DJM2.4 MANUAL
34
Oct 00 R2
2.
There are two possible burners that the DJM2.4 can be applied to. Check the burner in your
unit and if necessary cut the jumper next to terminal “PV1” on the back of the control before
mounting the control.
STANDARD BURNER
(Round Burner)
- do not cut jumper.
HIGH TURNDOWN BURNER
(Rectangular)
- you must cut jumper.
NOTE:
Be aware that the position of the “CONT” pot should be considered during
parts of the set up procedure as it may make the control react slowly if set
too far CW.
3.
NOTE:
If the DJM2 is controlled by a Maxitrol series 14, Johnson TE 6000-960 discharge
sensor or DC volts applied to terminals “R and W”.
Jumper “SV to SR” to put the control into service mode, adjust combustion as per
instructions found under “
Burner Set Up
”. Remove jumper.
Set the discharge set point to desired setting.
Adjust pot 1 DCAL to match set point and D/A temperature if needed.
Adjust pot 3 CONT as described in the manual to give an acceptable temperature control
band.
4.
NOTE:
If the DJM2 is controlled by a C-TRAC2.1 or Metasys then resistor R19 should be cut
before installation. If the DJM2.4 is being controlled by a BMS signal that cannot
put out enough VA to drive the DJM2.4, resistor R19 should be cut.
If the DJM2 is controlled by a C-TRAC, Megatrac, METASYS or other BMS device that is wired
to terminals "+ and
-" then:
Set combustion as in point 3A above.
Return control to the C-TRAC
(or whatever control is attached)
by removing the jumper
“SV to SR”.
Make a call for full heat; adjust pot 6 BMSS to obtain full fire. You are at full fire when
output to the Maxitrol valve exceeds 13 VDC.
Make a call for low fire and adjust pot 2 BMSZ to just keep low fire on. When incoming
voltage on terminals "+ and -" falls below about 2.5 VDC
(5.5 ma)
the burner should cycle
off.
XVIII.
MISCELLANEOUS NOTES
Combustion Blower Speeds
DJM2 configured for the
REGULAR ROUND BURNER
.
Low fire combustion blower speed
is about 1830 RPM ±10 RPM
(30.5 Hz.) [1800 to 2000
RPM]
High fire combustion blower speed
is about 3400 RPM
Light off speed
is about 2700 RPM
DJM2 configured for the
HIGH TURNDOWN BURNER
.