DJM2.4 MANUAL
11
Oct 00 R2
7.
After the main flame has been established, the combustion blower speed may slow down to
the low fire speed
(standard round burner 1850 RPM, high turndown rectangular burner is 1250
RPM at 10:1 turndown and 1150 RPM at 15:1 turndown)
. After about 10 seconds, the pilot
solenoid contacts between DJM2 terminals "PV1" and "PV2" open and the AC power to the
pilot valve from the flame relay is turned off.
8.
After lighting, the combustion blower speed and the gas valve voltage will modulate to
maintain the required discharge temperature while maintaining proper combustion.
9.
If the heating demand is satisfied, the burner is cycled off. At this point, the combustion blower
returns to the intermediate light off speed. This is referred to as a "maintain purge mode".
(2700 RPM for the standard burner or 2300 RPM for the high turndown burner.)
NOTE:
Opening the heat switch will also cycle the burner flame off. If this occurs, the
combustion blower will be continue running for 1 to 4 minutes to cool the
burner.
10.
If at any time the combustion blower tachometer senses an insufficient blower speed, the pre-
purge timer is reset and the control logic goes to step 3.
11.
If the discharge sensor initiates another call for heat within the next 4 minutes while the
DJM2.4 is operating in its "maintain purge mode", the control logic goes to step 6 and the
burner will re-light.
12.
If there is no heat call within the 4 minute "maintain purge mode", the combustion blower is
shut off. If another call for heat is initiated at this time, the control logic returns to step 1.
Service Mode
When DJM2.4 terminals "SV" and "SR" are jumpered, the DJM2.4 is placed into service mode. An
irregular flashing on the
(centre)
LED Heat Call light indicates Service mode on the DJM2.4. When in
service mode, the burner will be brought on and held on and will not cycle off. Adjusting pot 4
“SER” will allow complete manual control of the burner-firing rate from low to high fire. This
operation is useful for troubleshooting or burner set-up.
Important Usage Notes Regarding the Service Pot and Service Mode
1.
The unit must not be left in the service mode.
2.
When leaving the unit make sure to remove the jumper from terminals SV and SR.
3.
When in service mode, the burner will not cycle off.
4.
An irregular flashing of LED 2 indicates that the DJM2 is in the service mode.
5.
The supply fan contactor has to be powered on.
X.
TEMPERATURE CONTROL – GENERAL OVERVIEW
The DJM2.4 is not
designed
for use with any application requiring reset signal such as Room,
Ambient, or BMS Reset. It will only accept one temperature-controlling signal at a time.
The DJM2.4 control signal can come from
ONE
of the following sources.
Maxitrol TS114 sensor and TD114 set point.