Installation instructions for professionals
Temperature control
Heat recovery
Heat recovery is limited during summertime, if the
outdoor temperature is over +8°C. During this the heat
exchanger is not operating if no heating request is
received.
Heat recovery is on at 100% efficiency when temperature
is lower than +8°C. This may lead to contradictions,
especially in the spring, when the sun is heating the
indoor air even though the temperature outside is still
under +8°C. The temperature limit value can be changed
from the control panel.
Cooling recovery
During the summertime power limitation, the heat
exchanger activates at full power when the outdoor air
is over 1°C warmer than exhaust air. The heat exchanger
stops, when the outdoor temperature drops below the
exhaust air temperature. This helps with maintaining the
coolness of indoor spaces.
Heat recovery anti-freezing
MD control divides the supply blower operation based on
temperature measurements, which in turn prevents the
heat exchanger from freezing. Supply blower operates
normally after freezing risk has passed. Anti-freezing
automation can be activated from the control panel.
Efficiency of heat recovery
The efficiency of the heat recovery of supply and exhaust
air is displayed in the Measurements menu of the control
panel.
Supply, exhaust, and room
temperature controls
The supply air temperature in the apartment is controlled
by the supply air control. Ventilation unit can be used
either as supply air controlled, which is when the unit
aims to keep the supply air temperature on the set level,
or as exhaust or indoor air controlled, which is when the
unit aims to keep the exhaust or indoor air temperature
on a set constant level by controlling the setting point of
the supply air controller.
The supply air controller makes sure that the temperature
does not drop or rise over the limits set in the panel. If
the outdoor temperature is less than the heat recovery
temperature limit (default value +8°C), or if the ECO mode
is active, the supply air temperature can rise over the set
temperature, if the rise is from heat recovery only.
Exhaust or indoor air temperature constant control is used
when the temperature in the whole apartment needs
to be adjusted by heating or cooling the ventilation unit
supply air. The method of control is standard in ventilation
unit models that have cooling.
If the outdoor temperature is less than the heat recovery
temperature limit (default value +8°C), or if the ECO mode
is active, the exhaust or indoor air temperature can rise over
the set temperature, if the rise is from heat recovery only.
Room temperature control requires that the unit has
either a temperature sensor (extra) connected to the
control panel or a room temperature transmitter (extra)
connected to the MD card. Indoor air temperature control
measurements must be activated separately from settings.
Heating is active when the control requests heating,
i.e. when the set temperature value is higher than the
measured exhaust air (or indoor air) temperature. Cooling
is active when the control requests cooling, i.e. when the
set temperature value is lower than the measured exhaust
air (or indoor air) temperature. Heating and cooling can be
active at the same time, if the ventilation unit is equipped
with supply air absolute humidity control (extra).
W model have a water heating coil return water check
function that activates heating if the temperature of
the return water drops too much. If the return water
temperature is still dropping, the ventilation unit will shut
down and send an alarm.
If Max. heating / Max. cooling is selected from the control
panel quick menu, efficient heating or cooling activates
momentarily. The function forces the supply air control to
its limit value and raises the blowers to the Manual boost
level.
The function will run until the temperature value set in
the control panel main screen is reached.
Содержание LTR-3 eAir
Страница 8: ...8 Kanavaliitännät ulkoilma tuloilma poistoilma jäteilma ...
Страница 20: ...20 11 13 9 12 Lisävaruste 1 2 min 10 ...
Страница 48: ...48 ...
Страница 50: ...50 2016 1254 2014 ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI LTR 3 A 45 dB 230 m3 h ...
Страница 51: ...51 Ammattilaisen asennusohje ...
Страница 52: ...52 LTR 3 eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Страница 58: ...58 Kanalanslutningar uteluft tilluft frånluft avluft ...
Страница 70: ...70 9 13 15 11 10 14 Extra tillbehör 1 2 min 12 ...
Страница 98: ...98 ...
Страница 100: ...100 2016 1254 2014 ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI LTR 3 A 45 dB 230 m3 h ...
Страница 101: ...101 Installationsanvisningar för yrkesfolk ...
Страница 102: ...102 Installeringsinstruksjoner for ventilasjonsenheten Norsk LTR 3 eAir ...
Страница 108: ...108 Kanalkoblinger utendørsluft tilluft avtrekksluft avkastluft ...
Страница 120: ...120 9 13 15 11 10 14 1 2 min 12 ...
Страница 148: ...148 ...
Страница 150: ...150 2016 1254 2014 ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI LTR 3 A 45 dB 230 m3 h ...
Страница 151: ...151 Installasjonsinstrukser for fagfolk ...
Страница 152: ...152 LTR 3 eAir Installation instructions for the ventilation unit English ...
Страница 158: ...158 Duct connections outdoor air supply air extract air exhaust air ...
Страница 170: ...170 9 13 15 11 10 14 Extra 1 2 min 12 ...
Страница 198: ...198 ...
Страница 200: ...200 2016 1254 2014 ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI LTR 3 A 45 dB 230 m3 h ...
Страница 201: ...201 Mittapiirrokset Måttritningar Måltegninger Dimensional drawings LIITTEET BILAGOR VEDLEGG APPENDICES ...
Страница 202: ...202 Sähkökytkentäkaaviot Elscheman Elektriske skjemaer Electrical diagrams Liitännät Anslutningar ...
Страница 203: ...203 Koblinger Connections ...
Страница 204: ...204 ...
Страница 205: ...205 ...
Страница 206: ...206 ...
Страница 207: ...207 ...
Страница 208: ...208 ...
Страница 209: ...209 ...
Страница 210: ...210 ...
Страница 211: ...211 ...
Страница 212: ...212 ...
Страница 214: ...214 eAir W Periaatekaavio eAir W Principschema eAir W Prinsippskisse eAir W Principle schema ...
Страница 215: ...215 ...
Страница 218: ...218 ...
Страница 219: ...219 ...