background image

 

TOC1314NUEN_1013

 

                                               4/4 

 

  
10020057.xx  detectors  transmit  the  state  of  the  dry  contact  using  the  frame  described  in  the 
document EnOcean Equipment Profiles EEP §D5-00-01 (consultable under 

www.enocean.com

). 

   

5.1 Detection: 

  

Each time the dry contact changes state, open to closed or vice-versa, a radio signal is immediately 
transmitted. Moreover a signal containing the state of the contact will be sent approximately every 
15 minutes. 
 

   

 

 

5.2 Programming and LRN button:     

                            

Switch  the  receiver  to  learn  mode  and  by  pressing  the 
LRN button placed behind the sensor, initiate the sending 
of an association frame. 
Where the sensor is located on its base, it must first of all 
be unclipped from the base to allow access so that it can 
be  placed  closed  to  the  matched  receiver  during  the 
identification  or  association  phase  (the  receiver  having 
reduced sensitivity during this phase). 

  

  
 

   

6.1 New or existing installation 

  

 

• If the receiver functions at a shorter distance relative to the sensor, it is subject to interference or 
use outside the transmission range. 
•  Search  the  system  environment  for  changes  that  could  cause  the  interference  (for  example 
movement of metallic cabinets, furniture or partitions). 
• Use the sensor or receiver in a more suitable location. 
• Clear the receiver and perform a new learn process. 

      

6.2 Limitation of the range of the radio signals 

   

•  Transmitter/receiver  used  close  to  metallic  objects  or  close  to  materials  containing  metallic 
elements. Observe a distance of at least 10 cm. 
•  Humidity in the materials. 
•  Devices emitting high frequency signals such as audio and video systems, computers, electronic 
ballasts or fluorescent tubes. Observe a distance of at least 0.5 m. 

      

6.3 Contacts 

   

E-mail:............................ [email protected]

 

   

 
 

  

These products can be marketed and distributed in the countries of the European Union, 

Switzerland, Iceland and Norway. 

TRI

0

2

SYS

 hereby declares that the sensors 10020057.xx 

conform to the base requirements and other applicable requirements of the directive 1999/5/CE 
referred to as R&TTE.

 

 

6. Troubleshooting 
ion and initial use

 

5. Controls and functions 
ion and initial use

 

7. Declaration of conformity 

Touche LRN

 

 

TOC1314NUEN_1013

 

                                               1/4 

 
 
 
 
 
 
 
 

  

 
 

   
 

1.1 Use 

  

   

Sensors 

0

2

LINE

 

10020057.xx are designed to detect any changes in state of equipment having a 

dry  contact  output,  normally  open  (preferred)  or  normally  closed.    They  are  used  to  connect  any 
products  reporting  an  On-Off  state  to  the  EnOcean  protocol  where  it  is  either  not  desired  or  not 
possible to connect them via a wired connection. 
The sensor is equipped with a wire that can be connected to the dry contact. The sensor is supplied 
by  a  solar  cell  and  consequently  is  maintenance-free.  As  soon  as  the  dry  contact  changes  state 
(open  to  closed  or  vice-versa)  a  radio  signal  is  immediately  transmitted.  Moreover  the  signal  is 
retransmitted every 15 minutes. 
Before any use, the sensor must be associated with a receiver (maximum 2 sensors). Each sensor 
can control an unlimited number of receivers. 
Note:

 

Read the operating manual carefully before initial use. 

  
 

1.2 Guarantee terms 

    

This operating manual is an integral part of the device and our guarantee terms. It must always be 
delivered to the user. We reserve the right to  modify the technical design of these devices without 

warning. 

TRI

0

2

SYS

 

products  are  manufactured  and  their  quality  checked  by  making  use  of  the 

latest  technologies  and  taking  into  account  the  applicable  national  and  international  directives.  If 

nevertheless  a  fault  arises, 

TRI

0

2

SYS

  undertakes  to  remedy  the  default  as  follows,  without 

prejudicing the rights of the end customer that arise from the sales contract with his reseller: 

If  the  event  of  exercising  of  a  legitimate  and  regular  right 

TRI

0

2

SYS

,  may  at  its  sole  discretion, 

rectify  the  device  fault  or  supply  a  fault-free  device.  Any  claim  beyond  this  and  all  claims  for 
consequential damages are excluded. 
A  legitimate  fault  exists  if  the  device  cannot  be  used  at  the  time  of  delivery  to  the  end  customer 
because of a design or manufacturing defect or if its practical use is severely limited. The guarantee 
is void in cases of natural wear and tear, incorrect use, incorrect connection, where the device has 
been  repaired  or  external  influence.  The  period  of  guarantee  is  24  months  (from  the  date  of 
invoicing). French law applies to the regulation of guarantee rights. 

   
 

1.3 Recycling of the device 

   

To recycle the device, conform to the legislation and standards in force in the country of use. 

  

 
 

 
 

WARNING! Risk of electric shocks! (See UTE C18-150) Where a connection is 
made  to  an  equipment  item  which  is  not  connected  to  a  very  low  safety 
voltage  (TBTS)  or  via  an  autonomous  power  supply,  a  fault  in  or  lack  of 
insulation of the latter could cause injuries in the event of accidental contact; 
this includes contact with our sensor! All  work on the mains supply network 

and the connected device must only be carried out by authorised professional technicians. 
 

 1. General 

TRI

0

2

SYS

 sarl 

– 8 grande rue le village 

21160 FLAVIGNEROT

 

 2. Safety 

 

Installation and operating manual 

 Wired dry contact sensor 

  
 Ref. 
10020057.xx 

EN

 

Отзывы: