background image

ACTIVATE MONITORING

DANGER! 

Electric shock hazard. The DC  

conductors of this PV system are ungrounded  

and may be energized.

7

      Terminate the Unused End of the Cable

A )  Remove 60 mm of the cable sheath from the conductors.
B )  Check that all the terminator parts are present.
C )  Slide the hex nut onto the cable.

D )  Insert the cable end all the way into the cable organizer (up to the 

stop).

E )  Attach the cap.
F )  Attach the terminated cable end to the PV racking with a cable clip or tie 

wrap so that the Engage Cable and terminator do not touch the roof.

hex 

nut

wire  

organizer

cap

WARNING

: Never unscrew the hex nut. This action  

can twist and damage the cable.

Connect to the AC Junction Box/Isolator

Connect the Engage Cable into the AC branch circuit junction box or 

isolator. The Engage Cable uses the following wiring color code.

240 VAC Single-Phase Wires

208 VAC Three-Phase Wires

Black – L1 

Red – L2 

White – Neutral 

Green – Ground

Black – L1 

Red – L2 

Blue – L3 

White – Neutral 

Green – Ground

The green wire acts as equipment ground (EGC). 

8

After you have installed the microinverters, follow the procedures in the 

Enphase Envoy Quick Install Guide

 to activate system monitoring and 

complete the PV installation.

• 

Connecting the Envoy

• 

Detecting the microinverters

• 

Connecting to Enlighten

• 

Registering the system

• 

Building the virtual array

      Connect the PV Modules

Mount the PV modules above the microinverters.

A )  Connect the DC leads of each PV mod-

ule to the DC input connectors of the 

corresponding microinverter.

B )  Check the LED on the underside of the 

microinverter. The LED flashes six times 

when DC power is applied. 

      Energize the System

A )  If applicable, turn ON the AC disconnect or circuit breaker for the branch 

circuit.

B )  Turn ON the main utility-grid AC circuit breaker. Your system will start 

producing power 

after a five-minute wait time. 

C )  Check the LED on the underside of the microinverter: 

LED

Indicates

Flashing green

Normal operation. AC grid function is normal and there 

is communication with the Envoy.

Flashing orange The AC grid is normal but there is no  

communication with the Envoy.

Flashing red

The AC grid is either not present or not within specifi-

cation.

Solid red

There is an active “DC Resistance Low, Power Off” or 

“GFDI” fault. To reset, refer to the 

Enphase M250 and 

M215 Microinverter Installation and Operation Manual

 

at: 

http://www.enphase.com/support

9

status 

LED

bend wires down into 

recesses of wire organizer 

and trim to length

place cap over 

the wire organizer

hold the cap with 

the disconnect tool 

or a #2 screwdriver

rotate the hex nut with 

your hand or a wrench 

until the latching 

mechanism meets the 

base–do not over torque

10

Содержание M215-60-2LL-S22-IG

Страница 1: ...reaker in the load center Design for a voltage rise total of less than 2 for the sections from the microinverter AC branch circuit to the breaker in the load center Refer to the Voltage Rise Technical Brief at enphase com support for more information Best practice Center feed the branch circuit to minimize voltage rise in a fully populated branch PREPARATION A Download the Enphase Installer Toolki...

Страница 2: ...lectricity network connection using equipment and practices as required by local jurisdictions 2 WARNINGS Install the microinverter under the PV module to avoid direct exposure to rain UV and other harmful weather events Do not mount the microinverter upside down or in a vertical position that allows water to collect in the DC connector recess as it may have a harmful effect on the long term endur...

Страница 3: ...ing the microinverters Connecting to Enlighten Registering the system Building the virtual array Connect the PV Modules Mount the PV modules above the microinverters A Connect the DC leads of each PV mod ule to the DC input connectors of the corresponding microinverter B Check the LED on the underside of the microinverter The LED flashes six times when DC power is applied Energize the System A If ...

Страница 4: ... allow contamination or debris in the connectors Use the terminator cap and cable connections only when all parts are present and intact Do not install or use in potentially explosive environments Do not allow the terminator to come into con tact with open flame Make sure that all terminator cap seals are seated correctly in the wire organizer Fit the terminator cap using only the prescribed tools...

Страница 5: ...om Use this map to build the virtual array in Enlighten s Array Builder Escanee el mapa completo y cárguelo en Enphase Haga clic en Añadir nuevo sistema en https enlighten enphaseenergy com Utilice este mapa para crear el conjunto de paneles virtual en el Creador de conjuntos de paneles de Enlighten A B C D E F G H J K L M 1 2 3 4 5 6 7 To Sheet A la hoja de ________ To Sheet A la hoja de ________...

Отзывы: