3.3
List of parameters and possible modifications
Proceed as follows to set the configuration parameters:
–
press the
S
key for 4 seconds
–
the display reads out “
PA
”
–
press the
S
key
–
within 15 seconds, enter the parameter “
PAS
” (password) using the
A
and
V
keys. The default value is -19
–
scroll through the parameters using the
A
and
V
keys until you reach the parameter you want to change
–
press the
S
key
–
within 15 seconds, press the
A
and
V
keys to set the value
–
press the
S
key
–
to exit the procedure, press the
S
key or wait for 60 seconds.
The following parameters are the most frequently used:
Parameter
Description
Default
Range
U.M.
min.
max.
Setpoint
SP
Setpoint
4
r1 (installer) r2 (installer)
°C/°F
Inputs
P2
Unit of measure of temperature:
- 0 = degrees Celsius (°C)
- 1 = degrees Fahrenheit (°F)
0
0
1
- - -
P5
Quantity displayed during functioning:
- 0 = ambient temperature
- 1 = operating setpoint
- 2 = value of second analogue input
0
0
2
- - -
Defrosting
r0
Operating setpoint differential
2
0,1
15
°C/°F
d2
Evaporator temperature at end of defrosting
2
-99
99
°C/°F
d7
Duration of dripping time
2
0
15
min
Alarms
A1
Ambient temperature below which minimum temperature alarm
is activated
0
0
99
°C/°F
A4
Ambient temperature above which minimum temperature alarm
is activated
40
0
99
°C/°F
A7
Minimum temperature alarm delay
15
0
240
min
Fans
F1
Evaporator temperature under or over which the evaporator fan is
switched off
-1
-99
99
°C/°F