USER MANUAL
EMDC
–
ENOCEAN MOTION DETECTOR AND LIGHT LEVEL SENSOR
© 2020 EnOcean | www.enocean.com
EMDC User Manual | v1.0 | March 2020 | Page 63/75
9.5.20
LIGHT_TX_INTERVAL
If solar cell illumination-controlled reporting has been enabled and the solar cell illumina-
tion is above the defined threshold then the resulting reporting interval will be determined
by the register LIGHT_TX_INTERVAL shown in Figure 43 below.
LIGHT_TX_INTERVAL
Bit 15
Bit 14
…
Bit 1
Bit 0
LIGHT SENSOR INTERVAL
Figure 43
–
LIGHT_TX_INTERVAL register
The encoding used by the LIGHT SENSOR INTERVAL bit field is shown in Table 25 below.
LIGHT SENSOR INTERVAL
Light sensor illumination-based reporting interval
0x0000, 0x0001, 0x0002
Not supported (Do not use)
0x0003
3 seconds (minimum setting)
…
…
0x003C (Default)
60 seconds (default setting)
…
…
0xFFFF
65535 seconds (maximum setting)
Table 25
–
LIGHT SENSOR INTERVAL bit field encoding
The default reporting interval while the light level measured by the light sensor is above the
light sensor illumination threshold is 60 seconds. This can be reduced according to user re-
quirements keeping in mind the energy balance.