20

“HIGHEST”

The voltage value corresponding to the maximum value of the selected analog output type is set in
this menu. This value can be entered between -200 and 200V.

Example: 

When the analog output type is selected as 0 - 20 mA and 

“HIGHEST”

 value is set as

100V, current value on the analog output will be 20 mA when the measured voltage becomes 100V.

“LOWEST”

The voltage value corresponding to the minimum value of the selected analog output type is set in
this menu. This value can be entered between -200 and 200V.

Example: 

When the analog output type is selected as 0 - 20 mA and 

“LOWEST”

 value is set as

10V, current value on the analog output will be 0 mA when the measured voltage becomes 10V.

2.2.4 “RS-485” Serial Communication Setting Menu

All measured parameters can be transferred via RS485 line with MODBUS protocol and menus can be set
remotely.

Note:

 Communication feature is available only on 

DCV-10S/10CS/11S/11CS

 models. In order for the

communication to be accomplished; Address, Baudrate and Parity values must be entered to the device
correctly. RS – 485 menu has 3 sub-menus. 

“ADDRESS” , “BAUDRATE” , “PARITY”.

LOWEST

00

LOWEST

SET

03

030

SET

SET

000

LOWEST

LOWEST

V

V

HIGHEST

00

HIGHEST

SET

10

SET

SET

200

HIGHEST

V

HIGHEST

100

V

“ADDRESS” Address Setting

Address information can be entered between 1 and 247.

ADDRESS

ADDRESS

ADDRESS

01

ADDRESS

SET

  001

03

030

SET

SET

PARITY

BAUDRATE

9600

ADDRESS

001

RS-485

SET

BACK MENU

NONE

SET

Содержание DCV-10

Страница 1: ...www entes de DC VOLTMETER DCV 10 10A 10C 10S 10CS 11 11A 11C 11S 11CS User Manual and Menu Map A4741 Rev 1...

Страница 2: ...The device has a 2 year guarantee In case of a malfunction repairs of the device must be done only by the authorised technical service or the guarantee will be void 1 INTRODUCTION 1 1 1 APPLICATIONS 4...

Страница 3: ...a warning signal can be created for the user with Alarm1 C1 and Alarm2 C2 contact outputs if this monitored voltage goes out of the determined range DCV 10C 10CS 11C 11CS With a programmable Analog Ou...

Страница 4: ...the measured voltage 8 Indicates the notification messages or the menu where the user is 9 Units belonging to measurements and analog output parameters 10 Indicates that the contact or contacts are in...

Страница 5: ...2 10V 0 4 20 mA Analog Output connector 3 pin V GND I DCV 10A 11A RS 485 connector 4 Pin DCV 10S 10CS 11S 11CS 2 Relay connectors 4 pin DCV 10C 10CS 11C 11CS Supply input 2 pin 85 265V AC DC DCV 10 10...

Страница 6: ...n value of those samples You can set the sampling time in this menu Period value can be entered between 1 600 seconds PERIOD PERIOD PERIOD 01 PERIOD SET 001 05 050 SET SET 2 2 2 ALARMS Alarms Menu DCV...

Страница 7: ...OFF ALRM STAT CONTCT POS OFF ALRM TYPE HIGH BACK MENU SET ALRM STAT Alarm Status Setting Menu Alarm function of the relay is activated in this menu If OFF option is selected in this menu alarm paramet...

Страница 8: ...entered If the value is entered as 0 zero high alarm is deactivated When the alarm type is selected as High Alarm first contact output opens after an on delay time H ON DEL if the measured voltage bec...

Страница 9: ...ered between 000 0 and 999 9 seconds L OFF DEL It is the delay time for the low voltage alarm to deactivate The value is entered as seconds It can be entered between 000 0 and 999 9 seconds TRIP If th...

Страница 10: ...3 ANLG OUT Analog Output Setting Menu ANLG OUT The device can give a voltage or current output with respect to the measured voltage according to your selection Analog output value can be selected as 0...

Страница 11: ...t value on the analog output will be 0 mA when the measured voltage becomes 10V 2 2 4 RS 485 Serial Communication Setting Menu All measured parameters can be transferred via RS485 line with MODBUS pro...

Страница 12: ...s at the selected baud rate Adress range 1 247 is address of the connected device The data field contains data sent to the slave by master or data sent to master by slave CRC is a error check method b...

Страница 13: ...0 value is written into the addresses that these values are stored Preset Single Register 06H function is used for change device settings and resetting the measured minimum maximum values For example...

Страница 14: ...1 minute 300 s On for 5 minutes 900 s On for 15 minutes Backlight turns off after the selected time if no button is pressed at the end of that time BACK MENU CONTRAST 15 BACKLIGHT YES DISPLYSET SET SE...

Страница 15: ...loaded in this menu A 4 digit password is asked when entering this menu If password protection is active the password isn t asked again when entering this menu because it was entered during entering...

Страница 16: ...Change Password Menu Password is changed in this menu 2 2 10 ESCAPE Exiting Main Menu It is used to exit the main menu If any changes has been made in the menus a confirmation is asked to save those...

Страница 17: ...INSTALLATION 3 1 DIMENSIONS AND INSTALLATION Only for DCV 10C 10CS 11C 11CS Only for DCV 10A 11A Only for DCV 10S 10CS 11S 11CS Only for DCV 11 11A 11C 11S 11CS DCV 10 10A 10C 10S 10CS 85 265V AC DC...

Страница 18: ...Contact Position Output Inverse Off Alarm Type High Alarm High Alarm Value 100V Low Alarm Value 10V High Alarm Hysteresis 10V 33 GND GND B A PC REPEATER MAX 1200 mt MAX 1200 mt TR B A RS 485 RS 232 C...

Страница 19: ...0CS 10 56V DC DCV 11 11A 11C 11S 11CS Frequency 50 60 Hz DCV 10 10A 10C 10S 10CS Supply Input Power Consumption 4 VA Measuring Input Power Consumption 1 VA Measuring Input Resistance Rin 2M Measuring...

Страница 20: ...PR 20 Weight 0 240 kg Installation Class Class III Panel Cutout Dimensions 48X96 mm PR 20 38 Only valid for DCA 10 10A 10C 10S 10CS 11 11A 11C 11S 11CS 6 REGISTER TABLE Trip Active Latch Inactive Lat...

Страница 21: ...ow Hysteresis Alarm 1 High Alarm ON Delay Alarm 1 High Alarm OFF Delay Alarm 2 Latch Function Alarm 2 Trip Function Alarm 1 Low Alarm ON Delay Alarm 1 Low Alarm OFF Delay Alarm 2 Activation Protection...

Страница 22: ...High Alarm ON delay counts b4 0 Relay 1 HighAlarm OFF delay doesn t count b4 1 Relay 1 HighAlarm OFF delay counts b5 0 Relay 1 Low Alarm ON delay doesn t count b5 1 Relay 1 Low Alarm ON delay counts...

Страница 23: ...UTPUT TYPE VOLT RANGE 2 10 V 3 OUTPUT TYPE CURRENT RANGE 0 20 mA 4 OUTPUT TYPE CURRENT RANGE 4 20 mA 0 OUTPUT INACTIVE Backlight Status Contrast Average Period Language Backlight Off Backlight On cont...

Страница 24: ...YPE DEVICE ID DEVICE TYPE Supported Modbus Functions 03H READ HOLD REGISTERS 06H PRESET SINGLE REGISTER 10H PRESET MULTIPLE REGISTERS 2BH READ DEVICE INFO When a reading operation from addresses that...

Страница 25: ...LUE 010 V HIGH HYS 005 V H ON DEL 020 0 HGH VALUE 100 V TRIP NO TRIP TRIP LATCH NO BACK MENU Only valid for DCV 10C 10CS 11C 11CS Selected parameter is displayed Selected parameter is displayed Select...

Страница 26: ...played PARITY 01 24 ADDRESS Last entered value is displayed Only valid for DCV 10S 10CS 11S 11CS ANLG OUT ANLG OUT 0 20 ANLG OUT mA mA ANLG OUT mA ANLG OUT V ANLG OUT V HIGHEST 100 V LOWEST 000 V BACK...

Страница 27: ...d is active LANGUAGE LANGUAGE ENTR PASS ENTR PASS 000 000 FCTRY SET SETTINGS DONE Selected parameter is displayed RESET RESET MIN RESET MAX BACK MENU RESET MIN RESET MAX DISPLYSET BACKLIGHT CONTRAST B...

Страница 28: ...SS ENTR PASS 000 000 PASS ACTV ENTR PASS Selected parameter is displayed SAVE Changes are saved Changes are discarded 120 00 OLD PASS OLD PASS 000 000 NEW PASS 000 AGAIN 000 AGAIN 111 PAS CHNGD If pas...

Отзывы: