POWER FACTOR CONTROLLER

RG3-12C/CS

Warnings :

1.3 Rear Panel

4

CONNECTION DIAGRAM

Current value of 3-Phase fuses, which are connected to protect the capacitors, must be chosen according to the nominal

current value of capacitors which are given by the manufacturer.

** 

Optional.

15

16 17 18 19 20 21

5

6 7 8 9 10

K

L

K

L

K

L

6A

Alarm Relay

11 12

C1

C6

C7

C12

22 23 24 25 26 27 28

2A

2A

2A

k

1

l

1

k

2

l

2

k

3

l

3

k

1

l

2

k

2

l

3

k

3

l

1

29 30 31 32

N
L3

L2

L1

*

*

*

*

Generator

Input

13 14

110~250 V AC

1

2

3

4

L1

L2

L3

N

First, connection type of auxiliary supply, voltage measurement and current measurement input must be         3 phase-neutral. The
device will not operate properly if these connections are not done.
After the device is energized, it finds connection errors and corrects automatically as the first operation. 

Phase current should not be aqual

to zero in order to let the device to detect the connection error.

 Device detects the connection error according to Active Power direction.

Device switches “ON” and “OFF” the 1st step’s 3-phase capacitor during the correction of connection errors (Phase sequence error and
polarity error of Current Transformer). Device may not correct the connection errors if there are too many instant variations for loads and
nonlinear loads (Such as Thyristor or triac controlled frequency inverter, UPS etc.). In this case, user should disconnect the device and restart
it to make the same operation. This feature also can also be operated with “turning ON” the “Auto SET” function in “Auto” menu. In this case
device corrects the errors and then calculates the capacitor values.
After connection errors are corrected; capacitor steps are calculated with turning “ON” the “Auto Setup” function in “Auto” menu (Refer to
“Automatic Capacitor Recognition” menu). 

A 3-phase capacitor has to be connected to 1st step of the device

. All steps are measured

seperately if the program-10 (PS-10) is selected in “Program” menu. In this program (PS-10); single or 3-Phase capacitors can be connected
according to requirements of the system in any order. If you let the device calculate the step power values in the previous step, you can
skip this part.If one of the other programs is chosen, device measures the 1st steps power value and then calculates the other steps values
according to 1st steps value. Device calculates the capacitor values which will be switched “ON” according to selected program and switches
“ON” or “OFF” the necessary steps.
Connection of a circuit breaker or an automatic fuse is highly recommended between the network and RG3-12C/CS. This circuit
breaker must be marked in order to seperate them from other breakers.
All fuses which are used must be FF type and the current values of the fuses must be 2A or  3A and 6A (Refer to Connection Diagram).
The connection to the generator input of the device must be done in a way that the energy comes to the system after the generator
connection to the network has been established. Otherwise, the device will be switched to the generator operation for any generator
starts including the ones for maintaining purposes.
In order make a correct measurement, J type (Fe/Cu-Ni) thermocouple must be connected to “TEMP” terminal.

a)

b)

c)

d)

e)

f)

g)

Fan Relay

38

37

**

33

34

35

36

J Type

Fe/Cu-Ni

+

**

T

EMP.

GND

B

TR

A

RS485

Содержание RG3-12C

Страница 1: ...scharge Time Settings 8 3 6 Power Value and Connection Type Settings for Capacitors 10 3 7 Current and Voltage Transformer Ratio Settings 12 3 8 Reset Settings 14 3 9 Alarm Settings 15 3 10 Fan Relay...

Страница 2: ...current transformer terminals If you disconnect them be sure to short circuit the terminals or connect them to another parallel load which has a low impedance Otherwise dangerously high voltage at th...

Страница 3: ...f the reactive loads became a necessity in todays energy network Power factor controllers monitor the reactive power of a plant and try to match the power factor value which is defined as the ratio of...

Страница 4: ...NORMAL LED 24 C LED 25 26 27 28 29 30 31 32 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on t...

Страница 5: ...corrects the errors and then calculates the capacitor values After connection errors are corrected capacitor steps are calculated with turning ON the Auto Setup function in Auto menu Refer to Automat...

Страница 6: ...can be monitored from the 12 step LEDs on the front panel C LED lights up when a step is switching on and C LED lights up when a step is switching off Factory set values for switching on t on and swi...

Страница 7: ...ic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be checked Select on or of using the UP and DOWN buttons Select on for...

Страница 8: ...sj values as Cosj ve Cosj2 If there is a voltage between 110 250 VAC present on the generator inputs of the device the target Cosj set on the device is deactivated and target Cosj2 is activated Then t...

Страница 9: ...program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET...

Страница 10: ...f you want to save the changes press the SET button If not press the ESC button Switch off delay time must be set according to system requirement in order to achieve compensation targets and also to p...

Страница 11: ...s power values are calculated according to selected program When setup parameter is selected as of power values of all capacitor steps including first capacitor step can be set manually Note When setu...

Страница 12: ...SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value settings of al...

Страница 13: ...000 For example For a 150 5 current transformer CT ratio must be set as 30 Note Be aware that this value is entered as a ratio not CT primary or secondary value 3 7 a Current Transformer Ratio Setting...

Страница 14: ...indicated in the table in order to select reactive power calculation methode for mechanical and digital energymeters Using the UP DOWN buttons find the reactive energy calculation method menu CALC Pr...

Страница 15: ...turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Using the UP DOWN buttons selec...

Страница 16: ...rvoltage Alarm Setting 3 9 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 9 a a Overvoltage Setting SAUE If you wa...

Страница 17: ...nds If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button The third setting in the voltage menu UoLt...

Страница 18: ...he ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Страница 19: ...ther changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button Press the SET button to enter the alarm ALr se...

Страница 20: ...0 0 99 9 C and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button SAUE If yo...

Страница 21: ...ress the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over voltage harmonic menu tHd which is the fourth setting in the alarm menu In this menu over voltage harmonic value...

Страница 22: ...999 9 seconds and press SET button Using the UP DOWN buttons find capacitor step StEP menu Press the SET button for capacitor step menu which is the third setting in the harmonic menu Using the UP DOW...

Страница 23: ...programmed in this menu The first parameter in the Fan menu FAn is the operating temperature of the fan Press SET button to enter the operating temperature settings Press the SET button to program th...

Страница 24: ...both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the generator input 3 11 Resetting the Energy Counters and Entering the Ene...

Страница 25: ...he energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gEn ACt yES parameter is s...

Страница 26: ...change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button In this menu Parity value can be set as no odd or EVEn 3 11 c Par...

Страница 27: ...SET button If you do not want to set another parameter press the ESC button In this menu user password is activated When the password is activated a pin code is always required before entering to the...

Страница 28: ...you do not want to set another parameter press the ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If y...

Страница 29: ...n Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displayed on...

Страница 30: ...by using UP DOWN buttons when I LED lights When phase current values are displayed if SET button is pressed HAR LED lights odd numbered harmonic values up to 19th harmonic can be observed In the meas...

Страница 31: ...ues are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on t...

Страница 32: ...ng UP DOWN buttons when W and h LEDs light In the example below I indicates that the displayed parameter is import energy and the remaining numbers show the energy value such as 203385706 8 kWh While...

Страница 33: ...ncreased Compensation Error Compensation Error Overheating Defected capacitor step or variable loads Target Cosj is capacitive even if all capacitor steps are switched off Capacitor powers are not suf...

Страница 34: ...g int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10 11 1...

Страница 35: ...06F 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE...

Страница 36: ...126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 PHASE 1 VOLTAGE 13TH HARMONIC P...

Страница 37: ...C 800D 800E 800F 8010 8011 8012 8013 8014 8015 8016 8017 8018 8019 801A 801B 801C 801D 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 809...

Страница 38: ...CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OFF 7TH CAPACITOR STEP SWITCH ON OFF 8TH CA...

Страница 39: ...columns reactive power values of the capacitors in single phase system are shown CAPACITOR CALCULATION TABLE kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr k...

Страница 40: ...1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Contact Generator Input No Volt Feature Setting Rang...

Страница 41: ...Connected to Capacitor Delta Connected to Capacitor Capacitor is not Connected R Phase Connected to Capacitor S Phase Connected to Capacitor T Phase Connected to Capacitor Delta Connected to Capacito...

Отзывы: