Section 40
8
00-02-1150
2018-10-08
Wiring Instructions
PIN Specifications for 8 Position Amphenol Connection
PIN
8 Pin
1
Battery (+)
2
CAN +
3
CAN -
4
RS485 +
5
RS485 -
6
Digital I/O
7
Ig
8
Battery -
Wiring of this device must meet all applicable electrical codes.
When the accessory harness is used, the PowerCore controller in the panel will need the I/O
established prior to use:
•
TEC-10 and ML1000: Set the Digital Output 2 function to Ignition On
(On in Standby).
•
ML2000: Set the Digital Output 4 function to Ignition On
(On in Standby).
NOTE:
If the application is left in Auto mode, a battery maintaining system should
be installed for possible battery drain due to parasitic loads of ancillary devices
on the system.