Feed through header for Generator I/O
Use the 3-pin feed through header for Generator dry contact connec-
tions. It is recommended to install this feed through header in Enpower
even if you are not currently planning to use the Generator feature.
This ensures that the header will not get lost. Use pins 1 and 3 on the
header for inserting wires. Supports AWG 28 to AWG 16 wire sizes.
Torque for tightening the screws on the top is 0.22 N•m (1.9 lb•in) to
0.25 N•m (2.2 lb•in).
2. Tighten these screws to
hold the wires in place
3. Insert into I/O port on En-
power in this orientation
Insert wires in these
terminals
The Enphase Enpower Lit Kit contains screws, feed through headers, filler plates and labels that enable you to properly install Enpower and configure
features such as PCS (power control system), load control with auxiliary contacts, and generator integration.
Q U I C K
I N S T A L L
G U I D E
Model number: EP200G-LITKIT
Instructions to use the
Enphase Enpower
Literature Kit
(Lit Kit)
The contents of the Lit Kit and how to use them
are
described below:
8-32 screw
Use the 8-32 screw from the lit kit to secure the mains breaker (not the load
breaker) to Enpower. Use a T20 drive to tighten the 8-32 screw to 1.5 N•m
(13.3 lb•in). Do not use any other screw.
Install 8-32 screw
with 1.5 N.M
torque
Feed through header for I/O-1 and I/O-2
Use the two 4-pin feed through headers shipped with the lit kit for
making auxiliary contact connections
for load control and excessive
PV shedding.
It is recommended to install these feed through headers
in Enpower even if you are not currently planning to use load control
and PV shedding features. This ensures that these headers will not get
lost. Supports AWG 28 to AWG 16 wire sizes. Torque for tightening the
screws on the top is 0.22 N•m (1.9 lb•in) to 0.25 N•m (2.2 lb•in).
Lit Kit label
If Enpower is installed as service equipment:
• Connect a grounding electrode conductor to the grounding bar.
• From the lit kit, place the label “GROUNDING ELECTRODE TERMI-
NAL” adjacent to the grounding bar.
• From the lit kit, place the label “SUITABLE FOR USE AS SERVICE
EQUIPMENT”/ “MAIN SERVICE DISCONNECT” on the deadfront
near the main breaker/service disconnect.
• If Enpower is not used as service equipment, these labels should
not be used.
© 2021 Enphase Energy. All rights reserved. Enphase, the Enphase logo, Enpower smart switch, Encharge storage system, Envoy, Combiner, Microinverter,
Installer Toolkit, Enlighten and other trademarks or service names are trademarks of Enphase Energy, Inc. Data subject to change. 04-16-2021
rev.
Modificaton
ECN
Date Drawing Approved
Material
Hardness
Finish
Description
Stainless steel A2-70
Customer Code
Customer P/N
& drawing no.
Drawing No.
Article No.
Scale
Size
UNSPECIFIED TOLERANCES
Version
QP Level
Q2
02
All dimensions are in inch
Third angle projection
00 Created
N/A
2019/12/4 Mary He Don Tang
A4
Not ot Scale
6358144
Business Unit
BOC
Important Disclaimer
The technical recommendations contained in this publication are necessarily of a general nature and should not be relied on for specific applications without first
securing competent advice. Whilst Bossard has taken all reasonable steps to ensure the information contained herein is accurate and current, Bossard does not
warrant the accuracy or completeness of the information and does not accept liability for errors or omissions.
Hexalobular socket pan head machine
screw #8-32UNCX0.63
0.306-0.322
0.105-0.115
0.63
0
-0.03
#8-32UNC
Hexalobular Drive X20
Note:
1.Without burr,Sharp edges or other disfigurements.
2.The part is RoHS compliance.
3. Refer ASME B18.6.3
.
4. Comply with thread locking standard IFI 124.
Passivation
02
Q2
Mary He
Mary He
2019/12/9
6358144
0.055-0.070
01 Add nylon patch.
N/A
2019/12/5 Mary He Don Tang
Nylon blue patch (half circle
90° ~180° ), cover 4-6
threads, 1-2 lead thread
free of locking material
02
Change nylon patch standard to IFI 124 for inch screw, was IFI 524.
N/A
2019/12/9 Mary He Don Tang
730-00305
1. Insert wires here
4. Tighten these screws to se-
cure the feed-through header
to the I/O ports on Enpower
Feed through headers for
I/O-1 and I/O-2
Feed through header
for Generator I/O
2
3
4
1