96
Parameter list
Parameter Description
Factory
setting
Note
Modbus
register
Field
setting
c1
Extract fan speed, mode 1, region: 20–100%,
step: 1%
36%
‘Away’ mode
102
c2
Supply fan speed, mode 1, control range:
20–100%, step: 1%
35%
‘Away’ mode
100
c3
Extract fan speed, mode 2, control range:
20–100%, step: 1%
56%
Home mode
52
c4
Supply fan speed, mode 2, control range:
20–100%, step: 1%
55%
Home mode
51
c5
Extract fan speed, mode 3, control range:
20–100%, step: 1%
83%
Maximum power also in the removal of
humidity and carbon dioxide
74
c6
Supply fan speed, mode 3, control range:
20–100%, step: 1%
80%
Maximum power also in the removal of
humidity and carbon dioxide
72
c7
Extract fan speed, mode 4, control range:
20–100%, step: 1%
100%
Manual boosting
68
c8
Supply fan speed, mode 4, control range:
20–100%, step: 1%
100%
Manual boosting
67
c9
Time limit for manual boosting (mode 4),
control range: 0–4 h, step: 1 h
2 h
Setting the time limit 0 h prevents
the use of mode 4 and activates the
3-speed external control
66
c10
Extract fan speed, fireplace/range hood
mode, control range: 20–100%, step: 1%
30%
55
c11
Supply fan speed, fireplace/range hood
mode, control range: 20–100%, step: 1%
50%
54
c12
Time limit for fireplace mode/selection of
range hood, control range: 0–15 min, step:
1 min
10 min
Setting time limit 0 min replaces the
fireplace mode with the range hood
mode.
56
c13
Heat recovery defrosting, on/off
Off
Coil 55
c14
Maintenance reminder interval 4 or 6
months
4
Register value in days
538
c15
CHG/AGH pre-heating and AGH precooling,
on/off
On
Coil 58
c16
CHG/AGH outdoor temperature TE01, below
which pre-heating is used, control range:
0–10°C, step 1°C (for pre-heating)
5°C
592
c17
CHG/AGH pre-heating is not in use when the
outdoor air temperature (TE01) rises above
value (c16) + (c17), control range: 1–5°C, step
1°C
1°C
593
c18
CG cooling or CHG pre-cooling, on/off
On
Applies to CG and CHG heat
exchangers
Coil 52
c19
Outdoor temperature TE01, above which
pre-cooling/cooling is allowed
17°C
164
c20
AGH outdoor temperature, above which the
earth duct is used, control range: 15–25°C,
step 1°C, (for pre-cooling)
20°C
629
c21
AGH pre-cooling is not in use when the
outdoor air temperature (TE01) drops below
value (c20-c21), control range: 1–5°C, step
1°C
2°C
630
c22
Temperature setting for air temperature
after the electric pre-heating, control range:
–10...–20°C, step: 1°C
–15°C
591
c23
Boosted operation for the removal of
humidity, on/off
On
Coil 19
Содержание Alta eWind
Страница 13: ...13 Ammattilaisen asennusohje Wifi moduulin asennus 1 2 A B A 3 4...
Страница 24: ...24...
Страница 26: ...26 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 27: ...27 Ammattilaisen asennusohje...
Страница 28: ...28 Alta eWind Installationsanvisningar f r ventilationsaggregat Svenska...
Страница 39: ...39 Installationsanvisningar f r yrkesfolk Installation av Wifi modulen 1 2 A B A 3 4...
Страница 51: ...51 Ammattilaisen asennusohje...
Страница 53: ...53 Ammattilaisen asennusohje 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 54: ...54 Installeringsinstruksjoner for ventilasjonsenheten Norsk Alta eWind...
Страница 76: ...76...
Страница 78: ...78 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 79: ...79 Installation instructions for professionals...
Страница 80: ...80 Alta eWind Installation instructions for the ventilation unit English...
Страница 91: ...91 Installation instructions for professionals Installation of the Wifi module 1 2 A B A 3 4...
Страница 103: ...103 Ammattilaisen asennusohje...
Страница 105: ...105 Installasjonsinstrukser for fagfolk 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...