background image

LED Zone Controller 0-10V Installation Guide  

© 2017 EnOcean GmbH    V2.0 

 

Page  1 

 

 

Package Contents 

Tools Required 

n

 

LED Zone Controller 

n

 

Screwdriver 

n

 

Wire nuts 

 

Product Description 

The LED zone controller (LEDD) uses wireless technology to 
communicate with other self-powered EnOcean based 
products and provides an amazingly simple solution for 
dimming control of LED lighting.  
LEDD is directly supplied from the auxiliary 12V supply 
output of a connected LED driver. Its compact size enables 
flexible installation inside of or next to electrical boxes and 
fixtures so it can be easily wired out of sight using standard 
wiring practices.  
Simply link the module to an EnOcean-based motion sensor, 
light level sensor or rocker switch and experience levels of 
efficiency and convenience that can only be achieved 
through wireless controls.  
It is also possible to link LEDD to a central controller or via a 
gateway to building automation systems like BACnet. 
Product Features Include: 

n

 

Enables wireless dimming of a single fixture or a zone of 
multiple daisy chained LED fixtures (e.g. 20 each 30W or 
10 each 60W). 

n

 

Supports California Title 24 daylight harvesting scenarios, 
occupancy control and manual dimming with input from 
self-powered wireless switches and sensors. Implements 
load shedding initiated by separate Demand Response 
Controllers 

n

 

Installs inside or mounts to electrical box using threaded 
connector 

n

 

Supports wireless remote commissioning to link devices 
and set parameters

 

Specifications (typ. values) 

Power Supply 

11.0 V – 13.2 V DC 

Supply Current (typ)  16 mA @12VDC supply (no sourcing) 

38 mA @12VDC supply  
(10V/20mA sourcing) 

Power Consumption  < 200 mW @ 12 V DC  

(excluding 0-10V sourcing power) 

< 460 mW @ 12 V DC  

(at maximum 0-10V sourcing power) 

0-10V output 

Tole3%/-4% (1-10V range) 

Current sourcing / sinking 20 mA*

 

* F

or high sinking current and dim value settings 

below 1V, the output voltage may exceed the 
selected output value and reach 1V max.

 

Inputs/Outputs 

Flying-lead style wires: 

n

 

2 power input wires 

n

 

2 output wires for 0-10V control 

Local User Interface  2 Buttons, 1 LED for device    

configuration & manual control 

RF Standard 

EnOcean 902 MHz (LEDRU) 

Transmission Range  80 ft. (25 m) 
EnOcean Equipment 

Profile 

D2-40-00 with RECOM 
Compatible with Navigan™ 

Interoperable 

Products / EEPs 
(EnOcean 
Equipment Profiles) 

 

Rocker Pad Switch (F6-02-02) 

Occupancy Sensor (A5-07-01) 
Occupancy Sensor (A5-07-02) 
Occupancy Sensor (A5-07-03) 
Light Level Sensor (A5-06-02) 
Light Level Sensor (A6-06-03) 
Central Controller (A5-38-08) 
Demand Response (A5-37-01) 

Dimensions 

2.24” H x 1.65” W x 1.2” D 
(57mm x 42mm x 30mm) 

Weight 

2.5oz. (70g)

 

Mounting 

n

 

Connect to electrical boxes and   
fixtures using threaded nipple 

n

 

Install inside standard electrical box 

Environment 

n

 

Indoor use only 

n

 

32° to 140° F (0° to 60° C) 

n

 

20% to 95% relative 
humidity  (non-condensing) 

Agency Compliance  FCC, IC 

UL 2043 plenum rated 

 

 

 

Содержание LEDD

Страница 1: ...ntrollers n Installs inside or mounts to electrical box using threaded connector n Supports wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 11 0 V 13 2 V DC Supply Current typ 16 mA 12VDC supply no sourcing 38 mA 12VDC supply 10V 20mA sourcing Power Consumption 200 mW 12 V DC excluding 0 10V sourcing power 460 mW 12 V DC at maximum 0 10V sour...

Страница 2: ...enna as shown in figure A 4 Restore power to the circuit 5 Use the setup interface to link devices and configure settings refer to the Linking Configuration sections WARNING Move the module away from any power line before using the local setup interface 3 Device Configuration The LED controller can be configured in two ways n By user input to the local setup interface This approach is used for bas...

Страница 3: ...e will stop after 30 seconds if no LRN telegram is received 2 For the transmitter to be linked do one of the following according to the type of device A Sensor click the designated link button B Rocker Pad click the I button top button marked on the switch plastic or I symbol on the back of the switch 3 times quickly 3 If the device has been linked successfully the LRN LED will display solid green...

Страница 4: ...rtly press DIM and LRN button simultaneously to store this value 5 Operating modes The LED Controller supports the following operation modes based on different types of connected devices Mode Default Action Title 24 Compliance Switches only Manual DIM or ON OFF No Occupancy sensors only Auto ON Auto OFF default Auto OFF after 15 minutes No Occupancy sensors and switches Manual DIM or ON Auto OFF C...

Страница 5: ...tion for a period defined by OccAutoOffTimer default 15min then light is set to OccAutoOffLevel default 0 Auto OFF function Ramp up SensorRampUpSpeed speed for Auto ON and ramp down SensorRampDownSpeed speed for Auto OFF are configurable default 20 per second Occupancy Sensors and Switches Light can be switched ON OFF manually function as described above Time based automatic switch OFF as defined ...

Страница 6: ...meter to 0 will cause all messages to be repeated Note 2 level repeating function and repeating of all messages RepeatLinkedDevicesOnly OFF should only be used if really needed Otherwise the system function can be compromised by collisions of telegrams Status messages The LED controller will transmit a status message EEP D2 40 00 after change of its output state or after StatusMessageTimer has ela...

Страница 7: ...y or light level sensor 2 point mode 20 s 0 No ramp immediate Parameter Description Default Notes Rocker Switch Parameters RockerSwitch OnSpeed Ramp up speed when rocker input request light switch ON 20 s 0 No ramp immediate RockerSwitch OffSpeed Ramp down speed when rocker input request light switch OFF 20 s 0 No ramp immediate RockerDim UpSpeed Ramp up speed when rocker input request light dim U...

Страница 8: ...usMessage Timer Defines how often status messages are transmitted seconds 0 off 0xFFFF only event based 0xFFFF RepeaterFunction Defines the repeater level of the device OFF 1 Level 2 Level OFF disabled RepeatLinked DevicesOnly Configures the repeater to only repeat telegrams from devices linked to it ON enabled Enable DebugMessages Enable or disable debug messages OFF disabled EnableLink Checker E...

Отзывы: