www.engproducts.com
5401 SMETANA DRIVE | MINNETONKA, MN 55343
P
800.336.1976 | F 800.336.2801
INSTALLATION INSTRUCTIONS
Safety Instructions
1. Use the hook to support the luminaire, not the electrical cord!
2. The luminaire is pre-wired at the factory to operate at 120 volts.
3. The luminaire is equipped with a multi-tap ballast for 120V, 208V, 240V and 277V applications. The leads 208V, 240V and 277V are capped off.
4. Never replace the Type-O lamp with the power supply “ON”.
5. All work must be performed by a qualified Electrician.
6. This luminaire must be installed in accordance with the requirements of the 2017 National Electrical Code and must comply with all state and
local electrical codes.
7. Use only Type-O specified replacement lamps.
Double check all wiring connections. Ensure that the proper luminaire voltage leads have been selected to
match the supply voltage. Improper wiring may damage the ballast and void the warranty.
WARNING
Connecting the Luminaire to a Power Supply other than 120 Volts
1. Remove the two (2) screws that hold the Access Cover to the luminaire.
Disconnect and remove the factory supplied power cord (see Figure 1).
Cap the unused supply cord hole.
2. Route the incoming power cord (not supplied) through the knockout hole in the
Access Cover using a strain relief bushing or conduit fitting (not supplied).
3. Remove the caps from the required leads and make sure to label the wires,
then match the voltage of the luminaire supply wires as required.
4. Make all wiring connections.
5. Cap off all unused luminaire wires.
6. Re-attach the Access Cover to the enclosure.
7. Hang the luminaire as directed.
Figure 1. Reconfiguring the Power Supply.
Power Cord
Access Cover
.75” Knockouts
208V, 240V, and
277V Ballast Leads
TIGER™ 400 HID Temporary Luminaire
Part Number 15702: TIGER 400 HID Temporary Luminaire: 400-Watt Type-0 Metal Halide Lamp, 6-Foot Cord,
Safety Cage and Lamp Guard.
NOTE:
Complies with the 2007 Energy Independence and Security Act (EISA) and meets the requirements of the 2017 National Electrical Code (NEC): Articles 410.62 (C) (1 and 2),
410.104 (A), 410.122, 410.130 (F) (5) and 590.4 (F).
Engineered Products Companies TIGER 400-Watt Metal Halide Light Fixture (MHLF) complies with the Department of Energy (DOE) February 2014 updated rule for stringent
energy conservation standards for Metal Halide Fixtures (MHLFs) and its February 10, 2017 implementation date.
CAUTION
Risk of
Electric
Shock
• TO BE INSTALLED BY A QUALIFIED ELECTRICIAN
• WARNING:
ELECTRICAL SHOCK HAZARD
• MAKE SURE THAT THE POWER IS “OFF” AT THE CIRCUIT BREAKER BEFORE PROCEEDING
• ULTRAVIOLET AND INFRARED RADIATION IS EMITTED FROM METAL HALIDE LAMPS
• POSSIBLE SKIN OR EYE IRRITATION CAN RESULT FROM EXPOSURES EXCEEDING 15 MINUTES
• DO NOT STARE AT EXPOSED LAMP IN OPERATION
• DO NOT REMOVE THE LAMP FROM LUMINAIRE UNTIL IT HAS COOLED
• NEVER HANDLE THE LAMP WHEN IT IS OPERATING
• RECOMMENDED FOR USE IN “HIGH BAY” APPLICATIONS ONLY! ENGINEERED PRODUCTS
COMPANY DEFINES HIGH BAY AS GREATER THAN 30-FEET OFF THE FLOOR
Part Number 15752: Replacement Type-0 400-Watt Metal Halide Lamp: Pulse-Start