![enervent Alta eWind Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/enervent/alta-ewind/alta-ewind_installation-instructions-manual_2411660089.webp)
89
Installation instructions for professionals
All Enervent ventilation units must be drained. When
air cools down (condenses), condense water forms. For
example in winter time when humid inside air meets cold
heat recovery wheel, or when warm outside air meets the
cooling coil in the ventilation unit (if applicable).
Draining condensate water
•
The condensate water should be led in a falling, at
least Ø15 mm pipe, through a water trap to a floor
drain or such.
•
The pipe must at all times lie lower than the
condensate water drip pan / condensate water
connection of the ventilation unit.
•
There must not be any longer horizontal sections on
the pipe.
•
The condensation drain pipe must be insulated if
mounted in spaces where freezing can occur.
•
Only one water lock is allowed for each condensate
water drain.
•
If the unit is equipped with more than one condense
water drains, each one must have a water lock of its
own.
•
There is underpressure in the ventilation unit. We
recommend a height difference of (A) 75 mm, or at
least the underpressure divided with 10 in millimeters
(i.e. 500 Pa under pressure -> 50 mm), between the
unit drain and the water lock drain.
The condense water drain must not be directly
connected to a sewer pipe.
CAUTION
•
We recommend that the height of backwater in the
water lock (B) is 50 mm, or at least the underpressure
divided with 20 in millimeters (i.e. 500 Pa under
pressure -> 25 mm height of backwater). The above
also applies to duct coils for cooling mounted in the
outside air duct or extract air duct.
•
There are over pressure inside duct coils mounted
in the supply air duct. We recommend the height
difference (A) between the duct coil drain and the
water lock drain is 25 mm. The water lock height of
backwater (B) must be 75 mm, or at least the over
pressure divided with 10 in millimeters (i.e. 500 Pa
under pressure -> 50 mm).
•
The water lock must be filled with water before
starting up the unit. The water lock might dry up
if water is not accumulated in it. If this happens,
air might get into the pipe and hinder water from
entering the water lock, which might result in an
irritating ”bubbling” sound.
•
The functionality of the water lock must be checked
every year before the heating season and also in the
spring if the ventilation unit is equipped with cooling.
A
B
Содержание Alta eWind
Страница 13: ...13 Ammattilaisen asennusohje Wifi moduulin asennus 1 2 A B A 3 4...
Страница 24: ...24...
Страница 26: ...26 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 27: ...27 Ammattilaisen asennusohje...
Страница 28: ...28 Alta eWind Installationsanvisningar f r ventilationsaggregat Svenska...
Страница 39: ...39 Installationsanvisningar f r yrkesfolk Installation av Wifi modulen 1 2 A B A 3 4...
Страница 51: ...51 Ammattilaisen asennusohje...
Страница 53: ...53 Ammattilaisen asennusohje 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 54: ...54 Installeringsinstruksjoner for ventilasjonsenheten Norsk Alta eWind...
Страница 76: ...76...
Страница 78: ...78 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...
Страница 79: ...79 Installation instructions for professionals...
Страница 80: ...80 Alta eWind Installation instructions for the ventilation unit English...
Страница 91: ...91 Installation instructions for professionals Installation of the Wifi module 1 2 A B A 3 4...
Страница 103: ...103 Ammattilaisen asennusohje...
Страница 105: ...105 Installasjonsinstrukser for fagfolk 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI ALTA A 44 dB 216 m3 h...