MOTOR LUBRICATION
Refer to motor manufacturer for lubrication recommendations.
On motors having grease drain plugs, remove the plugs and operate the motor for 15 minutes before
replacing plugs.
DO NOT OVER GREASE.
RECOMMENDED MOTOR LUBRICATION INTERVALS
Hours Service
Per Day
Up to 7.5 HP
Up to 5.6 kW
10 to 40 HP
7.5 to 29.8 kW
Over 40 HP
Over 29.8 kW
Less than 12
5 Years
3 Years
1.5 Years
More than 12
2 Years
1 Year
9 Months
NOTE: Motors that run in severe conditions should be greased as specified by the motor manufacturer.
GAS MANIFOLD
It is recommended that at least once each year the safety devices should be checked. Follow operational
check at detailed in this manual.
The Safety Shut Off Valves must be tested on at least an annual basis or as per the manufacturer’s
recommendations which ever is less.
Regulators with vent terminals must have yearly cleaning of the screen.