go back to the previous digit, 

“ESC”

 button is used

.

When automatic mode is selected, AUTO/MAN LED lights up
continuously.
When manual mode is selected, AUTO/MAN LED blinks.

Warning: Device warns user by blinking (short ON, long OFF)

the LED of the capacitor steps which will be switched on. Also

device warns user by blinking (long ON, short OFF) the LED

of the capacitor steps which will be switched off.

For proper operation; 3-Phase, neutral, voltage and current terminals

must be connected as shown in the connection diagram. Device does not
work properly without 3-phase connection.

After the connection of the current and voltage lines, connect the

capacitors to the device. The most important point is connecting a 3-phase
capacitor to the first step. Remaining single phase and 3-phase capacitors
can be connected to the other steps in any order and power values.

After the connection of capacitor steps; J-Type 0-400 V thermocouple

must be connected if temperature measurement function will be used
(Temperature measurement feature is optional).

Lastly, computer communication connection must be done.
Do not energise the device before verifying the connections.

Always connect a 3-phase capacitor to the 1st step.

3 sec.

Содержание RG3-12C

Страница 1: ...scharge Time Settings 8 3 6 Power Value and Connection Type Settings for Capacitors 10 3 7 Current and Voltage Transformer Ratio Settings 12 3 8 Reset Settings 14 3 9 Alarm Settings 15 3 10 Fan Relay...

Страница 2: ...current transformer terminals If you disconnect them be sure to short circuit the terminals or connect them to another parallel load which has a low impedance Otherwise dangerously high voltage at th...

Страница 3: ...f the reactive loads became a necessity in todays energy network Power factor controllers monitor the reactive power of a plant and try to match the power factor value which is defined as the ratio of...

Страница 4: ...NORMAL LED 24 C LED 25 26 27 28 29 30 31 32 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on t...

Страница 5: ...corrects the errors and then calculates the capacitor values After connection errors are corrected capacitor steps are calculated with turning ON the Auto Setup function in Auto menu Refer to Automat...

Страница 6: ...can be monitored from the 12 step LEDs on the front panel C LED lights up when a step is switching on and C LED lights up when a step is switching off Factory set values for switching on t on and swi...

Страница 7: ...ic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be checked Select on or of using the UP and DOWN buttons Select on for...

Страница 8: ...sj values as Cosj ve Cosj2 If there is a voltage between 110 250 VAC present on the generator inputs of the device the target Cosj set on the device is deactivated and target Cosj2 is activated Then t...

Страница 9: ...program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET...

Страница 10: ...f you want to save the changes press the SET button If not press the ESC button Switch off delay time must be set according to system requirement in order to achieve compensation targets and also to p...

Страница 11: ...s power values are calculated according to selected program When setup parameter is selected as of power values of all capacitor steps including first capacitor step can be set manually Note When setu...

Страница 12: ...SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value settings of al...

Страница 13: ...000 For example For a 150 5 current transformer CT ratio must be set as 30 Note Be aware that this value is entered as a ratio not CT primary or secondary value 3 7 a Current Transformer Ratio Setting...

Страница 14: ...indicated in the table in order to select reactive power calculation methode for mechanical and digital energymeters Using the UP DOWN buttons find the reactive energy calculation method menu CALC Pr...

Страница 15: ...turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Using the UP DOWN buttons selec...

Страница 16: ...rvoltage Alarm Setting 3 9 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 9 a a Overvoltage Setting SAUE If you wa...

Страница 17: ...nds If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button The third setting in the voltage menu UoLt...

Страница 18: ...he ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Страница 19: ...ther changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button Press the SET button to enter the alarm ALr se...

Страница 20: ...0 0 99 9 C and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button SAUE If yo...

Страница 21: ...ress the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over voltage harmonic menu tHd which is the fourth setting in the alarm menu In this menu over voltage harmonic value...

Страница 22: ...999 9 seconds and press SET button Using the UP DOWN buttons find capacitor step StEP menu Press the SET button for capacitor step menu which is the third setting in the harmonic menu Using the UP DOW...

Страница 23: ...programmed in this menu The first parameter in the Fan menu FAn is the operating temperature of the fan Press SET button to enter the operating temperature settings Press the SET button to program th...

Страница 24: ...both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the generator input 3 11 Resetting the Energy Counters and Entering the Ene...

Страница 25: ...he energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gEn ACt yES parameter is s...

Страница 26: ...change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button In this menu Parity value can be set as no odd or EVEn 3 11 c Par...

Страница 27: ...SET button If you do not want to set another parameter press the ESC button In this menu user password is activated When the password is activated a pin code is always required before entering to the...

Страница 28: ...you do not want to set another parameter press the ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If y...

Страница 29: ...n Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displayed on...

Страница 30: ...by using UP DOWN buttons when I LED lights When phase current values are displayed if SET button is pressed HAR LED lights odd numbered harmonic values up to 19th harmonic can be observed In the meas...

Страница 31: ...ues are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on t...

Страница 32: ...ng UP DOWN buttons when W and h LEDs light In the example below I indicates that the displayed parameter is import energy and the remaining numbers show the energy value such as 203385706 8 kWh While...

Страница 33: ...ncreased Compensation Error Compensation Error Overheating Defected capacitor step or variable loads Target Cosj is capacitive even if all capacitor steps are switched off Capacitor powers are not suf...

Страница 34: ...g int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10 11 1...

Страница 35: ...06F 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE...

Страница 36: ...126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 PHASE 1 VOLTAGE 13TH HARMONIC P...

Страница 37: ...C 800D 800E 800F 8010 8011 8012 8013 8014 8015 8016 8017 8018 8019 801A 801B 801C 801D 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 809...

Страница 38: ...CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OFF 7TH CAPACITOR STEP SWITCH ON OFF 8TH CA...

Страница 39: ...columns reactive power values of the capacitors in single phase system are shown CAPACITOR CALCULATION TABLE kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr k...

Страница 40: ...1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Contact Generator Input No Volt Feature Setting Rang...

Страница 41: ...Connected to Capacitor Delta Connected to Capacitor Capacitor is not Connected R Phase Connected to Capacitor S Phase Connected to Capacitor T Phase Connected to Capacitor Delta Connected to Capacito...

Отзывы: