187
Installation instructions for professionals
Alarm
Reason
Instruction
Solution
Supply air cold
(TE-10 min)
Heat exchanger trace has
broken
A green trace circles the heat exchanger.
Check if the trace can be seen from the LTO
cell review hole. If it cannot be seen, the trace
has broken.
Change the trace
The heat exchanger trace is
lubricated so that it can slide
A green trace circles the heat exchanger.
Check from the LTO trace review hole if the
pulley is rotating even though the LTO cell is
not rotating.
Change the trace
Exhaust blower has stopped
Open the access door while the machine
is operating. The supply blower should be
rotating. In LTR model machines, press with a
screwdriver and check, if the blower starts.
Change blowers
Exhaust air filter is blocked
Open the access door when the machine is
off. Pull out the filter and check the dirtiness
of the filter.
Change the exhaust filter
Exhaust air valves adjusted
wrong
Contact the company that installed the
ventilation unit and find out if the air flow and
valves are correctly adjusted.
Contact the maintenance.
Ducts have inadequate
insulation
Check the thickness of insulation in supply
and exhaust ducts, and add insulation if
necessary.
Contact the maintenance.
The protection against
additional heating
overheating has launched.
Find out the cause for the failure and reset the
protection against overheating (® button in
the radiator).
Contact the maintenance.
TE-10 temperature sensor
is faulty
Check from the measurements menu on
the control panel if the supply temperature
measurement is off the charts.
Contact the maintenance.
The motor/gearbox in the
heat exchanger is faulty
Open the access door while the machine is
operating and listen, if the sound comes from
the LTO.
Contact the maintenance.
The LTO controller card is
faulty (EDA models)
The LTO cell is controlled by a separate
controller card that is located in the electric
box of the machine.
Contact the maintenance.
LTO pulley has separated
from the shaft
Check from LTO trace review hole if the shaft is
rotating empty and the pulley is in its place.
Tighten the screw on the pulley.
Contact the maintenance.
Hot supply air
(TE-10 max)
Fire risk
Electrical post-heating faulty
Contact the maintenance.
Water heating radiator has a
faulty control valve actuator
Contact the maintenance.
TE-10 temperature sensor
faulty
Check from the measurements menu on
the control panel if the supply temperature
measurement is off the charts.
Contact the maintenance.
Hot room air
(TE-20 max)
Fire risk
Contact the maintenance.
TE-20 temperature sensor
faulty
Check from the measurements menu on
the control panel if the room temperature
measurement is off the charts.
Contact the maintenance.
Содержание Salla eAir
Страница 20: ...20 9 13 15 11 10 14 Lisävaruste 1 2 min 12 ...
Страница 46: ...46 ...
Страница 48: ...48 2016 1254 2014 A A ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI SALLA A 40 dB 263 m3 h ...
Страница 49: ...49 Installationsanvisningar för yrkesfolk ...
Страница 50: ...50 Salla eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Страница 68: ...68 9 13 15 11 10 14 Extra tillbehör 1 2 min 12 ...
Страница 94: ...94 ...
Страница 96: ...96 2016 1254 2014 A A ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI SALLA A 40 dB 263 m3 h ...
Страница 97: ...97 Installasjonsinstrukser for fagfolk ...
Страница 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Salla eAir ...
Страница 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12 ...
Страница 142: ...142 ...
Страница 144: ...144 2016 1254 2014 A A ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI SALLA A 40 dB 263 m3 h ...
Страница 145: ...145 Installation instructions for professionals ...
Страница 146: ...146 Salla eAir Installation instructions for the ventilation unit English ...
Страница 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12 ...
Страница 190: ...190 ...
Страница 192: ...192 2016 1254 2014 A A ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI SALLA A 40 dB 263 m3 h ...
Страница 193: ...193 ...
Страница 200: ...200 ...
Страница 201: ...201 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Страница 202: ...202 ...
Страница 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Страница 207: ...207 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...