background image

 
 

EnOcean GmbH 
Kolpingring 18a 
82041 Oberhaching 
Germany 

Phone  +49.89.67 34 689-0 
Fax 

+49.89.67 34 689-50 

[email protected] 
www.enocean.com 

Subject to modification 
EPM 300(C) User Manual  
October 1, 2010 10:15 AM 
Page 1/11 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

EPM 300(C) Installation Test Tool 

User Manual Template for OEM Manufacturers/First Marketer

 

Содержание EPM 300

Страница 1: ...any Phone 49 89 6734 689 0 Fax 49 89 6734 689 50 info enocean com www enocean com Subject to modification EPM 300 C User Manual October 1 2010 10 15 AM Page 1 11 EPM 300 C Installation Test Tool User Manual Template for OEM Manufacturers First Marketer ...

Страница 2: ...y is assumed for possible omissions or inaccuracies Circuitry and specifications are subject to change without notice For the latest product specifications refer to the EnOcean web site http www enocean com As far as patents or other rights of third parties are concerned liability is only assumed for modules not for the described applications processes and circuits EPM 300 and EPM 300C are designe...

Страница 3: ...USER MANUAL 2010 EnOcean www enocean com EPM 300 C OEM User Manual Page 3 11 EPM 300 C Content 1 Introduction 2 Technical Data 3 Overview 4 Getting Started 5 Approvals 6 Recommendations ...

Страница 4: ... available for original equipment manufacturers OEM s using EnO cean technology within there products 2 Technical Data Housing size 110 x 70 x 25 mm OEM label size 43 x 20 mm Weight 85 g w o battery Battery AA LR06 cell recommended Energizer L91 Operation temperature 0 C 45 C Storage temperature 15 C 65 C Operation humidity 0 95 r h Storage humidity 0 98 r h Product category IP54 R TTE EN 300 220 ...

Страница 5: ...ouch on the left sensor button for more than 2 s Operation modes will be changed via finger touch 1 s on right sensor button Current mode will be indicated by four indicator LEDs The device can be switched off via on off sensor button on the left side Radio signal intensity On off button Valid EnOcean telegram Mode button Mode selection indicators ...

Страница 6: ...attery low will be indicated by flashing mode LED 3 Send EnOcean telegram by pushing a self powered switch e g PTM 200 or by pressing the learn button of a self powered sensor 4 Signal strength RSSI value will be shown by a reverse traffic light EPM 300 signal strength 5 Valid LED shows if a valid telegram PTM switch or sensor teach in telegram has been received Valid EnOcean PTM or teach in teleg...

Страница 7: ... the received tele gram is received at a very low RSSI level without link budget Signal High without Valid indicates a high level of background noise on the same carrier frequency This could be from other This signal will disturb EnOcean telegrams Signal Low without Valid indicates a medium level of background noise on the same carrier frequency This noise can come from EnOcean sensor or system te...

Страница 8: ... for about 60s This is used to test radio telegram range by a single person installer Application example o Position EPM 300 C at desired actuator receiver position o Go to required switch or sensor position and push the button o Go back to the EPM 300 C and observe signal level held for 60s Attention This mode only provides reliable information if no other switch or learn tele grams have been sen...

Страница 9: ... EPM 300 C as RLT slave Application example o EPM 300 C is placed at switch sensor position and switched to RLT mode o AFT is placed at receiver position also in RLT mode o Start the test on the AFT it will automatically show a detailed analysis of the connection For details see radio link test protocol specification at http www enocean alliance org de downloads Mode LED flashing indicates battery...

Страница 10: ... device may not cause harmful interference and ii this device must accept any interference received including interference that may cause undesired operation 5 3 IC Canada EPM 300C 315Mhz is based on the EnOcean STM 300C radio module This module has an limited modular approval according to FCC The conformity has been proven and the ac cording documentation has been deposited at EnOcean Contains IC...

Страница 11: ...er The transmission range also depends on the materials used in the building The transmission range is reduced by increasing the distance between transmitter and receiver shielding by metal or massive walls mounting transmitter or receiver on the floor or close to the floor high humidity in materials devices generating RF interferences such as computers audio video equipment or electronic gear con...

Отзывы: