19
20
HIGHEST
The voltage value corresponding to the maximum value of the selected analog output type is set in
this menu. This value can be entered between -200 and 200V.
Example:
When the analog output type is selected as 0 - 20 mA and
HIGHEST
value is set as
100V, current value on the analog output will be 20 mA when the measured voltage becomes 100V.
LOWEST
The voltage value corresponding to the minimum value of the selected analog output type is set in
this menu. This value can be entered between -200 and 200V.
Example:
When the analog output type is selected as 0 - 20 mA and
LOWEST
value is set as
10V, current value on the analog output will be 0 mA when the measured voltage becomes 10V.
2.2.4 RS-485 Serial Communication Setting Menu
All measured parameters can be transferred via RS485 line with MODBUS protocol and menus can be set
remotely.
Note:
Communication feature is available only on
DCV-10S/10CS/11S/11CS
models. In order for the
communication to be accomplished; Address, Baudrate and Parity values must be entered to the device
correctly. RS 485 menu has 3 sub-menus.
ADDRESS , BAUDRATE , PARITY.
LOWEST
00
LOWEST
SET
03
030
SET
SET
000
LOWEST
LOWEST
V
V
HIGHEST
00
HIGHEST
SET
10
SET
SET
200
HIGHEST
V
HIGHEST
100
V
ADDRESS Address Setting
Address information can be entered between 1 and 247.
ADDRESS
ADDRESS
ADDRESS
01
ADDRESS
SET
001
03
030
SET
SET
PARITY
BAUDRATE
9600
ADDRESS
001
RS-485
SET
BACK MENU
NONE
SET