Engineered Comfort 35FH Series Скачать руководство пользователя страница 4

F a n   C o i l   U n i t s

www.engineered-comfort.com

Houston, Texas

Tel: 281-590-1172

Fax: 281-590-3086

Dimensions are in inches (mm).

Toronto, Canada

Tel: (416) 744-3300

Fax: (416) 736-4262

Page 4 of 4

10/18  EC-35FH-37FH-INST

Start Up

General

Before beginning any startup operation all start up personnel should 
familiarize themselves with the unit options, accessories, and 
control sequence to understand the proper system operation. All 
personnel should have a good working knowledge of the general 
start up procedures along with the appropriate start-up guides 
and balancing guides available. The building must be completely 
finished with all doors, windows, interior walls and insulation in 
place. The entire building should be as complete as possible before 
beginning any system balance. Before any startup operations occur 
a final visual inspection should be made of the system. Once it has 
been established that the installation is correct, complete, and no 
foreign articles have been left in the units or other areas the startup 
procedure can begin. 

Cooling/Heating System

Before the water system is started and balanced the chill/hot water 
systems should be flushed to remove any contaminant that might 
collect in the system during construction. All unit service valves 
must be in the closed position during this operation to keep foreign 
matter from entering the unit and clogging the valves. Strainers 
should be installed in the piping mains to prevent this material from 
entering the units while they are operating. During the filling of the 
system the vent valve on top of the coil should be turned counter 
clockwise one and one-half turns so any trapped air in the coil can 
escape.

CAUTION: 

The coil air vents are not to be used to bleed the entire 

system. The main piping must have air vents installed in it where 
potential air traps could be located. Some systems may require 
repeated venting over a period of time to properly eliminate air from 
the system.

CAUTION:

 Do not exceed 350 PSIG operating pressure.

Electric Resistance Heater Assembly

Electric resistance heaters typically require no normal periodic 
maintenance when unit air filters are changed properly. The two 
most important operating conditions for an electric heater are, 
proper air flow, and proper supply voltage. High supply voltage or 
insufficient airflow will cause the heater strips to cycle on the high 
side. The strip heaters are equipped with automatic reset switches 
to prevent overheating of the unit. Once the switches are tripped the 
heater will remain off until it cools past the lower set point for the 
trip switches to reset. If the trip switches actuate, the system should 
be checked and any condition causing the high limit cutout must be 
corrected immediately.

Normal Operation and Periodic 

Maintenance

ALL POWER MUST BE SWITCHED OFF BEFORE SERVICING.

General

Each unit on a job will have its own unique operating environment 
and conditions that will dictate the maintenance schedule for that 
unit. A formal schedule and maintenance log and an individual 
unit log should be established and maintained to establish 
max performance and service life. Information regarding safety 
precautions contained in the preface at the beginning of this manual 
should be followed during any service and maintenance operations. 

Motor Blower Assembly 

Nailor uses permanently lubricated motors that do not require field 
lubrication to ensure a long trouble-free blower life. However, should 
it become necessary, the blower assemblies in these units are easily 
removable. Disconnect wiring from the control panel. Removing the 
nuts located in the top and bottom left and right corners of the unit 
discharge panel allows the blower assembly to be removed from the 
unit. To reinstall the blower assembly, repeat the removal sequence 
in reverse order, making sure to reconnect all wiring harnesses. Dirt 
and dust should not be allowed to accumulate on the blower wheel 
or housing. This can result in an unbalanced blower wheel and 
damage the wheel or motor. The wheel can be cleaned periodically 
with a vacuum cleaner and brush.

Coil Assembly 

To access coils for servicing, remove the bottom access panel of 
the blower section. Coils may be cleaned by brushing the coil face 
with a soft brush. The brush strokes should be in the direction of 
the fin never across the fin. Cleaning with a vacuum cleaner should 
follow this. If compressed air is available the coil may be cleaned 
by blowing air through the coil from the leaving air-side. Vacuuming 
should follow this procedure also. Even coils that have the filter 
changed on a regular basis still require cleaning periodically.

Filters

Return air filters should be replaced on a regular basis. The time 

interval between each replacement should be established based on 

inspection of the filter. If the replacement filters are not purchased 

from the factory, the filters used should be the same type and size 

as those furnished from, or recommended by the factory. 

Отзывы: