3.2 Wiring the EX-5120 to a Control Unit 

C

AUTION

:

 

Area must be declassified during installation.

 

Run conduit and 16 

AWG 

(1.5

MM

2

)

 wires to the enclosure from the power supply and controller.  If the 

EX-5120 

is installed in 

a hazardous location as defined by the National Electrical Code, then ALL wiring must be in accordance with the National code 
and any local governing codes. 

Open the enclosure, and remove the 2 screws that retain the display overlay to the circuit board.   

Use caution when removing the over lay.  Do not damage the magnetic switches.   

Remove the two overlay standoffs and remove the circuit board, exposing the terminal strips on the bottom of the circuit board.  
Do not disconnect the circuit board wiring. 

Connect the wires from the controller (power supply) to the supplied J4 plug then attach to J4 terminal. 

Connect the wires from the sensor to the supplied J8 plug then attach to the J8 terminal. 

See Figure 3 for locations 

J4

 

P

LUG 

 

T

ERMINAL TO 

C

ONTROLLER 

W

IRING

 

Position 

Function 

+ 

24 

V

DC

 

power 

 

GND  

s

 

4 - 20 mA out 

4* 

RS-485 D+ 

5* 

RS-485 D– 

*Contact 

ENMET

 for Modbus 

Address information 

 

 

 

 

 

 

 

 

 

 

 

 

J8

 

P

LUG 

 

T

ERMINAL TO 

S

ENSOR 

W

IRING

 

Position  Function  Sensor 

+ 

Power 

Red 

s

 

Signal 

White 

 

GND 

Black 

 

 

 

 

 

 

Circuit Board Bottom View 





J 4  

J 8  

1   2   3 

P l u g   J 8  

To J8 

Wires to 

Sensor 

s  

P l u g   J 4  

To J4 

Wires to 

Controller 

Relay Output Board 

Bottom View 

Optional Relay Output Board 

 

It is recommended that the auxiliary  
alarm be powered separately. 

 

Use 14 – 20 

AWG 

(2.5

 

 

0.5

 MM

2

) wire. 

 

When on power the relays are energized. 

 

Relays are rated at 0.5 Amp continuous. 

N

OTE

: Auxiliary alarms should be powered from an 

independent power source separate form the 
instrument power to avoid alarm failure due to 
controller malfunction. 
All wiring must be in accordance with the 
National Code and any local governing codes. 

Содержание EX-5120

Страница 1: ...ENMET Corporation PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual Part Number 80003 092 MCN 13 011 12 20 13 EX 5120 INFRARED 0 100 LEL Sensor Transmitter Manual...

Страница 2: ...tenance Menu 10 5 3 Sensor Replacement 12 6 0 REPLACEMENT PART NUMBERS 13 7 0 WARRANTY 14 List of Figures and Tables Figure 1 EX 5120 Features 2 Figure 2 EX 5120 Mounting Dimensions 3 Figure 3 Termina...

Страница 3: ...ion and after you have received written acknowledgment of the damage from the carrier contact ENMET Customer Service for return authorization and further instructions Have your Purchase Order and Sale...

Страница 4: ...maintenance functions The switch locations are indicated by MENU and SELECT A magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and then removing...

Страница 5: ...property or personnel when choosing locations of sensor transmitters Also take into consideration environmental factors when deciding on S T location Avoid locations where the S T may be damaged by l...

Страница 6: ...J4 plug then attach to J4 terminal Connect the wires from the sensor to the supplied J8 plug then attach to the J8 terminal See Figure 3 for locations J4 PLUG TERMINAL TO CONTROLLER WIRING Position Fu...

Страница 7: ...n the S T Do Not apply power to the S T without the cover in place Sensor Transmitter Enclosure Cutaway View Printed Circuit Board PCB Display Overlay Display Overlay Screws 2 places Display Overlay S...

Страница 8: ...ansmitter configuration and calibration condition the furthest right character in the display may flash a letter indicating the instrument status Consult ENMET Distributor or ENMET Corp 4 1 Start up 4...

Страница 9: ...splay indicates Alarm 1 Set point Tap the magnet over the MENU button Display indicates Alarm 2 Set point Tap the magnet over the MENU button No Function for the SELECT button in this mode Display ind...

Страница 10: ...de Measurement of target gas Hold the magnet over MENU switch for 2 5 seconds to enter the Maintenance Menu The Power Fault LED will flash Green Red to indicate the EX 5120 is in Maintenance Mode To e...

Страница 11: ...0 9 Oxygen is used to provide a fresh air reference or Zero point for the calibration Another cylinder is used to provide the Span reference point for calibration Depending on the instrument calibrati...

Страница 12: ...il Exit appears then tap the SELECT switch Check span gas and repeat calibration NOTE Some software revisions require the SELECT switch be tapped to accept the signal 7 Calibration is complete 5 2 3 E...

Страница 13: ...set point The MENU switch changes digit indicated by underscore cursor The SELECT switch locks underscored digit and moves to next digit To return to Normal Gas Display Tap MENU switch until EXIT is d...

Страница 14: ...or PC Board Assembly Reassemble the sensor housing After the new sensor has been installed it is suggested to allow the sensor to stabilize for several minutes A Factory calibration must be performed...

Страница 15: ...ropane 0 100 LEL 03056 008 Consult ENMET Distributor or ENMET Corp for additional ranges Regulator Assembly for 17l cylinders 02506 004 Magnet 50030 001 Calibration Sampling Adapter 03700 034 Calibrat...

Страница 16: ...damage caused by the improper use of the product The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others...

Страница 17: ...processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a minimum...

Страница 18: ...erms K COD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Card C...

Отзывы: