INSTALLATION

       Plan a location for the Encharge batteries

The Encharge housing is NEMA type 3R and can be installed indoors or out-

doors. The terminal blocks accepts copper conductors of No. 12 - 8 AWG.
A ) 

Following local standards, 

choose a well-ventilated location where 

the ambient temperature and humidity are within -15° C to 55° C 

(5° F to 131° F) and 5% to 100% RH, non-condensing, preferably 

out of direct sunlight. The optimum ambient temperature range for 

installation location is  0º C to 30º C (32º F to 86º F).

B ) 

Ensure that the mounting location can sustain the total weight 

of the Encharge batteries and mounting bracket. 

Total weight for 

the Encharge 3, including the Encharge base unit, cover and wall 

mount bracket, is 52 kg (114.6 lbs). Total weight for the Encharge 

10, including the three Encharge base units, cover, and wall mount 

bracket, is 154.7 kg (341 lbs).

*

 WARNING: 

The installer should install blocking between studs 

to ensure that no single stud carries the entire weight load of the 

Encharge batteries.

C )  Plan the mounting location to be at least 15cm (six inches) off the 

ground and 15cm (six inches) from the ceiling. Keep the Encharge 

away from falling or moving objects, including motor vehicles.

*

 WARNING: 

If mounted in the path of a motor vehicle, we 

recommend a mounting height that is 91 cm (36-inch) minimum 

above the floor.

D )  Ensure that there are no pipes or electrical wires where you plan to drill.
E )  Plan to maintain at least three feet of clearance in front of each 

Encharge. Allow at least 15cm (six inches) clearance on top and 

bottom of the Encharge so that the vents on the top and bottom of 

the units are not blocked for air circulation.

F )  Consider the dimensions of the Encharge batteries, easy access, 

height, and length of cable when selecting the location. 

G )  Select a location where you can interconnect to the Enphase 

Enpower smart switch.

H )  Follow all local standards. 
J )  Review your external conduit plan to determine to which side of the 

field wiring compartment you will connect conduit.

K )  Up to two Encharge 10 (or six Encharge 3) units can be daisy 

chained on one circuit. For installations with more than this number 

of units, there must be a separate load center, subpanel, or circuit 

combiner with over current protection to combine the daisy chained 

circuits, and you must run only one circuit for all the Encharge 

units to the Enpower (or to Enphase IQ Combiner for grid-tied-only 

installations). You must select proper conductors and AC discon-

nects for these circuits according to local codes, standards, and 

other applicable requirements. Enpower supports up to a maximum 

of 80 A breaker for Encharge connection circuit. 

 

The subpanel could be a small, two circuit box with circuit breakers 

(the drawing only shows switches). The circuit breakers in the box 

would have to be suitable for back-feeding, per NEC 408.36(D). 

 

Select the right size subpanel and breakers based on the number of 

Encharge units being installed. If there are only three Encharge 10s, 

for example, then you can use a box with current rating less than 80A.

 

To do this, you must  purchase an off-the-shelf subpanel and install 

as shown in the following image:

1

       Install the AC disconnect

Following all local codes and standards:

 

A )  Install an AC disconnect that can break the maximum rated current 

of the branch circuit under load. The AC disconnect must be 

installed in line-of-sight of Encharge, per NEC 2017 706.7(A).

B )  Each Encharge unit is suitable for use with up to No. 8 AWG wires 

on a maximum 40 A branch circuit. If more than 32 A of Encharge 

batteries (corresponding to a 40 A branch circuit) are installed, a 

separate subpanel must be installed between the Encharge units 

and Enpower to combine the Enpower circuits together. All circuit 

breakers in the subpanel must be suitable for back-feeding, per NEC 

408.36(D).

C )  Verify that AC voltage at the site is within range: single-phase L1 to L2 

voltage must measure between 211 and 264 VAC, while L-N should 

measure between 106 and 132 VAC.

2

     Prepare to install the wall-mount bracket

A )  Make sure that the planned position for the wall-mount bracket 

meets clearance requirements as shown. The image depicts a 

single bracket, but clearances and requirements are the same for 

the triple-width bracket.

B ) 

Ensure that the mounting location can sustain the weight of the 

Encharge batteries and mounting bracket. Total weight for the 

Encharge 3 including the mounting brackets and cover is 52 kg 

(114.6 lbs), while the total weight for Encharge 10 including the 

mounting bracket and cover add up to 154.7 kg (341 lbs). 

C )  Starting at installation position closest to the power source, mark a 

level line on the wall as a guide. 

WARNING!

 Multiple risks. Make sure not to drill or attach into 

electric wiring or pipes that are in the wall!

3

Minimum 15cm 

(6 inches) from 

ground/next 

surface below

Minimum 15cm 

(6 inches) from  

ceiling/next  

surface above

Blocking installed 

between studs

Wood screw 

7.6 cm (#10x3”)

Encharge Battery

P R 

E L 

I M

Содержание ENCHARGE Series

Страница 1: ... 10 Encharge 3 storage system Generator Future IQ 6 IQ 7 M IQ Combiner Enpower smart switch Home Loads Main Load Panel Wireless Whole home backup with Enpower as service entrance and PV combiner connected to Enpower This is the preferred configuration for back up of the entire main load panel This configuration supports up to an 80A breaker for the PV circuit and an 80A breaker for battery storage...

Страница 2: ... structural engineer and local standards for requirements Three 10 lag bolts or screws 7 6 cm 3 inches long depending on attachment wall for each single wide wall mount bracket Nine 10 lag bolts or screws 7 6 cm 3 inches long depending on attachment wall for each triple wide wall mount bracket Washers for use between fastener heads and wall mount bracket Copper conductors No 12 8 AWG 11mm 7 16 inc...

Страница 3: ...mbiner for grid tied only installations You must select proper conductors and AC discon nects for these circuits according to local codes standards and other applicable requirements Enpower supports up to a maximum of 80 A breaker for Encharge connection circuit The subpanel could be a small two circuit box with circuit breakers the drawing only shows switches The circuit breakers in the box would...

Страница 4: ... to the wall so that it is no more than five percent from vertical See the following image for reference Encharge 10 triple width bracket A Place the wall mount bracket on the wall so that the mounting holes in the middle of the bracket align with the center of the stud and the mounting holes on the left and right align with the adjacent studs B Use a level to keep the bottom of the wall mount bra...

Страница 5: ...Together lift the Encharge battery and bring it to the already mounted bracket G Hold the Encharge battery at an angle so the top of the unit sets into the top of the wall mount bracket WARNING Risk of injury and equipment damage Do not release the Encharge battery unit until you ensure that the Encharge battery unit is fully seated in the wall mount bracket shelf H Once the top of the battery is ...

Страница 6: ...onduit opening has a groove around the hole to fit the O ring red of the raceway Make sure that the O ring is captured in the groove between the Encharge enclosure and the raceway flange adjacent to the O ring 6 Install conduit and field wiring continued E Using the conductors and suitable conduits connect the AC disconnect and the first adjacent Encharge Battery Use the conduit openings provided ...

Страница 7: ...ol kit help topics for more information After the IQ Envoy has detected the Encharge Battery ies the Encharge LEDs operate as described in the following section CONFIGURE and ACTIVATE OPERATION a LED overview After being commissioned the LED flashes yellow while each Encharge Battery boots up If the LED rapidly flashes green for more than two minutes the battery is in trickle charge mode and will ...

Страница 8: ...ncharge Battery ies in storage ensure that AC power is not present and that the DC switch is in the Locked position While in storage damage to the battery can occur from over discharge If the battery state of charge falls to 0 the Encharge Battery ies can be damaged or destroyed Because of this the Encharge Battery ies must only be stored for a limited amount of time The Encharge Battery ies must ...