
177
Installation instructions for professionals
6
Analog input 1
%RH sensor1
Define the functionality and set the voltage for
the analog inputs 1-6 on the MD motherboard.
AI settings needs to be configured if there are
external sensors connected to the ventilation unit,
besides the two RH% and CO₂ sensors that are
preconfigured.
Analog input 2
%RH sensor 2
Analog input 3
None
Analog input 4
None
Analog input 5
CO2 sensor1
Analog input 6
CO2 sensor 2
7
Constant duct pres-
sure control
OFF
Options are ON/OFF.
Air flow setup mode Constant pressure
Selecting
Constant pressure
requires all fan power
settings to be entered as duct pressures, and the
automation will automatically maintain the duct
pressure by varying the fan speeds. Select this set-
ting if you know the required duct pressures for the
different operating modes.
Selecting
Constant speed
will allow the airflow
measurements to be made without the duct pres-
sure control. The measured duct pressures are
shown under the fan speed settings for reference,
and are automatically stored when continuing to
the next setting. After completing all fan speed
settings the constant duct pressure control is auto-
matically activated, and fan speed control will be
automatic according to duct pressures. Use this set-
ting if you don’t know the needed duct pressures
for the different operating modes.
P-band
25
P-band value determines how much the fan speed
will be altered.
I-time
5 s
I-time value determines how quick the change to
the fan speed will be.
DZ
2 Pa
DZ (dead zone) is the deviation in the set duct pressure
where the controller has no effect on the fan speed.
Alarm delay for
supply air duct
pressure
200 s
If pressure deviation is greater than the set alarm
limit, an alarm will be triggered after the delay set
here.
Alarm delay for
extract air duct
pressure
200 s
If pressure deviation is greater than the set alarm
limit, an alarm will be triggered after the delay set
here.
Alarm limit
10 Pa
An alarm is triggered if pressure deviation is greater
than the alarm limit set here.
Содержание Pingvin XL eAir
Страница 20: ...20 9 13 15 11 10 14 Lis varuste 1 2 min 12...
Страница 46: ...46...
Страница 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Страница 49: ...49 Installationsanvisningar f r yrkesfolk...
Страница 50: ...50 Pingvin XL eAir Installationsanvisningar f r ventilationsaggregat Svenska...
Страница 68: ...68 9 13 15 11 10 14 Extra tillbeh r 1 2 min 12...
Страница 94: ...94...
Страница 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Страница 97: ...97 Installasjonsinstrukser for fagfolk...
Страница 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pingvin XL eAir...
Страница 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12...
Страница 142: ...142...
Страница 144: ...144 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Страница 145: ...145 Installation instructions for professionals...
Страница 146: ...146 Pingvin XL eAir Installation instructions for the ventilation unit English...
Страница 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12...
Страница 190: ...190...
Страница 192: ...192 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Страница 193: ...193...
Страница 198: ...198...
Страница 199: ...199 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Страница 200: ...200...
Страница 204: ...204 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Страница 205: ...205 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Страница 210: ...210...
Страница 211: ...211...